Easy Guide Conduit & Trunking Sizing in Electrical Installations with Worked Examples using OSG

Sdílet
Vložit
  • čas přidán 29. 08. 2024
  • How to use the On-Site -Guide to size Conduit & Trunking Installations. How many conductors can you fit in a conduit or Trunking this one stop easy guide to find the answers. Worked examples for all to try.

Komentáře • 5

  • @AndrewCook7
    @AndrewCook7 Před 2 dny +1

    How are the cable factors worked out. 22 for 1 mm and 27,for 1.5.

    • @sparkyhelp3997
      @sparkyhelp3997  Před 2 dny

      Hi they are based on tried and tested unit system method the IET have established over many years. The numbers do not have a unit they are just factors taken form table from the IET guides. Hope that helped, please share with like minded people or even like and subscribe.

    • @AndrewCook7
      @AndrewCook7 Před 2 dny

      @@sparkyhelp3997 Brilliant thank you, been driving me nuts trying to work it out, diameter, circumference etc even a percentage.

  • @michaelcostello6991
    @michaelcostello6991 Před 9 měsíci +1

    Why are the elctrical affects of grouping not factored ??

    • @sparkyhelp3997
      @sparkyhelp3997  Před 9 měsíci +2

      Hi, Because the number of circuits (not conductors) is not known or the loading of each circuit - this will have an impact on grouping and would be considered by the designer, which may change the cable size and therefore containment size.
      Hope that helps. Please Like, Share & Subscribe.