REF (Restricted Earth Fault) PROTECTION of Transformer Explained in Details (हिंदी Hindi)

Sdílet
Vložit
  • čas přidán 29. 12. 2018
  • To watch same video in English click on below Link.
    • REF (Restricted Earth ...
  • Věda a technologie

Komentáře • 331

  • @NiteshKumarElectrical
    @NiteshKumarElectrical  Před 5 lety +10

    Video of Difference between High Impedance & Low Impedance REF.
    czcams.com/video/apT0mVCIQgk/video.html
    हिंदी में😊

    • @chithiram8113
      @chithiram8113 Před 4 lety +1

      Sir tell me how to calculate stabilizing register value

    • @anmolmaharana5770
      @anmolmaharana5770 Před 3 lety

      Sir in my gss 132/33kv trf 40mva is tripped on ref when heavy wind and rain occurs. I want to know the reason

    • @NiteshKumarElectrical
      @NiteshKumarElectrical  Před 3 lety +1

      Hi Anmol,
      Please check the REF CT wiring from Transformer Marshalling Box to Relay end. If rain start and REF operated means ..There might be some moisture issue or loose connection of CT wiring.
      You may take shutdown of transformer and check Turret CT secondary box of transformer from where CF wiring is taken up to marshalling box for CT ckt paralling.
      Note:-But before doing anything, discuss with your senior and then take any action. This is my personal opinion and suggestions based upon my experiences.

    • @anmolmaharana5770
      @anmolmaharana5770 Před 3 lety

      @@NiteshKumarElectrical ok sir.. during rain condition other feeders tripped on O/C E/F. Is there any relation between these trips and ref?

    • @NiteshKumarElectrical
      @NiteshKumarElectrical  Před 3 lety +1

      @@anmolmaharana5770 No !
      If other feeder is tripping due to rain means, there might be fault due to trees, punctured insulators and transient faults.
      But there is no relation between feeder tripping and REF. Concept & circuit is completely different. Yeah ! REF may trip due to inrush current during charging of transformer on no load.

  • @rajuperumandla6781
    @rajuperumandla6781 Před 3 lety +1

    Nithish kumar jee you explained regarding REF protection superbly,and i hope everyone can under stood very easyly.
    Thank you for in-depth explanation sir jee

  • @ManojKumar-rm7bn
    @ManojKumar-rm7bn Před 5 lety +4

    Ab tak hajaaro bndo ki vedios dekhi meine but you have a great quality of explain a subject

  • @rajuperumandla6781
    @rajuperumandla6781 Před 3 lety +1

    Nithesh kumar jee you are explained very clearly where the REF Relay will tripped ,wether restricted zone or out of the zone .
    Thank you a lot.

  • @rajuperumandla6781
    @rajuperumandla6781 Před 3 lety +1

    Nithesh sir jee mera ku to bahut acha laga apka lecture.
    I understood very clearly.
    I think this vedio can understood every technician below the engineer level also.
    Thank you sir jee.

  • @amitprasad2588
    @amitprasad2588 Před 2 lety

    Sir aapke jitna deeply or itne sahi dhang se kisi ko samjhate nahi dekha

  • @patelchirag9530
    @patelchirag9530 Před 4 lety +4

    Keep it sir..it very detailed video that I only found nd superb explanation. Very detailed and in depth. We are respectful for your hardwork😊.

  • @memanaspak2113
    @memanaspak2113 Před 5 lety +1

    Keep it up...sir....clearly understand sir....with good graph and depth of knowledge...hats off....sir...

  • @sreeramne
    @sreeramne Před 5 lety +2

    VIDEO EXPLANATION WAS very good thanks please do continue to make more such kind of videos on different topics

  • @patakotisrinivas1918
    @patakotisrinivas1918 Před 5 lety +3

    Superb explaination bro...U r efforts are really appreciable and commendable..thanks a lot for uploading this video..

  • @Vicky_paakad
    @Vicky_paakad Před 2 měsíci

    Thanks sir, for explaining the REF protection, specially thanks for Rs, VDR calculations.

  • @rakeshkumarrajan4549
    @rakeshkumarrajan4549 Před 3 lety

    Sir your explanation very simple & good. We learnt easy way of REF protection in power transformer.
    *Thanks a lot* 🙏🙏

  • @mythbuster1993
    @mythbuster1993 Před 5 lety +2

    Very well explained... please upload more such practical videos

  • @babjibabuseelam5218
    @babjibabuseelam5218 Před 4 lety +1

    Thank you very much sir, this video any one can understand ........like that u clearly explained.

  • @MRASIFRAZA1
    @MRASIFRAZA1 Před 5 lety

    Nitesh bhai आपने बहुत अच्छे से बताया है calculation... Keep it up..

  • @ganeshsamal2906
    @ganeshsamal2906 Před rokem

    Sir transformer ki differential protection scheme pura ref wesa banaye sir please. Jitna protection hai sab banaiye. Ref pura samjh gaya sir 🙏thank you

  • @shivamtripathi2210
    @shivamtripathi2210 Před 4 lety +2

    Excellent video on REF..Please also make a video on Transformer impedance, its importance and beneficial.

  • @gaur2050
    @gaur2050 Před 5 lety +7

    Sir,
    This type of practical course will help all Electrical Engineers.
    I am really keen to meet you personally as today your way of explanation has remembered me about my great college teacher also.
    Hats off to you sir.....

    • @NiteshKumarElectrical
      @NiteshKumarElectrical  Před 5 lety +1

      Thanks Gaurav !! For understanding well through my way of explanation. Mee too want to explain Practically with core theory and many electrical engineers are getting benefits. Such comments motivate me to find time out of my busy schedule to make & deliver great content to all.

  • @MdArif-dk4ms
    @MdArif-dk4ms Před 2 lety

    sir really aap bahot achchhe se expalne karte hai chuki mai bahot logo ka video dekhta hu lekin kisi ko comment nahi karta pahli bar mai aap ko kar raha hu q ki aap bahot achchhe se samjhate hai

  • @wasimsharif8242
    @wasimsharif8242 Před 3 lety

    Bahut kuch sikha hai bhai very nice explanation

  • @amrinkagzi9207
    @amrinkagzi9207 Před 5 lety

    Very nice explaination..easily understood...Thank you sir..

  • @muthuraman6093
    @muthuraman6093 Před rokem

    Excellent 👌
    best wishes🎉
    From Sweden

  • @petpujo2220
    @petpujo2220 Před 3 lety

    Very well discussion. I have to know much more things to know from you

  • @charinath5445
    @charinath5445 Před 5 lety +4

    How the positions (primary) of the CTs to be arranged (P1 & P2) for both the line and neutral CTs?

  • @Alpha19103
    @Alpha19103 Před 3 lety

    Fan ho gaya bhai aapke explanation bka

  • @SumitKumar-pf9gr
    @SumitKumar-pf9gr Před 3 lety

    U really doing a good job... appreciated

  • @komalyadu7794
    @komalyadu7794 Před 3 lety

    Very sharply explained sir I am understood so easily...thanks

  • @devendraladava793
    @devendraladava793 Před rokem

    Nice video..after so many year you cleared my concept about REF.. request to make video for differential protection same also.

  • @panchalruchit6741
    @panchalruchit6741 Před 3 lety

    Really Help Full for me
    your teaching skill very Great... Thank you

  • @anilkumarshah4523
    @anilkumarshah4523 Před rokem

    you are great sir i watch your every video i have learned a lot thanks sir

  • @ramkharasane6219
    @ramkharasane6219 Před 4 lety +1

    Thank you so much sir for knowledge full video.....

  • @ZahidHussain-wk1zl
    @ZahidHussain-wk1zl Před 5 lety +2

    Well explained... Keep sharing your experiences

  • @rameshtripathy5978
    @rameshtripathy5978 Před 5 lety +1

    Very good description !

  • @pjosephkumar
    @pjosephkumar Před 5 lety

    Excellent Bro.. well explained.

  • @pitamber8879
    @pitamber8879 Před 5 lety +1

    👌👌sir make video on every equipments installed in 400kv substation.

  • @Alwayslovingdude
    @Alwayslovingdude Před 2 lety

    Very well explained..superb 👏

  • @imadullah3619
    @imadullah3619 Před 4 lety

    Perfect Mr. Nitesh

  • @arvindkaushik5081
    @arvindkaushik5081 Před 4 lety

    Really good #Nitesh ji

  • @vijaybhagat4245
    @vijaybhagat4245 Před 4 lety

    Really very very informative and well explained video Sirji

  • @sohailjanjua123
    @sohailjanjua123 Před 2 lety

    Hi, I like your lecture. Thanks

  • @rambhoolsingh2754
    @rambhoolsingh2754 Před 4 lety

    Thanks for best knowledge .

  • @deepak1529
    @deepak1529 Před 5 lety +2

    Brilliant sir ji...

  • @khanindrkaaushik6742
    @khanindrkaaushik6742 Před 9 měsíci

    Really good explanation 👍

  • @debduttbhattachargee1814

    The current flows in secondary of CT Opposite to primary due to faradays law which will oppose the change in EMF. Please include. Nicely explained.

  • @ambikaraja9656
    @ambikaraja9656 Před rokem

    Superb explanation.

  • @kulkarnir93
    @kulkarnir93 Před 4 lety

    Great sir.I like ur video.I want to know about Differential & bias current in differential protection.
    Thanks

  • @md.uzzalmiah644
    @md.uzzalmiah644 Před 4 lety

    Thank you very much for a good lecture. Please do u have any lecture about NGR in generator? How connected with parallel generator and how does calculated resistance valu? Please give me link about its.

  • @sunilkumarmishra332
    @sunilkumarmishra332 Před 3 lety

    Very informative video sir. Please make video on Insulation Monitering device & their setting.

  • @saakchannel3351
    @saakchannel3351 Před 4 lety

    Excellent way of teaching. .Learned a lot from your video thanks to a lot dear.

    • @NiteshKumarElectrical
      @NiteshKumarElectrical  Před 4 lety

      Thanks !😊💐💐

    • @saakchannel3351
      @saakchannel3351 Před 4 lety

      @@NiteshKumarElectrical
      If possible please upload videos of relays testing for feeder protection, differcial protection, imedence protection, etc.

  • @ASIFKHAN-ui7jp
    @ASIFKHAN-ui7jp Před 3 lety

    GREAT EXPLANATION THANKS A LOT

  • @PANKAJKUMAR-kv2eh
    @PANKAJKUMAR-kv2eh Před 5 lety +2

    The influence of good teacher can never be erased . Thanks a lot Sir. You are inspiration for many people..

    • @NiteshKumarElectrical
      @NiteshKumarElectrical  Před 5 lety +1

      Thanks for your feedback ! Such comments really motivate me to make good things for all. I find very less time to make videos due to my job but even though I find time. If people's are getting benefits from my videos then I think so that my labour is successful.

    • @PANKAJKUMAR-kv2eh
      @PANKAJKUMAR-kv2eh Před 5 lety

      You deserve it Sir. I am proud to be your youtuber student. Your video helps me to clear my concepts and to gain practical knowledge...You have a done great work for the nation and youths in improving their practical skills. You can easily achieve theoretical knowledge by books but for practical knowledge everyone needs a Tuitor like you...Jai Hind

    • @NiteshKumarElectrical
      @NiteshKumarElectrical  Před 5 lety

      @@PANKAJKUMAR-kv2eh जय हिंद, जय भारत। !!👍

  • @Ajay_4488
    @Ajay_4488 Před 5 lety

    very true and related to the real eg. nice keep it up sirji..can you have any idea of cbct protection with 3 wire inside cbct and N wire outside cbct..and another all 4 wire inside cbct..so how D2EFR1 relay will work..please share your valuable knowledge ..

  • @alhaseef8268
    @alhaseef8268 Před 9 měsíci

    Hi nithish your video is very useful, please advise me as we have stabilising resistor in series with relay and the settings we kept in very low value. When the fault happens how the resistor will allow small current to pass through to the relay. Actually the resistor would have its own resistance to restrict the current. Please advise

  • @rakeshgehlot9590
    @rakeshgehlot9590 Před 5 lety

    Very nice explanation sir thank u

  • @cookwithkhushboosingh9466

    Wonderful explanation 👍

  • @jhum954
    @jhum954 Před 3 lety

    Sir Mera job jbsepl me lga hai as a testing engineer transmission substation me kya testing hota hai my frasher huu

  • @Sarojsandarbh
    @Sarojsandarbh Před 5 lety

    Well done Very nice sir....

  • @juhaanable
    @juhaanable Před 5 lety

    Nitesh sir grt video but pls try to upload 1 videos once 1 week and make a video on protection of circuit breaker and CT saturation in details and thank you very much for selecting a very useful topic

    • @NiteshKumarElectrical
      @NiteshKumarElectrical  Před 5 lety

      I am trying my best Aryaan. Due to busy schedule, I couldn't find time. But now I am striving hard to help more and more to young engineers. Thanks for suggestions!!

  • @maroofchoudhary2296
    @maroofchoudhary2296 Před 3 lety

    Very very good explanation

  • @pradeepsingh350
    @pradeepsingh350 Před 4 lety

    Very good explanation Sir..kindly make a video on power transformer benifit of star to star windings and other combination...deta to star

  • @Ashokkumar-je7kn
    @Ashokkumar-je7kn Před 2 lety

    Good afternoon sir well stitching

  • @drsimx3729
    @drsimx3729 Před 5 lety

    good territorial thanks a lot sir

  • @yadavparvind6710
    @yadavparvind6710 Před rokem

    Very good video sir..

  • @wasimsharif8242
    @wasimsharif8242 Před 3 lety

    Best explanation bro

  • @sandeeptiwari-ti8wt
    @sandeeptiwari-ti8wt Před 4 lety

    good explanation sir
    make note on differential protection of single phase transformer.

  • @machhivivek4167
    @machhivivek4167 Před 3 lety

    Excellent sir..

  • @neerajpiplani185
    @neerajpiplani185 Před 4 lety

    In one of our substation whenever the 66 kv voltage is on higher side may be greater than 70 kv and if power transformer after maintenance is switched On it trips with REF indication .Could you please explain the reason for same

  • @adithihomeplant3661
    @adithihomeplant3661 Před 3 lety +1

    Super video sir.r u doing any video TNC switch? Pls inform me

  • @patelsatyam6649
    @patelsatyam6649 Před 4 lety +1

    Great video sir....Thanks for your knowledge sharing

  • @ASHISHSHARMA-gz7yp
    @ASHISHSHARMA-gz7yp Před 2 lety

    What are the repurcusions of not grounding neutral of Hv side of PTR in star star configuration ptr. As it is tripping line with neutral grounding .

  • @niravthakar6557
    @niravthakar6557 Před 5 lety

    Very good Explanation .. Sir

  • @Arijit_VU3ICT
    @Arijit_VU3ICT Před 5 lety +1

    Thank you.. Need a video about why CT saturate? How to recover saturated ct? And what is knee point voltage?

  • @RakeshKumar-bt3nr
    @RakeshKumar-bt3nr Před 4 lety

    Nice explained !!

  • @ramrah4734
    @ramrah4734 Před 4 lety

    Superb explanation sir

  • @yashucutebabu4751
    @yashucutebabu4751 Před 5 lety

    Aapke videos bahut achhe hote hai sir ...aap har roz ek video dala kare ...aap bahut aage tak jayenge ..33 kv vcb ki wiring batye sir ...detail me
    Thanks in advance

    • @NiteshKumarElectrical
      @NiteshKumarElectrical  Před 5 lety

      दिल से धन्यबाद आपको cute pushu !! मेरी भावना मदद करने की ही है। टेक्निकल रूप से फ्री में ट्रेनिंग देने का।

  • @muhammadsajjad1723
    @muhammadsajjad1723 Před 5 lety

    Very good explanation. Appreciate your job sir. Thanks

  • @akashsenta3601
    @akashsenta3601 Před rokem

    Respected Sir
    My trasformer REF protection
    Neutral CT 5P15 and phase CT PS class
    At a time near fault REF protection is operated.
    Can different class CT use for fault feeding operated.

  • @arabindabehura4181
    @arabindabehura4181 Před 5 lety

    Tremendious sir.

  • @ashishdixit7050
    @ashishdixit7050 Před 4 lety +1

    Nice explanation

  • @mahingajjar6059
    @mahingajjar6059 Před 4 lety

    excellent sir, pls make vedio on generator protection relay

  • @ManojkumarSahoo_electrical

    Sir, How to calculate the power rating (Wattage) of stabilizing Resistor for REF relay.

  • @kundankumarroy5507
    @kundankumarroy5507 Před 5 lety

    Very good explain and easy to do

  • @satjain2971
    @satjain2971 Před 5 lety

    Brilliant explanation...nitesh

  • @realityofworld1786
    @realityofworld1786 Před 5 lety +1

    Bohot awla sir

  • @jppatnaik2240
    @jppatnaik2240 Před 3 lety

    Thank you very much sir,

  • @mksingh0121
    @mksingh0121 Před 5 lety

    You are so good sir more video

  • @anandbhadang291
    @anandbhadang291 Před 3 lety

    Nice one

  • @sameermd9956
    @sameermd9956 Před 5 lety

    Excellent sir 👌👌👌

  • @shareeffishingtasteydishin491

    Nice explain...

  • @Shiva68
    @Shiva68 Před 4 lety

    Realy great

  • @deepakswami9614
    @deepakswami9614 Před 2 lety

    Nice video...very very useful. Please sir differential and distance relay ka bhi ek dictated video banaye.

  • @sapannayak2368
    @sapannayak2368 Před 5 lety

    Nice explanation brother

  • @aftabraj1865
    @aftabraj1865 Před 5 lety +1

    Great explanation sir....
    Sir make a video about DISTANCE Protection plzzzzzzz

  • @tufailalam6438
    @tufailalam6438 Před 5 lety

    Sir. If Vsp>2kv..what should be the value of VDR.

  • @nirajmaheta2656
    @nirajmaheta2656 Před 5 lety +4

    Sir one more video SEF protection

  • @salimmalek9992
    @salimmalek9992 Před 2 lety

    Very Good teaching sir

  • @soumyajitsundarray4316

    Dear Nitesh Can you will made a video on centralized busbar protection vs a decentralized busbar protection system

  • @Manish-cs9tr
    @Manish-cs9tr Před 3 lety +1

    Super sir......

  • @souravbose8115
    @souravbose8115 Před 4 lety

    Sir, ek doubt hai. Why would I1 flow from the load to the fault? Shouldn't the current of B- phase flow directly to earth at the fault and come back through the neutral and not flow through the phase C.T at all ideally? Aur Normal condition me kya hoga? tab to B phase ka C.T full phase current sense karega aur neutral ka c.T ideally koi current sense nehi karega. Tab kyu trip nehi hoga?
    Please explain as early as possible. I will be grateful.

  • @vipsingh908
    @vipsingh908 Před 5 lety

    Sir maza aa gya is bar ..thanks & keep sharing

    • @NiteshKumarElectrical
      @NiteshKumarElectrical  Před 5 lety

      मजा आने के लिए ही तो बनाया था !!😊😊👍
      अभी और भी मज़ा आएगा। देखते रहिये। और ज्ञान बढ़ाते रहिये फ्री में।😊😊😊👍 दूसरे को भी शेयर कीजिये वीडियो।

    • @vipsingh908
      @vipsingh908 Před 5 lety

      Sir apka email address milega ?? I have a some doubt

    • @vipsingh908
      @vipsingh908 Před 5 lety

      @@NiteshKumarElectricalin case study :- observation :- at substation 132/33 kV t/f was in ckt. As & when fault occured on 11 kV lines, 11 kV side either of LA failed it was replaced no of time
      Action taken:- 11 kV LA replaced by 33 kV LA then failure of LA was stoped
      Explain reason of failure ..
      Thanks .

    • @A1993M
      @A1993M Před 5 lety

      @@NiteshKumarElectrical sir how to study electrical drawing wale video upload kro