Manually Testing an Inverter Board

Sdílet
Vložit
  • čas přidán 7. 09. 2024

Komentáře • 35

  • @FAT_splashes
    @FAT_splashes Před 5 lety +4

    Your videos have helped me so much! I recently was placed in charge of a building with a 10 year old vrv3 system and needless to say I have had my problems. Your videos have simplified my day to day life and I thank you for it.

    • @tcphvacr9950
      @tcphvacr9950  Před 5 lety +2

      Kyle Anson and I want to thank you for the nice comment. I know when I was starting out, seeing how you did a diagnosis compared to reading how, made the world of difference. Thanks for watching!

  • @robertozavala9869
    @robertozavala9869 Před 2 lety

    My name is Rob-Z. I'm a VRV service technician from Indianapolis, IN. I find your videos very helpful. Keep up the good work!

    • @tcphvacr9950
      @tcphvacr9950  Před 2 lety

      I’ve learned quite a bit more in the VRV world in the last 4 years, but Daikin has a strict “no videos” policy 😞 I work for a Daikin factory rep since 2018. Thanks for checking out the video!

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC Před 2 lety +1

    I just recently purchased the Refco inverter checker. Great video

  • @vlqllvol
    @vlqllvol Před rokem

    Great vid, By the way - O.L. doesn't mean Open Line as you say - that means Out Limit of the meter range.

  • @manjulaishara1281
    @manjulaishara1281 Před 4 lety +1

    I have seme pcb .is comin error l5 how to rapair .this falt..help me thank you.

  • @Blueblurr112
    @Blueblurr112 Před 5 lety

    great vid thanks for the info, I just finished the trouble shooting course in FL it covered exactly what you were talking about.

  • @abdelhalimrabie255
    @abdelhalimrabie255 Před 5 lety

    excellent work

  • @GamertagAKACUZ
    @GamertagAKACUZ Před 5 lety +1

    Good vid. Keep the vrf/ vrf videos coming!
    Any other meters besides fluke you like for vrv work?

    • @tcphvacr9950
      @tcphvacr9950  Před 5 lety +1

      I also have the Fieldpiece SC640, which has a high ohm reading range (like 40 million ohms) that is good for the thermistor checks, and it's response time is pretty quick (better the the Uei DL429). It still has the 32 degree operating temperature limitation (although I don't know how "limiting" that really is) like most manufacturers have except Fluke.

  • @soleman9
    @soleman9 Před 4 měsíci

    Please, can you provide a diagram of the testing device

    • @tcphvacr9950
      @tcphvacr9950  Před 4 měsíci

      The testing device is a Fluke 87V meter, on diode mode.

  • @mineshvarma345
    @mineshvarma345 Před 2 lety

    WHWT SHOULD WE DO AT (L5) ERROR AT INVERTOR BOARD WE HAVE SAME BOARD.

  • @kennyw7453
    @kennyw7453 Před 5 lety

    Great video

    • @tcphvacr9950
      @tcphvacr9950  Před 5 lety

      Kenny W thanks, I’m going to try and post more stuff that helps get you to a proper diagnosis of what’s going on in the system.

  • @serbianknights4988
    @serbianknights4988 Před 4 lety +1

    Hi mate Can you please give me more information for aluminium cased inverter checker? Who made it and what is model number?

    • @tcphvacr9950
      @tcphvacr9950  Před 4 lety

      Ti Network Australia its not made anymore, and it doesn’t have any nomenclature. The manufacturers rep sold it to us (I work for them now), and now they sell the plastic ones now, made by Refco. I have found that they can pass a board, and the board can fail later, taking out compressors. If we have a compressor fail electrically, we replace the inverter board with it.

    • @serbianknights4988
      @serbianknights4988 Před 4 lety

      @@tcphvacr9950 I have inverter checker from DAIKIN Australia but I don't trust them at all.

  • @garantaoseufuturo9603
    @garantaoseufuturo9603 Před 3 lety

    If you should find above 1.2 and was just open it means your board was in fault?

    • @tcphvacr9950
      @tcphvacr9950  Před 3 lety +1

      What happens is it starts low then climbs, eventually going open. Then you have to wait for it to discharge and check the others. It is fine if it does that. If it was lower and didn’t go up, it would be bad.

  • @parimalbhagat3763
    @parimalbhagat3763 Před 3 lety

    Main Power Source MCB is tripping without any alarm.
    What might be the problem if you can guide me sir.

  • @MJ-iy4fb
    @MJ-iy4fb Před 3 lety

    thanks for posting. how can i get a hold of the daikin manuals?

    • @tcphvacr9950
      @tcphvacr9950  Před 3 lety +1

      www.daikinac.com/content/resources/manuals/service-manuals/vrv-systems/?

    • @MJ-iy4fb
      @MJ-iy4fb Před 3 lety

      @@tcphvacr9950 thank you

  • @user-mn2dk4yp2v
    @user-mn2dk4yp2v Před 3 měsíci

    😮

  • @user-sw6sz7gr8t
    @user-sw6sz7gr8t Před 10 měsíci

    We want the test kit shop sftess

  • @sainathgajjila7919
    @sainathgajjila7919 Před 4 lety

    Hi vrv 3 inverter pcb l5 error repair how to repair sir

    • @tcphvacr9950
      @tcphvacr9950  Před 4 lety

      Sainath Gajjila get your service manual and find the error and follow the step by step flow diagram of troubleshooting. Always turn off power, and wait fifteen minutes before testing the inverter board.

  • @joelwatts8951
    @joelwatts8951 Před 4 lety

    I thought the testing is between P1 not P2?

    • @tcphvacr9950
      @tcphvacr9950  Před 4 lety +1

      In the service manual I have it's P2. Having said that, I noticed they have different methods in different manuals. In one manual it goes to a power transistor check I described in this video, and in another manual it has different methods of testing. In VRV IV service manual it shows the same method in the video. I'm going to study it and possibly have to do another video doing the methods described in the other manual. Thanks for commenting!

  • @duartepaintinghandymanservices

    do you repair inverters?

    • @tcphvacr9950
      @tcphvacr9950  Před 4 lety

      Duarte Handyman Services LLC. Duarte no. This is just to see if the diode bridges are good.

  • @user-jf5jp5ib4u
    @user-jf5jp5ib4u Před 3 lety

    Erro L5