Faulty circuit breakers could be a fire hazard

Sdílet
Vložit
  • čas přidán 28. 08. 2024

Komentáře • 27

  • @Calico5string1962
    @Calico5string1962 Před 7 měsíci +1

    Another huge issue with these panels is the lack of a "main" breaker to protect the busbar and overall loading of the panel & feeder conductors.
    As an electrician (40+ years, retired but still doing "side work") I've come across these panels in several older homes, over the years.
    I've replaced a few, but sometimes the homeowner can't (or doesn't want to) afford the replacement, despite the potential danger.
    Thankfully, with the many videos on CZcams, which document the problems & dangers of these FPE panels, people are starting to wise-up.
    I just recently replaced an FPE panel in a home built in the early 70's. The panel & breakers looked great. But a home inspector flagged it, and it resulted in the prospective buyers backing out of the purchase (that's when I got the call to replace).
    Thanks for posting (yes, I know it's a 9 year old video! But still...)

  • @TheChipmunk2008
    @TheChipmunk2008 Před 6 lety +6

    Stab Lok are well known for this and have been for 30 yrs

  • @samsquires2877
    @samsquires2877 Před 5 lety +6

    Replace with Square D QO end of story.

    • @ironmartysharpe8293
      @ironmartysharpe8293 Před 4 lety +1

      You got that right , Whenever I change out a breaker panel , I only use the Square D QO panel , Nothing else

    • @blazertracer1
      @blazertracer1 Před 3 lety +1

      Exactomundo QO is the only panel I will use. 66 yrs of being around proves that the QO is the best.

  • @dimitriberozny3729
    @dimitriberozny3729 Před 7 měsíci

    My Dad was an electrician from the late 1930’s till the 1980’s,he was NEVER a fan of any type of circuit breakers! He liked fuses best! NEC and insurance companies have everything backwards!!

  • @jimhumphreys3846
    @jimhumphreys3846 Před 6 lety +6

    This news clip says it started in the 80's. That is majorly wrong. I have seen them from the 60's and 70's do the same thing. What they need to show is a short circuit. Unlike an overload, which will most the time eventually trip. A short will not and you have a welder. This is more dangerous than an overload. I have found many FPE breakers that actually trip at lower amps than rated. Found several 20 amp bkrs tripping at 16 and 17 amps.

    • @cherrysdiy5005
      @cherrysdiy5005 Před 4 lety

      I have heard that any circuit breakers will trip when 80% ampacity has been reached.

    • @yomomma9070
      @yomomma9070 Před 2 lety +1

      Yes a short circuit has several thousand amps flowing. I too have seen failure to trip with a short. Not just FPE but also Zinsco and GE.

    • @dimitriberozny3729
      @dimitriberozny3729 Před 7 měsíci

      @@yomomma9070Read my latest comment about my Dad being an electrician and hating circuit breakers!!

  • @didicoles1233
    @didicoles1233 Před 2 lety +1

    wish i known this before my house fire in 2016

  • @MichaelBrown-pv3tv
    @MichaelBrown-pv3tv Před 3 lety +1

    I wish he had compared a newer Stab Lok , after the deception had been found and corrected. The Challenger ,American , or Federal Pioneer might have shown positive results. If you think other brands do not melt and cause fires , just Google a few other brands. Yes , the brown ones and the orange handle ones without the little white dot might have been tested deceptively , but after that , was there rally anything wrong with them?

  • @MasterTheNEC
    @MasterTheNEC Před 7 lety +4

    Just remember....the FPE did end up tripping well before a fire started or the breakdown of the insulation. Very important facts to remember. I will let you decide.....but as stated their are many options like listed replacement circuit breakers that do work in the FPE panel and have been tested. This allows for just the replacement of the circuit breakers (not the main). This is viable if the total # of CB's are 20 or less. If more than 20 cheaper to simply replace if that is your option...Just some FYI

    • @BenjaminEsposti
      @BenjaminEsposti Před 7 lety +3

      There are at least 2 problems with these panels.
      1. The bussbar contacts (stab-lok) tend to fail and heat up. (Using an incorrect or cheap chinese replacement breaker can also cause this.)
      2. The circuitbreakers have an approximate fail-to-trip rate of about 70% to 80%, according to one study (sorry lol I don't have the source, but I'm pretty confident it is at least 70%). This is due to a defect in the construction of the breaker which causes them to jam mechanically.

    • @MasterTheNEC
      @MasterTheNEC Před 7 lety

      Benjamin Esposti I am sorry....i do no concur with your limited analysis.

    • @yosefmacgruber1920
      @yosefmacgruber1920 Před 6 lety +2

      According to the report, they tripped way too slowly. The delay was far longer than the normal start-up surge of so many devices. There is no excuse to have a trip delay that is so long, that the wires could overheat faster.

    • @RobertMarts
      @RobertMarts Před 6 lety +3

      I don't understand your devil's advocate position. Just replace the panel and move on.

    • @xenadu02
      @xenadu02 Před 2 lety

      There are multiple failure modes with these. Double pole FPEs tend not to trip both poles. Both double and single are often wildly out of spec - quality control was variable over their run. They also have problems with the lugs. And the larger size breakers have had problems "welding" contacts due to the design. They are absolutely a hazard and none of the manufacturing runs are any good. They are a fire hazard and should be replaced.

  • @retrochristmas7329
    @retrochristmas7329 Před 2 lety

    They had one job, make electric boxes

  • @Yashwin-qm1vk
    @Yashwin-qm1vk Před 3 lety

    That's y I still use a fuse at the power entry from the meter...

    • @arpc0027
      @arpc0027 Před 2 lety

      Even worse with those stupid Edison fuses. You might as well light your house on fire.

  • @aaronlowe3156
    @aaronlowe3156 Před 8 lety +1

    Fft $1500 for a $5 standard 20A single-pole breaker is absolute bullshit. For a whole panel? $140 in parts. So where in the hell did the rest of the $1,360 go? Mhm. This is why I never trust handymen. Some HVAC technicians lie & charge 1 grand to replace a part that didn't need replacing when all that was needed was a simple 24v wire to be secured.

    • @BenjaminEsposti
      @BenjaminEsposti Před 8 lety +2

      Welp they gotta make a living doing this...
      The rest of the cost is for labor, licensing, tax, etc... lol

    • @_ohmz_electric
      @_ohmz_electric Před 7 lety +4

      Aaron Lowe that's the cost for the entire panel change over I believe.

    • @link52j
      @link52j Před 6 lety

      Aaron Lowe 1500 replaces with permits and labor included plus the parts that actual company only gets $500 usually