Daikin VRV4 | Monitoring Function and Field Setting | check error code history

Sdílet
Vložit
  • čas přidán 25. 08. 2024
  • Brand : Daikin VRV4
    model : RXQ8TY1/RXQ14TY1
    How to check error code history at outdoor unit, using monitor mode.
    Monitoring Function and Field Setting
    Mode 1
    [1-17]=show the latest error
    [1-18]=show the error code which occurred 1 time before current error code.
    [1-19]=show the error code which occurred 2
    time before current error code.
    When the latest error codes were reset by accident on an indoor unit user interface, they can be checked again through this monitoring settings. Detailed information about error code can be consulted in the service manual of this unit.
    please subscribe my CZcams channel
    / bonmj
    #bonmj #daikin #vrv

Komentáře • 57

  • @BonMj
    @BonMj  Před 2 lety +1

    Thanks wacthing my video, please like, share and Subscribe 🙏🙏

  • @truthmatters6719
    @truthmatters6719 Před rokem +1

    Loved the song at the end although I don't understand anything it says.

  • @soulmpowered
    @soulmpowered Před 2 lety +2

    Ty I have set in many Daikin classes and I have learned more from your video in 10 minutes . You should teach.

  • @goparismail9727
    @goparismail9727 Před 2 lety +1

    thanks bon MJ sukses selalu ilmu bermanfat berbagi ilmu buat semua dunia teknisi AC VRV

    • @BonMj
      @BonMj  Před 2 lety

      Terima kasih master🙏

  • @bahribahri228
    @bahribahri228 Před rokem +2

    Trimaksih mistersdari didik Surabaya Jawa timur Indonesia🙏🙏🙏👍👍👍❤️😀

    • @BonMj
      @BonMj  Před rokem

      Terima kasih master🙏

  • @electrolatif
    @electrolatif Před rokem +1

    Mr Bon he like Turkey, i can tell from the music 🤣🤣🤣

  • @kashibaba521
    @kashibaba521 Před rokem +1

    Sir bon make A video on DIP switching of vrv machine

  • @josequintero9850
    @josequintero9850 Před 11 měsíci +1

    Exellent good check

  • @satechengineeringservices31

    Thank you Sir. Kindly make a video about the checking of Inverter Board!

  • @VinodKumar-ix7rt
    @VinodKumar-ix7rt Před rokem +1

    Nice information sir!

  • @brandonle4930
    @brandonle4930 Před 2 lety +1

    Thank you Mr Bon!

  • @alanwong2761
    @alanwong2761 Před 2 lety +2

    Hi Bon 1st error code means the latest error code isn’t?

  • @peramaraj2763
    @peramaraj2763 Před 2 lety +1

    Very useful your latest update the video

  • @alanwong2761
    @alanwong2761 Před 2 lety +1

    Mr Bon thanks for your useful technical skill guidelines with clearly content’s 👍👍👍

    • @BonMj
      @BonMj  Před 2 lety

      Thanks

    • @kooldoodzmark5947
      @kooldoodzmark5947 Před 2 lety +1

      @@BonMj need help may remote of vrv 4 is cant change temperature model BRC1C61 i see the image under centralized control how to turn off the centralized control thanks

    • @BonMj
      @BonMj  Před 2 lety

      @@kooldoodzmark5947 you need go to crc change the setting

    • @kooldoodzmark5947
      @kooldoodzmark5947 Před 2 lety

      @@BonMjwhat i needed to change? thanks

  • @matazglb5346
    @matazglb5346 Před 2 lety +1

    Boss.......Thanks so much

  • @SM-jm1gv
    @SM-jm1gv Před 2 lety +1

    Hi Mr Bon and thanks for your hard work and heaps more thanks for sharing your experience ..
    I’ve got an issue with one of my VRV single phase unit it shows U9 error code on wall controller . ( one outdoor and two indoors)
    Would you give me some advice about this error code.
    Thanks

    • @BonMj
      @BonMj  Před 2 lety +1

      Check the other fcu.
      U9 is show the other indoor unit got problem.

  • @himawansutanto4382
    @himawansutanto4382 Před rokem +1

    can I get all field setting ouutdoor vrv for vrv IV

  • @osmarradansantos8483
    @osmarradansantos8483 Před 2 lety +1

    Hello Mr Bon !!! great explanation!!!
    Thanks so much 👏🏻👏🏻👏🏻👏🏻

  • @karaors8970
    @karaors8970 Před 2 lety +1

    bon school nice video bro.

  • @Kai-18v
    @Kai-18v Před 2 lety +1

    Sir bon to check error history at Mitsubishi VRF?

  • @tyronyuen_96
    @tyronyuen_96 Před rokem +1

    What then meaning of sub code?🙏🏻

  • @Karaoketone
    @Karaoketone Před rokem +1

    hello mister Bon, may I ask to share the pdf file which contains how to check outdor errors and the error code file for Daikin VRV? greetings from Indonesian technicians and cold greetings

  • @rightandrealinformation6384

    Hello sir, 1,which time required test operation. 2, what is 2-88 settings. 3, 2-38 means compressor emergency settings but which situation use this setting.

    • @BonMj
      @BonMj  Před 2 lety

      1)when replace pcb,compressor or ...etc
      2(2-88) not sure.(please share me more infor)
      3)(2-38)emergency setting like,multi outdoor unit, you need to by pass one of the faulty cu for temporary use.
      Or master unit got two inverter compressor, one of the compressor faulty,you can by pass one compressor for temporary use.

    • @rightandrealinformation6384
      @rightandrealinformation6384 Před 2 lety +1

      @@BonMj 1, sir, scroll compressor pumping checking possible please, and which method to check pumping good and bad. 2, Sir 2-88 gathering detailed refrigerant information during test operation. Please you make video this setting.

    • @rightandrealinformation6384
      @rightandrealinformation6384 Před 2 lety +1

      @@BonMj sir, how I confirm my setting mode is done?

  • @kentbalolong1260
    @kentbalolong1260 Před 2 lety +1

    sir bon i have encounter the error code E5-02..can you please help me..what i do to fix this error problem..thank you and godbless..from philippines.

    • @BonMj
      @BonMj  Před 2 lety

      Hi.
      E5 check inverter pcb and inverter compressor

  • @ashfaqansari6145
    @ashfaqansari6145 Před 2 lety +1

    Ye kis cheeez ka code hota h kin c machine h ye

  • @asangajayalath1665
    @asangajayalath1665 Před 4 měsíci +1

    Lc 30. What can do

    • @BonMj
      @BonMj  Před 4 měsíci

      Check main cu inverter pcb and main pcb

  • @ferdiaslan7809
    @ferdiaslan7809 Před 2 lety

    It only shows my previous registered code, can we learn the new fault codes with this method?

    • @BonMj
      @BonMj  Před 2 lety

      Latest error code is [1-17]

  • @vijaygani1179
    @vijaygani1179 Před 2 lety +1

    What is mean by sub code -02?

    • @BonMj
      @BonMj  Před 2 lety

      E5-02/JA-09
      Normally -02/-09 mean slave cu got problem

  • @ferhataslan9269
    @ferhataslan9269 Před 2 lety

    Hello boss how we will learn the correct fault from the outdoor unit ?

    • @BonMj
      @BonMj  Před 2 lety

      Latest error is [1-17]

  • @ferhataslan9269
    @ferhataslan9269 Před 2 lety

    And wich one is the true fault 1-17 or 1-18 or 1-19 ? İf you give answer ı will be happy boss

  • @MrRandyj72
    @MrRandyj72 Před 2 lety +1

    Hey Bon I'd love you to join our Facebook group specifically for VRV VRF tech talk...