What is Intrinsically Safe?

Sdílet
Vložit
  • čas přidán 20. 08. 2024

Komentáře • 61

  • @Roberval.Bulgarelli
    @Roberval.Bulgarelli Před 2 lety +1

    Clear, simple and straightforward basic explanation of the main aspects and concepts of intrinsic safety. Congratulations!
    Just a small conceptual comment: Both "classified" and "unclassified" areas need to be considered and deemed as "SAFE".
    Electrical, automation and instrumentation installations, in both cases, need to use equipment with appropriate "Ex" protection types (in classified areas) or associated equipment (in non-classified areas), in addition to performing the applicable installation, inspection and maintenance "Ex" service procedures, according to IEC 60079-14 and IEC 60079-17. 👍
    Thus, it is suggested to use the term "UNCLASSIFIED AREA" or "NON HAZARDOUS AREA" instead of "SAFE AREA".

  • @MrDinger24
    @MrDinger24 Před 2 lety +4

    Absolute brilliance! Teaching this to new apprentices and time and time again I find exactly what I am teaching right here at RealPars - Thank you

  • @tonyj8949
    @tonyj8949 Před 2 lety +12

    For your example division two actually refers to the presence of a hazardous atmosphere under abnormal operating conditions such as maintenance

    • @mervbohrer3537
      @mervbohrer3537 Před 2 lety +3

      Did they flip flop Div 1 and 2 (normal vs abnormal) in this video?

    • @rsmakishi
      @rsmakishi Před 2 lety

      I can’t remember where I read it but it said that Div.2 is presence of a hazardous atmosphere less that 6 hours per year which means emergencies only and Div.1 is over 6 hours per year.

    • @leojrbarcenas8813
      @leojrbarcenas8813 Před 2 lety +2

      I agree; I also think that they got it switched with Division 1.

  • @87113037
    @87113037 Před 2 lety +2

    4:29 Division 2 means particles present during ABNORMAL operations.

  • @zakirsayed111
    @zakirsayed111 Před 2 lety +3

    Hello, the video was really helpful in understanding intrinsic safety in a context of plc control system. But, I have something to clarify. It was said in the video that Div 1 is for environment where combustible dust is present during abnormal conditions. I think abnormal is for Div 2. Would like if you can give clarification on this. Thank you

    • @realpars
      @realpars  Před 2 lety

      Correct. Div 1 conditions exist where the hazard is normally present. Div 2 is when the hazard exists under abnormal conditions.

  • @thesilentgamer4210
    @thesilentgamer4210 Před 3 dny

    Hello, I am aware of IS CALCULATION concept. But for one loop only. Like BARRIER to JB to LT.
    But I am not sure how would be the process for IS like this case. BARRIER to JB to FIT to FE? How is The cable from FIT for FE considered in calculation?

  • @emmanuelsanusi1389
    @emmanuelsanusi1389 Před 2 lety

    Thank you Realpars. You are doing great!

  • @asadiqbal87
    @asadiqbal87 Před 2 lety +2

    another interesting video thanks real pars

    • @realpars
      @realpars  Před 2 lety

      Glad you enjoyed it! Happy learning

  • @bagsnwa6243
    @bagsnwa6243 Před 12 dny

    Thanks for the information

  • @anusyirvan
    @anusyirvan Před rokem +1

    On minutes 5:00 when photo-eye ON it will turn on a diode. Where is the power from? Is there any battery inside photo-eye?

    • @realpars
      @realpars  Před rokem

      The power (usually 12VDC or 24VDC) comes from the PLC card it is attached to, or in some cases, an external power supply. Photo eyes do need a power source.

    • @anusyirvan
      @anusyirvan Před rokem

      @@realpars But on the video 05:00 the circuit only connected with light diode to PLC. Is there any other wire to photoe eye to carry 24VDC?

    • @Solder_it
      @Solder_it Před 2 měsíci

      I think the power will not come from PLC card, the power is from external source, then the feedback (alarm reading or normal reading from the photo eye) ia connected to the barrier, the barrier then converts that small signal to a higher voltage signal to reach to the PLC AI card (i think the signal is Analog), if there is an alarm signal the ESD system will shutdown the power or act to prevent any explosion etc.. i think its done that why but i am not sure.

  • @abdelrahmanabdelgadier5537
    @abdelrahmanabdelgadier5537 Před 4 měsíci

    Very useful as usual from RealPars

  • @adhamshorafa5338
    @adhamshorafa5338 Před 2 lety

    i always isolate the inputs and outputs between the panel and the field

  • @saltlight4220
    @saltlight4220 Před 2 lety

    Definitely for Electrical control engineering and technicians

  • @fitz83
    @fitz83 Před 2 lety +1

    You mentioned at the start, that the video would show how to DESIGN a circuit which is intrinsically safe? Is this video demonstrating the LOOP concept (follow the manufacturer certification exactly) and ignores the ENTITY circuit calculations?
    What about the requirements for the circuit calculation, the entity parameters, cable capacitance and inductance? The number of times I’ve had near misses from sub contractors, mistakenly thinking, that when they pick a barrier which will power a device in the field also means it’s safe for the hazardous area is beyond frustrating (at times has lead to follow up action with their employer when competency is an issue). Also, would it not have been easier just to say the barrier must be installed in a safe area rather than give a specific example of a purged panel which achieves this?

    • @realpars
      @realpars  Před 2 lety +1

      @fitz83 Our short videos 9n CZcams are meant to introduce viewers to concepts used in the automation industry. Entity circuit calculations are quite a bit more involved than what our short videos can cover. And yes, in hindsight, placing the panel in a GP area would have simplified the discussion.

  • @ohnanawhatsmyname3281
    @ohnanawhatsmyname3281 Před 2 lety

    Whats the difference between Ex d and Ex i? What are the applications?
    Also all barriers will need a photo eye?

    • @realpars
      @realpars  Před 2 lety

      A simplified answer is that Ex-ia sensors are classified as Category 1G/1D equipment, for installation in Zone 0, 1, or 2 and 20, 21, and 22 areas. Ex-d sensors are classified as Category 2G equipment, for installation in Zone 1 or 2 and 21 or 22 areas. Ex-ia sensors (such as a tuning fork level switch) can be installed in a tank with hazardous material , whereas an Ex-d sensor cannot be installed in that location.

  • @nikolas8741
    @nikolas8741 Před 2 lety +1

    High quality content ❤️

  • @aminokamad1681
    @aminokamad1681 Před 2 lety

    Highly recommended videos 🔥

  • @abdessamedghettas7167

    Thanks

  • @jesusmanuellevinsonrondon5107

    What about intrinsic safety for wireless loops? Does the receiver has to comply with IS regulations too?

    • @realpars
      @realpars  Před 2 lety +1

      The short answer to your question is YES. Every part of the "circuit" must be analyzed to insure that the maximum radiated energy does not exceed the threshold for IS installations. A good summary can be found at: www.controlglobal.com/articles/2019/how-to-ensure-intrinsic-safety-for-wireless-systems/. Most wireless installations do not exceed the 2W limitation for the most stringent Group IIC environments, and when installed properly (in Ex d enclosures, for example), can be used in hazardous areas without modification.

  • @gamelover2594
    @gamelover2594 Před rokem

    so for 4-20 mA we can use a zenner barier and for discrete signals we can use isolated barier? Thank you!

    • @realpars
      @realpars  Před rokem +1

      Hello GameLover!
      Thank you for your question! Unfortunately, I can’t fully assist as it is not in the contents of our video, as we discuss in Intrinsic safe example 1. But it is a valid question. To help you with your question, here is a head start. Here are 2 links to manufacturers that might be able to help you with these devices you are asking about.
      0-10v, 4-20ma intrinsic safety barrier Zener barrier explosion-proof safety
      www.alibaba.com/product-detail/0-10v-4-20ma-intrinsic-safety_62468731323.html
      www.pepperl-fuchs.com/usa/en/classid_14.htm
      Signal Converters - Intrinsic Safety Barriers
      Happy learning from RealPars!

  • @TuanNguyen-qi8iq
    @TuanNguyen-qi8iq Před 2 lety

    Thank you!

  • @bitebonumbere1426
    @bitebonumbere1426 Před 2 lety

    Realpars, please what's the difference between this video vis-a-vis IS vs Non-IS cables?

    • @realpars
      @realpars  Před 2 lety +1

      Intrinsically safe cables are designed to be UV and weather-resistant and conform to certain ISI standards. Cables that are installed in IS service should have blue jacketing/insulating covering to distinguish the cables from those installed in non-IS circuits. In many cases, the type of connection made in the hazardous area is restricted to eliminate the possibility of arcing (as with quick-disconnect cables).

    • @bitebonumbere1426
      @bitebonumbere1426 Před 2 lety

      @@realpars Thank you RealPars.

  • @docteresamo703
    @docteresamo703 Před 2 lety

    Another interesting video on safety. Is Siemens ET 200iSP better to use in the field as DP compared with the inc. safety barriers?

    • @realpars
      @realpars  Před 2 lety +1

      The ET200iSP I/O cards have IS barriers built into the I/O card. It is a matter of convenience and cost to use the ET200iSP system versus a standard PLC I/O card with external IS barriers. Remember, that all systems placed into or interfacing with Zone 1, Zone 21, or Class 1 Div 2 or Class 2 Div 2 areas, must be designed for the appropriate level of protection from the field instrument through to the PLC or DCS. Just installing ah IS barrier or ET200iSP system is not alone sufficient to ensure safe operation.

  • @cleversomtoyoda8086
    @cleversomtoyoda8086 Před 2 lety

    Very Nice!

  • @nikhilpatil9231
    @nikhilpatil9231 Před 2 lety

    Sir please make videos on mitsubishi plc

    • @realpars
      @realpars  Před 2 lety +1

      Thanks for your topic suggestion, Nikhil!

  • @shaun1961hodge
    @shaun1961hodge Před 2 lety

    What happens if the field instrument is not ATEX certified?

    • @realpars
      @realpars  Před 2 lety +1

      If an instrument is not ATEX certified, then there is no guarantee that the construction of the instrument and its circuitry will provide the level of protection against flammable hazards that may be required.

    • @shaun1961hodge
      @shaun1961hodge Před 2 lety

      @@realpars even if it’s a simple device

  • @abulfazibrahimov1990
    @abulfazibrahimov1990 Před 2 lety +1

    👍

  • @user-gc1wu4me2g
    @user-gc1wu4me2g Před 2 lety +1

    Hello
    What beautiful animations!
    What software do you use to make these animations?
    Thank you @RealPars

    • @realpars
      @realpars  Před 2 lety +1

      Thank you! I am actually not sure, as the animations are created by our graphic and animation department.

  • @aminokamad1681
    @aminokamad1681 Před 2 lety

    🔥🔥🔥

  • @jeremyreynolds5497
    @jeremyreynolds5497 Před rokem

    I wish the video in Arabic would be much easier

    • @realpars
      @realpars  Před rokem

      Hi Jeremy,
      Thanks for your comment! We currently only provide our course videos in English, you are always able to turn on the English subtitles as that might make it a bit easier for you.