Mitsubishi ductless mini split heat pump not heating

SdĂ­let
VloĆŸit
  • čas pƙidĂĄn 23. 02. 2022
  • no heat call on a Mitsubishi ductless mini split heat pump, lets see what we get into.
    if you would like to buy me a cup of coffee www.paypal.me/norcalrefrigera...
    #Mitsubishi
    #mini split
    #hvac
    #ductless mini split air conditioner
    Music đŸŽ¶ for videos at epidemic sound www.epidemicsound.com/referra...
  • Jak na to + styl

Komentáƙe • 118

  • @camiloramirez3367
    @camiloramirez3367 Pƙed 2 měsĂ­ci

    Keep up the great work man, just one thing to add: between S2-S3 you’re reading DC Voltage, fluctuation between 10-32VDC means properly communicating ODU-IDU.

  • @howardblasingame7961
    @howardblasingame7961 Pƙed 5 měsĂ­ci

    Thanks for the video, and especially highlighting the troubleshooting. I'm an Electrical Contractor for 50 years, and now semi-retired, I help friends & family with their mini splits. Your videos have kept me out of trouble many times.

  • @sknight0391
    @sknight0391 Pƙed 2 lety +3

    LIKE A BOSS with the shoulder strap ladder trick!!!😎👍

  • @sharky5570
    @sharky5570 Pƙed 2 lety +2

    Got lucky on the placement of those boards in condenser. Usually they are upside down and a pia to get to. Great stuff Super Dave

  • @georgeian3243
    @georgeian3243 Pƙed 2 lety +2

    Nice work, I like your troubleshooting technique. Must say I’ve never had the pleasure of a short sleeved no heat call on a rooftop in February.

  • @RCM442
    @RCM442 Pƙed 2 lety +3

    I'm in an entirely different field (I mainly do gas appliance repair) and my tool bag tips over all the time like yours lol

  • @vicenterivera69
    @vicenterivera69 Pƙed 2 lety +1

    I like how you work. Super chill! My style also

  • @ronkurey8840
    @ronkurey8840 Pƙed 2 lety +1

    Didn’t you hear me yelling! Dave
condensate pump..float..safety switch
 good catch
installed 47 minis in one school
prior to renovations
after completing the renovations, guess what 35 condensate pump services.😂😂

  • @awesomebillfromdawsonville8715

    I hate those micro inline pumps. Stopped using them due to premature failure causing high temperature alarm in small server rooms. We use external mounted one piece mini split pumps easier to maintenance and repair. Another useful idea to keep door screws from getting lost I carry collapsing magnetic tray in my service bag. Craftsman and Matco have them available work awesome. I got tip from HVAC UK video 👍

    • @MrBdogg317
      @MrBdogg317 Pƙed 2 lety +2

      I agree we now use the aspen pumps that mount on the outside. Sooooo much better

    • @NorCal-refrigeration
      @NorCal-refrigeration  Pƙed 2 lety

      I’ll look into those pumps

    • @sprockkets
      @sprockkets Pƙed 2 lety

      Refco COMBI has a good reputation from what I've heard.

    • @awesomebillfromdawsonville8715
      @awesomebillfromdawsonville8715 Pƙed 2 lety

      @@sprockkets yep used those work great and install easy, but only one vendor in town stocks them.

  • @PaulHVAC1
    @PaulHVAC1 Pƙed 2 lety

    Great video Dave. Cheers!!

  • @jamestoy426
    @jamestoy426 Pƙed 2 lety

    Super tech all the way i have only installed 3 mini splits did not know about the float switch nice job again i always learn watching your channel

  • @sergiodoordie319
    @sergiodoordie319 Pƙed rokem +1

    I have learned one or two things watching ur videos I'm new on the mini split field I've just installed a multi zone mini split system. Installing is always easy but troubleshooting a unit takes a lot patience cuz it ain't easy

  • @gr82becool
    @gr82becool Pƙed 2 lety

    The one handed up the ladder. Love it 👍

  • @joelsalmon6643
    @joelsalmon6643 Pƙed 2 lety

    Excellent work!

  • @scottk0623
    @scottk0623 Pƙed 2 lety +2

    Nice job Dave, I like the Aspen pumps by rector seal they are external and mount just below the unit same color.

  • @MrMultitool
    @MrMultitool Pƙed 2 lety

    Great job Dave. I still use my Fluke 16 too. I bought a 116 but I still like my 16 the best.

  • @danwittels5542
    @danwittels5542 Pƙed 2 lety +3

    I was diggin' that disconect too. I never seen one like that before, perfect for a condenser on a roof. I've got to look for those.

    • @SupremeRuleroftheWorld
      @SupremeRuleroftheWorld Pƙed 2 lety +2

      always spend some extra on a good disconnect with plugs. its so nice for the next guy, because the next guy is probably you.

    • @danwittels5542
      @danwittels5542 Pƙed 2 lety +1

      @@SupremeRuleroftheWorld amen!

  • @Eddy63
    @Eddy63 Pƙed 2 lety

    Good troubleshooting vid ... Thx for posting ...

  • @bobbysim5480
    @bobbysim5480 Pƙed 2 lety +3

    Should of just checked voltage across L1 and L2 at the wall mount and if you have voltage there then the problem isnt at the condenser.

  • @carlocurotto7555
    @carlocurotto7555 Pƙed 2 lety

    good catch dave

  • @AliG-vv2rd
    @AliG-vv2rd Pƙed 2 lety

    Good stuff my man!

  • @philltafolla
    @philltafolla Pƙed 2 lety +1

    He’s a SUPER TECH 😃

  • @captainkirk7702
    @captainkirk7702 Pƙed 2 lety

    Another fine quality job done by super tech Dave!!! Go Crying Cowboy’s Fan seat warmer to the niner’s!!!

  • @DWAYNE2ism
    @DWAYNE2ism Pƙed 2 lety

    great video as usual. nice place to put your main electrical panel,

  • @garikharutyunyan163
    @garikharutyunyan163 Pƙed 2 lety

    Great job Bro

  • @ruttworksfabrication1954
    @ruttworksfabrication1954 Pƙed 2 lety

    you're a hero!!!

  • @middleamerica646
    @middleamerica646 Pƙed rokem

    Watching you I’m like, yep, yep, yep, yep, yep. The process of elimination in perfect sequence.

  • @robertv4442
    @robertv4442 Pƙed 2 lety +3

    Hahaha, that blood check you did had me cracking up. Stay safe out there Dave!

  • @ntsecrets
    @ntsecrets Pƙed 2 lety

    this one had it all, blood sweat and tears!

  • @jamierushing8811
    @jamierushing8811 Pƙed 2 lety

    Hi bro from west Alabama love y’all

  • @hugoguevara3864
    @hugoguevara3864 Pƙed 2 lety

    Excelente

  • @thefixer6973
    @thefixer6973 Pƙed 2 lety +1

    keep up the great work dave love the vids. learned a new thing pumps in minis new to this i've put 4 units in and never went up with lineset

  • @heavydiesel
    @heavydiesel Pƙed 2 lety +2

    I keep water in the truck when its warm here, though I got an army surplus water bottle to refill as I'm tighter than a ducks arse....
    Those buzzy pumps are nothing but trouble!

  • @SchwaAlien
    @SchwaAlien Pƙed rokem

    We’ve got an older Mitsubishi mini split AC in an artist studio that just drains outside by gravity and tends to build up ice in the drain pan and then leaks into the room. The building doesn’t allow permanent AC installation anymore, ours is grandfathered and we supposedly aren’t allowed to replace it, but it would be nice if they would make an exception and recognize the environmental benefits of the energy efficiency advantages of us upgrading it to a heat pump instead of just using an electric baseboard heater in the relatively mild winters we get in Vancouver... I was able to air heat the place with 700 watts of continuous crypto mining, not quietly but it wasn’t toooo bad for a couple winters as a productive alternative to the baseboard.

  • @REFRITEKREFRIGERACION
    @REFRITEKREFRIGERACION Pƙed 2 lety

    Great job as always Dave, your Troubleshooting skills are on another level. Supertech for life. What camera are using?

  • @chrisbivens5410
    @chrisbivens5410 Pƙed 2 lety

    Cool vid
heard a little Hack coming through at the 8:05 mark đŸ€™

  • @qomco
    @qomco Pƙed 2 lety

    Just installed 2 combi 2 pumps this week on my install. I tried to keep em accessible bc i know the service tech is gonna have to find them some day. But i test them b4 i leave at least

  • @andrewedis9907
    @andrewedis9907 Pƙed 2 lety

    I've worked on a lot of Mitsubishi units and it's always a matter of keep taking screws out until you find what you're looking for. Fun stuff!

  • @baylifehvac991
    @baylifehvac991 Pƙed 2 lety

    I hate those pumps , i away use the gobi 2 pumps made by reco . Good video

  • @sknight0391
    @sknight0391 Pƙed rokem

    #BreakersInTheShitter 😎👍

  • @SovereignTroll
    @SovereignTroll Pƙed 2 lety

    I like cassettes in the ceiling for ease of service.

  • @danwittels5542
    @danwittels5542 Pƙed 2 lety

    We know you love Tippy! 😉

  • @marcushenneman4185
    @marcushenneman4185 Pƙed 2 lety

    I'm going to be recovering from many walk in coolers soon, for the first time, can you give me some tips on how to approach this.

  • @tyhuffman5447
    @tyhuffman5447 Pƙed 2 lety

    Can you use a Skuz-away pill to treat the sump?

  • @joesolis8423
    @joesolis8423 Pƙed 2 lety

    Hey, Dave u forgot to shake those batteries!!!

  • @scrambler350
    @scrambler350 Pƙed 2 lety

    Mini-split....rhymes with Money Pit.

  • @rickross7796
    @rickross7796 Pƙed rokem

    s1 to s2 is 240 ac and s2 to s3 is DC voltage ranging from 12 to 26 or 27 volts

  • @tad2021
    @tad2021 Pƙed 2 lety

    $4.39 for gas, I wish it was still that cheap down here in socal on the coast. lol

  • @stephwaylonwells3218
    @stephwaylonwells3218 Pƙed 2 lety

    👍

  • @dantemariscal8679
    @dantemariscal8679 Pƙed 2 lety +1

    It’s awesome to see you work on all the stuff you do. How many years did it take for you to learn all that?

  • @harrydickson4575
    @harrydickson4575 Pƙed 2 lety

    👍👍👍

  • @qomco
    @qomco Pƙed 2 lety

    Voltage on s2 and s3 bounces between 0 and 19 vdc, something like that?

  • @davejohnsonnola1536
    @davejohnsonnola1536 Pƙed 2 lety

    Oh the joy of aging, leaks of all kinds....blood doesn't clot like it used to

  • @joaquiniglesias154
    @joaquiniglesias154 Pƙed 2 lety

    U gotta get a cooler for those water bottles . Sitting in the heat in the van the plastic starts to melt and dissolves in the water. Really bad for u brother . Other then that. Keep grinding . Hvac for life

    • @Lewdacris916
      @Lewdacris916 Pƙed 2 lety

      Yup ive always got an ice cooler packed with drinks, rockstars and water lol, life on the road

  • @gracida6
    @gracida6 Pƙed 2 lety

    why is uv tape black, doesnt black absorb more heat in the summer?

  • @chainoflakesrefrigerationa2906

    What are the most commonly used t handle allen wrenche sizes you carry?

  • @sterlingarcher46
    @sterlingarcher46 Pƙed 2 lety

    Nice one Super Dave 👍
    Do you guys use Sauermann condensate pumps over in the States ? Very popular here .

    • @NorCal-refrigeration
      @NorCal-refrigeration  Pƙed 2 lety

      I have not.

    • @REFRITEKREFRIGERACION
      @REFRITEKREFRIGERACION Pƙed 2 lety

      I think they sell it here in the US too. Are they good?

    • @sterlingarcher46
      @sterlingarcher46 Pƙed 2 lety +1

      @@REFRITEKREFRIGERACION yeah they're pretty good , I couldn't really spot the difference with the Aspen fancy super silent pumps really .

    • @REFRITEKREFRIGERACION
      @REFRITEKREFRIGERACION Pƙed 2 lety

      @@sterlingarcher46 Thanks, good to know. I was checking online a few months ago and I think I saw those Sauerman Pumps. I will check them out.

    • @mountainklima5602
      @mountainklima5602 Pƙed 2 lety

      @@REFRITEKREFRIGERACION sauerman are good, but the aspen are top-notch

  • @dougking7592
    @dougking7592 Pƙed 2 lety +3

    I for one do not like working on the glorified window unit mini splits

    • @OcRefrig
      @OcRefrig Pƙed 2 lety

      Me neither. seems like they dont last very long. Had a Samsung only last about 5 or 6 years. I did not install , the install did not look that great. so , i probably should not use this one i saw as a reference. poor install allways = Troubles & short life of any equipment.

    • @NorCal-refrigeration
      @NorCal-refrigeration  Pƙed 2 lety

      @@OcRefrig I was told today 20,000 hours life span if they run all the time.

    • @qomco
      @qomco Pƙed 2 lety

      I do mitsubishis, we give our customers a 10 to 12 yr parts warranty. But they are fussy as heck especially with elevtronics. And not cleaning the filters means replacinc the blower wheel. But for a lot of our customers its the only option

    • @mountainklima5602
      @mountainklima5602 Pƙed 2 lety

      @@OcRefrig Here in Europe they are full of electronics (weak part) life spam is about 10 years, but they are very energy efficient, I see you guys in the states are still running capacitor base units, which are much easier to serve and diagnosis

  • @ThePeavey23
    @ThePeavey23 Pƙed rokem

    Ductless outside wall only gravity drain

  • @kingofthecrease30
    @kingofthecrease30 Pƙed 2 lety

    since when does california need heating or air conditioning systems ? đŸ€” santa cruz is always 72 & sunny 😅

  • @musicmancecuador
    @musicmancecuador Pƙed 2 lety

    You know you can troubleshoot whit the remote itself..checks everything pressure pumps up..on the remote

  • @johnwoo9247
    @johnwoo9247 Pƙed 2 lety

    Hi super Dave I work on ice machine and small reach in refrigerator and freezer, I have a question in regards to critical charge systems, I use 36" hose, let's say the ice machine said to put in 15oz of 404A, how much should I put in exactly 15oz or do I go to 16-17 oz because when you remove your hoses you're losing some refrigerant, also how much in ounce refrigerant does each hose hold,for 36"hose and for 60" hose thanks.

  • @prashanshan7125
    @prashanshan7125 Pƙed rokem

    Doesn't it throw code for float switch..?

  • @ore-georgecicovic6533
    @ore-georgecicovic6533 Pƙed 2 lety

    Run to clean your blod from condensing unit or someone can have that sample to clone you. 😂😂😂

  • @kevinpoore5626
    @kevinpoore5626 Pƙed 2 lety +1

    Yeah I guess that's the reason why they have schools for work on those things just so you know how many dang screws you got to take out đŸ€ŁđŸ€Ł

  • @sknight0391
    @sknight0391 Pƙed 2 lety

    You know what happens when you lose your screws Dave???

    • @sknight0391
      @sknight0391 Pƙed 2 lety

      YOUR SCREWED!!!!!đŸ€Ș👌

  • @ras2820
    @ras2820 Pƙed rokem

    Are all mini split heat pumps

  • @KrazyKuul111
    @KrazyKuul111 Pƙed 2 lety

    Impacts aren't made for sheet metal

  • @00hate00
    @00hate00 Pƙed 2 lety

    What brand service bag is tippins?

    • @Justintime631
      @Justintime631 Pƙed 2 lety

      Veto tb xl

    • @Justintime631
      @Justintime631 Pƙed 2 lety

      I’ve seen the TP xxl doesn’t tip as much

    • @NorCal-refrigeration
      @NorCal-refrigeration  Pƙed 2 lety +1

      @@Justintime631 it’s expensive though

    • @00hate00
      @00hate00 Pƙed 2 lety +1

      @@Justintime631 thanks so much
      It's arriving Friday đŸ’Ș

    • @Justintime631
      @Justintime631 Pƙed 2 lety

      @@00hate00 congrats. It’s a good bag, it’s my main bag now. I’m pleased with it

  • @Hurpdurpdipidydoo
    @Hurpdurpdipidydoo Pƙed rokem

    Owning a ac company in this day and age means you have to pay a tech for 4 hours to fix one system, what a nightmare it must be for them .

  • @3amigos99630
    @3amigos99630 Pƙed 2 lety

    So simple a caveman can do it!

  • @Abrokadabro
    @Abrokadabro Pƙed 2 lety

    The main power switch is so stupid in Australia we have isolator switch made of plastic and why do you a fuse in a metal box on a roof when you have a fuse in the main switch board and why is everything like the 1970s when it comes to the main Power in the states

    • @NorCal-refrigeration
      @NorCal-refrigeration  Pƙed 2 lety

      It’s code here. Service disconnect within 6 feet I don’t believe fuses are required you can use a non fused disconnect, but it’s always a fused installed.

    • @Abrokadabro
      @Abrokadabro Pƙed 2 lety

      @@NorCal-refrigeration ok so you have a main fuse in the subox then you have a fuse next to the outside unit if it's three phase power do you still have fuse at the outside unit and does it loses all turn off if you lose a phase at the outside unit disconnect switch

  • @jrsmyth9761
    @jrsmyth9761 Pƙed 2 lety

    Be careful!!!!
    Safety conscious and fine happy CA might get you for having a tool bag in your hand while climbing the ladder AND you filmed it giving them proof.

  • @sknight0391
    @sknight0391 Pƙed 2 lety +2

    By the way....I F-IN' HATE MINI SPLITS!
    Do you know the name of the engineer that designed the first mini split? BEELZEBAB!!!!! đŸ‘č

  • @freelanceservices8704
    @freelanceservices8704 Pƙed rokem

    Negative 15 and this shits the bed

  • @allykatt940
    @allykatt940 Pƙed 2 lety

    i hate ductless all of them

  • @thereckchanic4709
    @thereckchanic4709 Pƙed rokem

    Poor video, can even see what you’re talking about.

  • @OcRefrig
    @OcRefrig Pƙed 2 lety

    Great video ! When you do the Pump replacement can u show how to remove the cover to access the pump. i have not worked on a mitsubishi head unit yet. Thanks. Like #55.