Diagnosing Daikin E5 Error

Sdílet
Vložit
  • čas přidán 5. 09. 2024
  • HVAC⎪HVACR⎪REFRIGERATION VIDEOS
    In this video I diagnose what's wrong with a Daikin Air Conditioner displaying an E5 fault code.
    Marac Services Pty Ltd
    Located in Sydney.

Komentáře • 40

  • @craigladewig3158
    @craigladewig3158 Před 2 měsíci +4

    Friday also had an RX50 with E5 error code - no refrigerant in system, windings measured fine - compressor had seized.

  • @MagandRocky
    @MagandRocky Před 2 měsíci +5

    The two screws floating around in the bottom of the board enclosure are meant to attach the heatsink to the board along with thermal paste, if the screws aren't installed and new paste wasn't applied that replacement board never had a chance.

    • @J.k313
      @J.k313 Před 2 měsíci +1

      The top right screw had seat sink on the threads. How the previous tech didn't see that is wild

    • @maracservices
      @maracservices  Před 2 měsíci +4

      As soon as I saw those screws I knew exactly where they were from. Like you said, they’re the ones that screw the board down to the heatsink. You make a good point about the thermal paste, there is a good chance it wasn’t applied and even if it was, it probably isn’t a good contact. I replaced that unit today so I actually have this old unit in the back of my van as we speak so I can see if thermal paste was applied.

    • @maracservices
      @maracservices  Před 2 měsíci

      @@J.k313 crazy stuff!

    • @chetmyers7041
      @chetmyers7041 Před 2 měsíci

      @@maracservices Please give us a report on the thermal paste.

  • @robalexander7348
    @robalexander7348 Před 2 měsíci +1

    A interesting fault Mitchell, i look forward to the next episode 🤔

  • @kamalhamdi6739
    @kamalhamdi6739 Před 2 měsíci

    شكرا على المعلومات القيمة والشروحات خالد من المغرب الدار البيضاء متعلم مبتدىء

  • @HHK1090
    @HHK1090 Před 2 měsíci +1

    Love the videos Mitch. Learning a lot, thank you. Keep them coming please 👍

    • @maracservices
      @maracservices  Před 2 měsíci +1

      Thanks mate. I think you will like the next one then. Cheers

    • @HHK1090
      @HHK1090 Před 2 měsíci +1

      @@maracservices Can’t wait to see it. Big fan from the UK.

  • @jamesmccann8896
    @jamesmccann8896 Před 2 měsíci +1

    @maracservices
    Hey mate!
    The 7 on the remote is actually a T for test!
    With an e5 fault the high chance of compressor seizure with your failed board, good call with the condemn of unit
    Would have been good to see if you had a strong insulation resistance reading or not

  • @craigladewig3158
    @craigladewig3158 Před 2 měsíci +2

    Problem with this scenario , you now quote client on new inverter PCB because compressor windings measured good. Client gives go ahead for new inverter PCB. You install new PCB only to find compressor has seized. Now Daikin wont return the PCB as it has been installed and client has to fork out the cash for compressor. At this stage it would have probably been more cost effective to install new unit with 1 year warranty. I always quote replacement of compressor + inverter PCB vs new unit.

    • @maracservices
      @maracservices  Před 2 měsíci

      I get what you’re saying. You’ll be happy to know I replaced the entire unit on the Saturday just past.

    • @dalebaker1529
      @dalebaker1529 Před 2 měsíci

      I would do the same thing Craig
      You never get any thanks from anyone by faulting the pcb then ordering them come back to replace the part to find out it’s another part that’s in fault also
      Would always advise to replace the whole outdoor unit which comes with warranty

    • @glenjones4404
      @glenjones4404 Před 2 měsíci

      Very true with all inverter compressors as damned if you do damned if you don't its a proper catch scenario
      I would quote for new out door as long as you can get the outdoor as they change to a new aircon model so then it's a new whole install and like he said it looks like it's had a new board in it's past or someone has been looking at it !!!
      I prefer working on refrigeration to be fair and only installing air-conditioning because even advice off Daikin and they say it's the board but it could be the inverter compressor wtf as you have to tell the customer ffs which doesn't sound reassuring 🤬

  • @jixia676
    @jixia676 Před 2 měsíci +1

    Hi, Mitch. Have you seen a faulty inverter board and a seized compressor at the same time?

    • @maracservices
      @maracservices  Před 2 měsíci

      I have not, only one or the other to be honest .

  • @GeneralAvitation
    @GeneralAvitation Před 2 měsíci +1

    its nice to see an old girl every now and then.
    Whats the difference between the FTXS60FVMA and FTXS60GVMA i Have both and for the life of me i can't tell.

    • @maracservices
      @maracservices  Před 2 měsíci +1

      They’re the same just manufactured at different times. I can confirm they have the same cover and evaporator and I assume everything else is identical.

    • @GeneralAvitation
      @GeneralAvitation Před 2 měsíci

      @@maracservices yeah the only notice that the outdoor unit has a different Daikin inverter logo it took me a while to notice

    • @maxd4968
      @maxd4968 Před 2 měsíci

      @@GeneralAvitation I have a ftxs60bvma and it is quite different to this

    • @GeneralAvitation
      @GeneralAvitation Před 2 měsíci

      @@maxd4968 yeah the bvma and jvea was made way earlier than these they were one of the first types if daikin inverters they were replaced to fix the bad inverter design and the fact that most of them still used r22

  • @jimmyteesahn
    @jimmyteesahn Před 2 měsíci +1

    Is that a daikin specific inverter checker? I have a refco brand, not sure on its compatability with different brand units though.

    • @maracservices
      @maracservices  Před 2 měsíci

      It’s all good, yours will work with everything. I bought mine from Daikin but they’re all the same. Mine doesn’t have any branding on it.

    • @craigladewig3158
      @craigladewig3158 Před 2 měsíci

      I have Refco checker and works fine

  • @Ahsan-zh2ou
    @Ahsan-zh2ou Před 2 měsíci +1

    Hi Mitch, how many years is warranty for changing parts.pcb board etc

    • @maracservices
      @maracservices  Před 2 měsíci +1

      I honesty don’t know what the manufacturers warranty is. A lot of manufacturers don’t warrant it once the packet is opened and I’m not even kidding haha.
      I think they’re covering themselves from hacks incorrectly installing parts and incorrect diagnosing. That’s not the consumers issue though because if the part doesn’t work from incorrect diagnosis then the air con repairer will wear that. So it’s important for the repairer to be pretty confident before buying parts.
      I think most air conditioning companies give 12 months warranty on their work.

    • @craigladewig3158
      @craigladewig3158 Před 2 měsíci

      @@maracservices I don't do warranty on inverter boards unless the supplier does warranty

  • @dalebaker1529
    @dalebaker1529 Před 2 měsíci

    Daikin’s will keep you in a job for life
    Over priced units ,the quality has gone down hill massively in the last 15 years
    Would always advise my customers to go Mitsubishi electric

  • @ameernoureddine5244
    @ameernoureddine5244 Před 2 měsíci +1

    Hey Mitch how do we get one of those tools?

    • @maracservices
      @maracservices  Před 2 měsíci +1

      I bought mine from Daikin however you can buy them online. Just search inverter checker. 👍🏻

  • @lokmangoksal7970
    @lokmangoksal7970 Před 2 měsíci

    Dostum tesekkrler meslektasiz turkiyeden yaziyirum videolarini turkce alt yazi yaparsan iyi olur

  • @USA-GreedyMenOfNoIntegrity
    @USA-GreedyMenOfNoIntegrity Před 2 měsíci

    You know you have a low quality units when the data plate is a label and is peeling off at 10 yrs…all units nowadays.
    Did you check communication?
    Install surge protector.

    • @maracservices
      @maracservices  Před 2 měsíci +1

      This unit was definitely over 15 years old. I couldn’t check for communication because the outdoor board was dead. I replaced the entire unit on Saturday

  • @technicsortechniques6373
    @technicsortechniques6373 Před 2 měsíci

    appareil photo
    e5 mechanical compressor lock possible to turn off the device is closed electrical switch in off mode in more than 6 hours after turning on your device it was working.

  • @richardbartlett6932
    @richardbartlett6932 Před 2 měsíci +1

    just swap out the outdoor unit. This board swapping is the road to hell. I've got a 2016 12.5kw unit with a bad board and I won't just swap boards. Its new condenser or nothing from me..
    Been bitten too many times by Daikin to play those games. Esp when the price of parts+ time+ no warranty fitting matches the cost of a new outdoor unit with warranty.

    • @maracservices
      @maracservices  Před 2 měsíci

      @@richardbartlett6932 I have a genuine question, where do you get an outdoor unit for older models? I’d love to change the whole outdoor. That would be amazing, just as far as I knew that wasn’t an option. Daikin only stock current models (as far as I’m aware).

  • @user-gk2ck4pr4g
    @user-gk2ck4pr4g Před 2 měsíci

    In the case of Japan, only certain people can get checkers.
    So I connected three analog testers in parallel and made an original checker😂