HVAC TROUBLESHOOTING | CONTROLS METHOD

Sdílet
Vložit
  • čas přidán 23. 04. 2022
  • How to troubleshoot a HVAC unit controls using schematics or wiring diagram. this video shows me troubleshoot a rooftop Aaon hvac unit heating furnace on a service call
    #d2dnyac #hvactraining #hvactraining101

Komentáře • 69

  • @TimUpgradeHVAC
    @TimUpgradeHVAC Před 6 měsíci +1

    Awesome! You are a true teacher

  • @luisgarcia-zy1kr
    @luisgarcia-zy1kr Před 2 lety +1

    I appreciate you using the schematic to fallow the wiring. These is helping me a great deal with troubleshooting.. Thanks..

    • @D2DNYAC
      @D2DNYAC  Před 2 lety +1

      Thank you for stopping by

    • @wd8557
      @wd8557 Před 2 lety +1

      He does this all the time. Because he is the man.

  • @CapsCup2012
    @CapsCup2012 Před 7 měsíci

    Good job I’m working on an Aaon this week. Makes me more comfortable reading the schematic and tracing the circuit.

    • @D2DNYAC
      @D2DNYAC  Před 7 měsíci

      Thanks for watching

  • @J2590J
    @J2590J Před 2 lety

    Love your videos, especially the diagnostics. I’m an apprentice in the trade in Connecticut your videos are great to help me learn while I’m going through electrical! Keep up the good work your videos don’t go unnoticed!

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      Thanks for watching my friend

  • @Strictly4Defense
    @Strictly4Defense Před 2 lety +1

    I enjoyed reading and following schematics with you. Subbed and looking forward to more. Keep it up.

    • @D2DNYAC
      @D2DNYAC  Před 2 lety +1

      Thanks for watching my friend

  • @wd8557
    @wd8557 Před 2 lety

    Another great trouble shooting video, you hit every point as usual I expected nothing less from you.

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      😂 thanks for watching my friend

    • @wd8557
      @wd8557 Před 2 lety

      @@D2DNYAC you know Detroit and NY have to stick together.

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      💪💪💪🏿💪🏿

  • @henryperez5404
    @henryperez5404 Před 2 lety

    Great trouble shooting, yes I like it will keep watching

    • @D2DNYAC
      @D2DNYAC  Před 2 lety +1

      Thanks for watching

  • @soloch69
    @soloch69 Před 2 lety

    Great video keep up the great work and keep the videos coming 👍🏻

  • @alvarolucio8264
    @alvarolucio8264 Před 4 měsíci

    Boa Noite parabéns belos videos, aqui no Brasil nao tem este tipo de aquecimento a gas, se tiver que fazer alguma brasagem corre algum risco? Parabéns

  • @jimmysegovia2688
    @jimmysegovia2688 Před rokem

    Thanks, partner for sharing loving all your work...

    • @D2DNYAC
      @D2DNYAC  Před rokem

      Thank you for watching my friend

  • @logankollatt2857
    @logankollatt2857 Před 6 měsíci +1

    I'm still new. But It was a red tagged, the thing you threw lol. Because the motor was bad

  • @Sc19869
    @Sc19869 Před 11 měsíci

    What is a 3 phase and a single phase. Thank you sir, for you knowledge

    • @D2DNYAC
      @D2DNYAC  Před 11 měsíci +1

      3 phases of power L1 L2 L3, three lines with power coming to the load in this case AC unit, single phase is only 1 phase of power L1 L2 or L1 and Neutral

  • @knockitofff
    @knockitofff Před 7 měsíci +1

    That motor should have a capacitor that needs to be checked, also you can try freeing up the motor by spinning it. Sometimes they seize from sitting all off season.

  • @getemjohnny
    @getemjohnny Před rokem

    Great video man. Any books you can recommend on electrical hvac troubleshooting.

  • @dioncurtiscurtis3188
    @dioncurtiscurtis3188 Před 3 měsíci

    Brotha!!!!!!!
    😄🤙🏾

    • @D2DNYAC
      @D2DNYAC  Před 3 měsíci

      I have an alliance with them 😂

  • @workaccount341
    @workaccount341 Před rokem

    Is the schematic based on when the unit is off?

  • @jetko43
    @jetko43 Před rokem

    I am having issues with some Aaon RTU's mine are not gas. Constant volume cooling units bas johnson controls. Condensor fan fuses keep tripping. Motor seems fine,traced wires no knicks

    • @D2DNYAC
      @D2DNYAC  Před rokem

      Ohm out the motor windings perhaps they are bad!

    • @jetko43
      @jetko43 Před rokem

      @@D2DNYAC will do, let you know how it goes

  • @prashanshan7125
    @prashanshan7125 Před rokem +1

    I see short here at 14.12 on cc1 & cc2 contactors N/C pins are shorted.. its on the schematic..why is that..?

    • @D2DNYAC
      @D2DNYAC  Před rokem +1

      You have to join my membership for schematics learning videos $3 per month coming soon

    • @Jason-wc3fh
      @Jason-wc3fh Před rokem

      The N/C pins are for when the unit is in the off position. It keeps the CCH1 and CCH2 energized when the unit isn't running. (Those are crank case heaters). They have constant power from the CFC line side of L2. The L1 of the CFC is going to the N/C pins to give those heaters power only when the units are not running. These are to keep refrigerant warm and in the places we want to prevent flooding and compressor damage. You needed to look closer to see the heaters in the diagram or else it would be a short.

    • @D2DNYAC
      @D2DNYAC  Před rokem

      👍

  • @jaykemm3472
    @jaykemm3472 Před 2 lety

    Nice Work. Subd

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      Thank you for stopping by

  • @luisgarcia-zy1kr
    @luisgarcia-zy1kr Před 2 lety

    Those two wires you connected to the relay for the motor ,would it matter if the were reversed ..?..

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      Good question 🙋‍♀️, no it doesn’t matter

  • @dougking7592
    @dougking7592 Před 2 lety +1

    Trouble shooting is a BIG part of the trade, and someone lets the customer know there is parts that need replaced and customer’s don’t realize that you need the combustible motor to work in summer time for Dehumidification then winter no heat , call in and find locked up inducer motor

  • @dioncurtiscurtis3188
    @dioncurtiscurtis3188 Před 3 měsíci

    I want the Skeematics to be my best friend

  • @thesilentonevictor
    @thesilentonevictor Před 2 lety +1

    So the work was buy the information was not transmitted

  • @reynaldomartinez4742
    @reynaldomartinez4742 Před 2 lety

    Great troubleshooting, i would just add alittle more caution when finding wires that have been removed by someone else. That is finding out first that those wires do go to the motor before plugging them in and energizing them and find out first if the motor is not shorted, you would create another problem if you blow the fuses.. guess we all have our own little way of doing things. Great video

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      Noted! Thanks for watching

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      @Reynaldo Martinez although one might argue that if the combustion motor was shorted or grounded then the fuses would had already been blown , also the wiring diagram clearly showed wht and blk wires going to the CB motor from the relay, now what’s the odds those same wht & blk wires and only those wires just dangling by the empty relay terminals 😂 🤷‍♂️

  • @ThermoRefrigerationLLC

    Good video .. why do you think the previous technician left the wires disconnected?.

    • @D2DNYAC
      @D2DNYAC  Před 2 lety +1

      Perhaps because the motor was bad! 😆

    • @nelsonjosorioruiz
      @nelsonjosorioruiz Před 2 lety +1

      Tech found the problem let the customer Knows but, He thinks is maybe a wrong diagnostic and call for a second opinion, a second opinion is a very expensive for the customer. Great video.

    • @D2DNYAC
      @D2DNYAC  Před 2 lety +1

      Thanks for watching

    • @ThermoRefrigerationLLC
      @ThermoRefrigerationLLC Před 2 lety

      @@nelsonjosorioruiz makes sense

  • @thesilentonevictor
    @thesilentonevictor Před 2 lety

    In my understanding any unit not running your safety switch are open 👌

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      Thanks for watching

    • @thesilentonevictor
      @thesilentonevictor Před 2 lety

      @@D2DNYAC ? Do you work for a company or for your self 🤔

    • @Jason-wc3fh
      @Jason-wc3fh Před rokem

      No. If a unit is not running, it means there's a problem that needs to be diagnosed. Your statement is about as intelligent as saying if the car won't start, it's because it's out of gas.

    • @D2DNYAC
      @D2DNYAC  Před rokem

      😂🤣

  • @brandoncorrea511
    @brandoncorrea511 Před 2 lety

    Please do more pro

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      OK thanks for stopping by

  • @dioncurtiscurtis3188
    @dioncurtiscurtis3188 Před měsícem

    We gotta chill on bashing each other as techs.
    U firmly implied the guy prior was incompetent,for you to come to the same conclusion.
    Shits mad unprofessional
    I’m a new tech striving to get better not all of us can be the skeematic king @ least not yet.

    • @D2DNYAC
      @D2DNYAC  Před měsícem

      Thanks for watching my brother

    • @dioncurtiscurtis3188
      @dioncurtiscurtis3188 Před měsícem

      @@D2DNYAC lol you’re welcome, just better not hear it again

  • @ares3914
    @ares3914 Před 2 lety

    Why is the motor no good?
    Sounds like the bearings may be bad. Is the amp draw to high? Is the fan dirty? Is it running backwards? These things you should show or you'll never find the main problem just fixing the symptom. Then a few weeks later you get a call it's not working again and you have another burnt out motor. You need to show why these parts go bad or your just changing parts. Part changers are a dime a dozen and that's why they're are so many systems shape.

    • @D2DNYAC
      @D2DNYAC  Před 2 lety +1

      @Ares the motor was Bad ( period ) and fortunately for me in this part of the world we do not repair motors unless it's a special motor!! Okay.. in addition the housing and wheel was also replaced, it all came from the supply house in 1 piece pre assembled.

    • @D2DNYAC
      @D2DNYAC  Před 2 lety

      @Ares this took me a whole 15 minutes to replace.. and no its running Prettyyy Prettay Prettay pretty good 😂😂😂

    • @Jason-wc3fh
      @Jason-wc3fh Před rokem

      If it's bad bearings, the motor needs to be replaced. If the amp draw is off, it means motor needs to be replaced. If it's running backwards when it's clearly not 3 phase, the motor needs to be replaced. All your suggestions don't make the guy a glorified parts changer, they're all the same symptoms of a part that needs to be replaced to fix the issue. No need to get down to specifics in this situation.