HVAC Pressure Testing a Refrigerant Line with Nitrogen!

Sdílet
Vložit
  • čas přidán 7. 07. 2017
  • In this HVAC Video, I go over how to Pressure Test Refrigeration Lines for an Air Conditioner. I show where to Find the Max Design Pressure, how long to hold the test, how to check the joints, and how to do an initial test before doing the higher nitrogen pressure test. Always follow manufacturers' instructions if they prescribe higher pressures or a longer wait time. I have the nitrogen tank set on the side so it was close up for the video but I usually stand it up vertically. Supervision is needed by a licensed HVACR Tech while performing tasks as Experience and Apprenticeship garners Wisdom and Safety.
    Tools Used In The Video
    Nitrogen Regulator: amzn.to/2bXdR5f
    Nitrogen Flow Meter: amzn.to/2brvoBg
    Yellow Jacket Refrigerant Gauge Set - amzn.to/2aenwTq
    Refrigerant hoses with valves - amzn.to/2aBumVI
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our Related Videos/Articles
    • HVAC Pressure Transduc...
    • The Real Operation of ...
    • Pressure Testing Gas L...
    • Top 7 Crucial Tips for...
    • HVAC Pressure Testing ...
    • Furnace Pressure Switc...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Educational Books, E-Books, Workbooks, Cards, Posters, and PowerPoints:
    All Our Educational Products on Our Site: www.acservicetech.com/store
    All Our Educational Products on Amazon: amzn.to/48pDd82
    Mini Split Book and E-Book on Our Site- www.acservicetech.com/mini-sp...
    Mini Split Paperback on Amazon- amzn.to/3ytHJSs
    Mini Split Paperback on TruTech Tools- www.trutechtools.com/BooksGui...
    Refrigerant Charging Book and E-Book: www.acservicetech.com/ac-book
    Refrigerant Charging Paperback on Amazon: amzn.to/46xTeHf
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Online Resources!
    Our HVAC Calculators: www.acservicetech.com/hvac-ca...
    Our Newest Articles: www.acservicetech.com/articles
    Try our HVAC/R Quizzes! www.acservicetech.com/quizzes
    Our Other Resources: www.acservicetech.com/resources
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Tools Used in Our Videos!
    Tool Links on Our Site: www.acservicetech.com/tools
    Our Tool List on Amazon: www.amazon.com/shop/acservice...
    Support the Channel by purchasing tools through TruTech Tools!
    Use this link www.trutechtools.com/?aff=8
    Save 8% at checkout using code "acservicetech"
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Follow Us On Our Social Media & Podcasting Channels!
    Patreon: / acservicetech
    Facebook: / acservicetech
    Instagram: / acservicetech
    X: / acservicetech
    LinkedIn: / ac-service-tech-llc
    Tiktok: / acservicetech
    Spotify: open.spotify.com/show/74KXLz5...
    Apple Podcasts: podcasts.apple.com/us/podcast...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    ⚠️ Disclaimer:
    Information in this video is intended for educational purposes only. Any work related to the topics in this video should be performed by licensed technicians or by apprentices under the supervision of licensed technicians. AC Service Tech LLC is not responsible for any possible damages or injuries caused by the use or misuse of any information provided. ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    #hvacr #hvacr #hvactrainingvideos #hvactraining #hvactraining101 #acservice #acservicetech #oil #pressuretest #leak #leaktest #hvacleak #hvaclife #pressure
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal.

Komentáře • 99

  • @acservicetechchannel
    @acservicetechchannel  Před 7 lety +2

    Tool List- www.amazon.com/shop/acservicetech
    Support- www.patreon.com/acservicetech
    For those that are looking for the tools used in the videos: (Linked Below)
    Here is a link the Nitrogen Regulator amzn.to/2bXdR5f
    Here is a link to the Nitrogen Flow Meter amzn.to/2brvoBg
    Here is a link to the Air Acetylene Torch setup- amzn.to/2aQalsb
    Here is the Link for the Yellow Jacket Refrigerant Manifold Gauge Set used in the videos-
    amzn.to/2aenwTq
    Here is a link to Refrigerant hoses with valves used in the videos- amzn.to/2aBumVI
    Here is a link to the Digital Refrigerant Scale used in the videos-
    amzn.to/2b9oXYl
    ACSERVICETECH is a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to Amazon.com.

  • @daviddelamaterii5801
    @daviddelamaterii5801 Před rokem +1

    Video description was very understandable and informative

  • @thisisyourcaptainspeaking2259

    Glad to see you doing this at a meaningful pressure, I see many barely pressurizing @ well below realistic values, sloppy work.

  • @jimbola77
    @jimbola77 Před 7 lety +2

    excellent video thank you for sharing!!!!!!

  • @Honestandtruth
    @Honestandtruth Před 2 měsíci +1

    As Always Thank you Teacher Craig 🙏👍

  • @officialmultie
    @officialmultie Před 3 lety +1

    Good stuff man

  • @kevinblankenship2433
    @kevinblankenship2433 Před 5 měsíci +1

    The yellow hose has a ball valve on it, right off the regulator. You can have both the red and blue manifold valves open, and throttle it at the ball valve on the yellow hose. Also, you could bring it up slowly by the screw on the nitrogen regulator. This helps, if you have digital gauges that are very sensitive.

  • @zekenzy6486
    @zekenzy6486 Před 7 lety +1

    great video. thanks you

  • @whitesheatingairappliancer7101

    Great video thank you.

  • @dcrickerson7611
    @dcrickerson7611 Před 7 lety +2

    Another great video! Thank for all your time and effort in making these video's.

  • @MdRizwan-by4hp
    @MdRizwan-by4hp Před 3 lety +1

    Thank you sir 🙏

  • @angelzucchet8543
    @angelzucchet8543 Před rokem

    Excelent thank you 😄

  • @guillermotejeda692
    @guillermotejeda692 Před rokem +1

    My gauges having been equalizing the high side seems to be about 20 psi more each timeI pressurize, any idea why?

  • @Louisyongcool2328
    @Louisyongcool2328 Před 4 lety +1

    One question can i use dye and nitrogen together to test the unit?

  • @paulkurilecz4209
    @paulkurilecz4209 Před 3 lety

    Is ten minutes at the test pressure with no pressure drop considered sufficient that only extremely small leaks exist? Is this best way to find very, very small leaks to put about 10 psig of refrigerant into the line set and evaporator and then pressure up with N2 to the test pressure? TIA

  • @monikarealtor2876
    @monikarealtor2876 Před 6 měsíci +1

    Good morning
    My ac refrugrent line exploded under the house is it possible to perform nitrogen pressure test on already broken pipe.
    Please let me know

  • @tommyteamer9037
    @tommyteamer9037 Před rokem

    Amazing video on showing how to do a pressure test.

  • @MrMagsimus
    @MrMagsimus Před 2 měsíci

    Thanks nice video

  • @cameronstrong100
    @cameronstrong100 Před 2 lety +1

    I'm sorry, did you say both of the Schraders we're out while nitro pressure testing?

  • @poryeyang1854
    @poryeyang1854 Před 7 lety

    i was wondering if you can do a review on the best leak detectors and which one picks up better..etc..and which one you prefer most.

  • @sergiodoordie319
    @sergiodoordie319 Před 6 lety

    Hey great video man so u did all this work without the valves on the service ports right ?

    • @acservicetechchannel
      @acservicetechchannel  Před 6 lety

      Thats correct, I put the valve cores back in after breaking the vacuum with the refrigerant, thanks

  • @raindogs451
    @raindogs451 Před 10 měsíci

    My only objection to brazing is that Stay Bright is almost always a superior connection; shear strength, tensile strength and bursting strength. Only in melting point (med gas) and sloppy connections is brazing worth a darn. Maybe dissimilar metals too. HVAC orthodoxy says "flux is evil" in spite of the fact it is used in some brazing too. Soldering is just a better connection in most applications.

  • @abbe6305
    @abbe6305 Před 5 měsíci

    when i braze in a new compressor, scroll copeland, i need to have nitrogen, its it correct that i put nitro on low side and blow out on the high side? Becuse the compressor have a rewerse seal on high side in compressor and can damage the seal?. correct? so its ok to flow nitrogen in to the compressor while braze?

  • @geoffrey5239
    @geoffrey5239 Před 3 lety

    Nice video and just what I was looking for in installing a split unit system. I note that you did not close off the nitrogen supply until the end. Would it not be better to shut off the nitrogen supply while you are waiting to see if the pressure drops in the system ?

    • @acservicetechchannel
      @acservicetechchannel  Před 3 lety +1

      Yes I could have, however, I had those handles shut and the pressure in the regulator was not much more but yes, I could have taken the pressure off at the tank reg, thanks!

    • @geoffrey5239
      @geoffrey5239 Před 3 lety

      I withdraw my comment - I did not appreciate that you had closed the manifold's connection to the Nitrogen cylinder while waiting to see if the pressure held !

  • @calledout4437
    @calledout4437 Před rokem

    Hey thanks for the video. I'm getting ready to replace my compressor. What if I don't have nitrogen? Is there some other effective way to test? Or if I'm confident in my joints while I know it's not recommended, can I just skip the pressure test?

    • @kinetic1259
      @kinetic1259 Před 7 měsíci

      I noticed in the installation guides for some new models don't require a nitrogen pressure test anymore (at least for warranty), only confirming that the piping and units hold a vacuum of -76 cmHg (­-0.1 MPa) for 15 minutes before releasing refrigerant into the system.
      Still a good idea... But not technically required for warranty.

  • @joes4407
    @joes4407 Před 4 lety

    If manual for Lg heat pump says to pressure test to 550psig but condenser has 450psig operating pressure labeled on unit, what would you recommend? Thank again.

    • @acservicetechchannel
      @acservicetechchannel  Před 4 lety

      If you have a digital manifold you can pressure test to 450 and see any drop very quickly compared to a compound gauge. If it is an older unit then only pressure test to 200 or maybe 300psi. You don't want to cause a leak, thanks!

  • @khybersafi9137
    @khybersafi9137 Před 4 lety

    How do you flow nitrogen from one side to the other if the coil has a non-bleed TXV? Thanks.

    • @exclusive_148
      @exclusive_148 Před 2 lety

      Let nitro in through both sides. Then let it out

  • @baleDELgavilan713
    @baleDELgavilan713 Před 6 lety +1

    Didnyou recover the refrigerant into the compresor or into a vacuum?

    • @acservicetechchannel
      @acservicetechchannel  Před 6 lety

      Initially, when taking out the old unit, the compressor internal pressure relief blew when doing the pump down as it was very weak. I just shut the valves and recovered the rest. I wanted to reuse this unit ans a testing unit at my shop. Usually you will just recover everything out and not pump down unless you are reusing a unit, thanks.

  • @Twoface0233
    @Twoface0233 Před 4 lety +1

    Why do you have to take the schrader cores out before brazing? And what exactly happens to the service valves if you don’t protect them?

    • @marconantel7735
      @marconantel7735 Před 3 lety +1

      They are pretty easily damaged from heat, orings and seals

  • @daryllneuburger4946
    @daryllneuburger4946 Před 7 lety

    I have recently been taught to slowly add thru the high side then slowly thru the low side I was told by adding to fast can cause the TXv to slam shut I personally have not had this happen but wondering your thoughts I have been replacing a few TXv s lately due to the installers adding the nitrogen to fast or that's what are senior tech says

    • @acservicetechchannel
      @acservicetechchannel  Před 7 lety

      That could possibly happen. It could also be the tech brazing the suction line for a long time without removing the bulb or an install brazed without nitrogen and the byproduct mixing with anti corrosives put in by the manufacturer. You should always add nitrogen into both the high and low sides at the same time. You can add it fairly quickly that way with no problem. When you say adding refrigerant into the liquid side, I am assuming that you are talking about breaking a vacuum with liquid refrigerant after doing something like a compressor changeout or weighing in refrigerant by weight per foot. Yes slowly add through the low side while on and best to use a kwik charge vaporizer to keep the compressor safe, thanks!

    • @daryllneuburger4946
      @daryllneuburger4946 Před 7 lety

      thanks for your responce the way you do it was the way i was taught but i try to never stop learning the way i was taught is not always the best lol

    • @acservicetechchannel
      @acservicetechchannel  Před 7 lety

      Thanks Daryll!

  • @ddcws1
    @ddcws1 Před 5 lety

    If you find a system almost completely out of refrigerant then recover the remaining refrigerant, pressure test with nitrogen and find no leaks. Should you put system under vacuum?

    • @acservicetechchannel
      @acservicetechchannel  Před 5 lety +1

      Hey David, yes pressure test with a digital gauge set for more precise measurements over a shorter span. If it doesn't drop after 10 minutes then there is not a leak. Remember nitrogen will still fluctuate due to temperature but very little compared to air. It could have leaked through the valve cores or there is the possibility of someone releasing it on purpose. After you get done the job, make sure to put locking caps on the ports. This way you know people are not able to get into the system without the key. The standing vacuum test will also verify no leaks, thanks a lot David and Great to hear from you!

  • @marcolopez9476
    @marcolopez9476 Před 23 dny

    Where can I buy and recharge nitrogen cylinder in Texas?

  • @ekie85
    @ekie85 Před 11 měsíci

    Are you using dry nitrogen or nitrogen?

  • @80SWoods
    @80SWoods Před rokem

    Do you have to use nitrogen to pressure test? I’m installing my own system and was hoping to use welding gas (argon/O2) since that’s what I have on hand. I “assume” the vacuum pump will pull anything all out anyhow when I do that step.

    • @A-bone
      @A-bone Před rokem

      Don’t use argon

    • @DaleKlein
      @DaleKlein Před rokem

      @@A-bone Why not? (beside the probably extra cost of CO2/Argon mix vs. N2)

  • @geometric2194
    @geometric2194 Před rokem

    Do you keep your Schrader valves out still when pressure testing?

    • @jayweiner977
      @jayweiner977 Před rokem

      You can. If you have a shrader removal tool it’s best to use that. Also makes your vacuum faster.

  • @fastlife866
    @fastlife866 Před 7 lety +1

    i have a technical question.. I was on a job today. r22 two ton unit with txv. evap is clean, filters clean, good airflow, condenser is clean good airflow. my question is I have 1 degree subcooling and high superheat. aprox 80 psig lowside and 201 psig high side. suction line temperature was 75F. i have 14 degree split across both indoor unit and outdoor unit. pressures are steady no fluctuations. unit is 2006. acording to my chart it says to add refrigerant but my suction saturated temp is 50 degrees. my guess is a bad txv what do you think my issue is?

    • @acservicetechchannel
      @acservicetechchannel  Před 7 lety

      Hey Brian, was it extremely hot and humid in the house possibly and there is that much heat in the refrigerant. What was the dry bulb outside?

    • @fastlife866
      @fastlife866 Před 7 lety

      acservicetech house was 79 inside, my outdoor dry was 84

    • @yonkromis7883
      @yonkromis7883 Před 6 lety

      @@fastlife866 tell me what the chart says or let the house cool down to the right temperature and test ir again

    • @fastlife866
      @fastlife866 Před 6 lety +1

      @@yonkromis7883 if i remember correctly i added refrigerant to bring the superheat down. Even though my pressures were higher then average the superheat n subcooling i got dialed in and it was working fine.

    • @yonkromis7883
      @yonkromis7883 Před 6 lety

      @@fastlife866 thank you for your timely response I figured that was the thing that you did

  • @fluoridaman2332
    @fluoridaman2332 Před 6 lety

    Can you use Dawn dish soap as the bubble leak detector?

    • @acservicetechchannel
      @acservicetechchannel  Před 6 lety

      We try to stay away from all dish soaps now, including Dawn. Just use non corrosive bubble leak detector. It is cheap, works well, and won't corrode the pipe, thanks- If you are looking for the right kind, I have the Rectorseal version I use linked at amazon.com/shop/acservicetech thanks

    • @fluoridaman2332
      @fluoridaman2332 Před 6 lety

      What if I rinsed it off good with a neutralizer like water and vinegar? Also, does that Rectorseal work as a leak detector and braze work sealant?

  • @ashyurivillanueva6095
    @ashyurivillanueva6095 Před 4 lety

    SIR, GOOD DAY! WHY THE PRESSURE OF MY SUNCTION LINE IS 55PSI THEN ALL OF A SUDDEN ITS DROP IN 30PSI? BUT MY AMPERE READING IS STILL 14.4AMPS? PLEASE HELP! THANK YOU! 🙂

    • @ashyurivillanueva6095
      @ashyurivillanueva6095 Před 4 lety

      LG MODEL: TP-C808FLA1. 72,000 BTU. R22. 3PHASE. NORMAL AMPERE 14.0A MAX 18.5A

  • @dougharsch9995
    @dougharsch9995 Před 5 lety

    What size nitrogen bottle and how much nitrogen is needed on a typical job for soldering lines and then pressure testing?

    • @acservicetechchannel
      @acservicetechchannel  Před 5 lety

      We use a 60cf or 40cf tank. I carry 60cf tanks in the truck and I use maybe a 1/4 of a tank each install, thanks and I have the nitrogen regulators and nitrogen flow regs that I use linked at amazon.com/shop/acservicetech

    • @dougharsch9995
      @dougharsch9995 Před 5 lety

      @@acservicetechchannel Thanks

  • @JacobandAlaina
    @JacobandAlaina Před 5 lety

    What size nitrogen tank did you use?

  • @Pretzel114
    @Pretzel114 Před 7 lety

    Thanks for the video Acservicetech. For R22 if no safe psig is given you only go to 150psig then what is a limit for r410 if there is no max psig listing on the unit? Thanks again.

    • @acservicetechchannel
      @acservicetechchannel  Před 7 lety

      Most R410A Evap coils are newer and usually have a max design pressure uless they were retrofitted from r-22 to r410a with a piston or txv change.If that is the case then I still wouldn't go much higher than 150, maybe 200 at the max. If the coil is newer within the last ten years or so and cooling only then maybe test up to 250-300, thanks Nick!

    • @Pretzel114
      @Pretzel114 Před 7 lety

      acservicetech Thanks for the reply acservicetech. Helps expand my knowledge a little more lol. take care

    • @acservicetechchannel
      @acservicetechchannel  Před 7 lety

      Glad to help Nick!

  • @MrSpartan117fan
    @MrSpartan117fan Před 5 lety

    I build refrigeration units and the company asks for a 250 psi test for 20 minutes and nomatter what the guages will stay put for a few minutes then start dropping . I check every joint with soap and nothing . The system then holds vacuum no problem . Dont understand whats happening you have any insite?

    • @acservicetechchannel
      @acservicetechchannel  Před 5 lety

      It is possible that the setup used for pressure testing is leaking or the bottle is hotter than the system which causes the pressure to lower.

    • @MrSpartan117fan
      @MrSpartan117fan Před 5 lety

      @@acservicetechchannel I have tested my guages with soap and submerged the hoses in water and there are no leaks . If the nitogen is cool the pressure will drop when its in the system? I use a large nitrogen bottle that is around 5 feet tall in a space where the ambient temperature is around 24-25 C . Could what you said about the nitrogen be my problem?

    • @acservicetechchannel
      @acservicetechchannel  Před 5 lety

      Certainly, especially if its holding vacuum during a ten minute standing vacuum test and this same thing happens every time, thanks

    • @MrSpartan117fan
      @MrSpartan117fan Před 5 lety

      @@acservicetechchannel Thank you very much for confirming with me !

  • @wildman8601
    @wildman8601 Před 6 lety

    If the condenser has a filter already installed is it still smart to add another filter dryer in the attic ??

  • @ergarzavala2330
    @ergarzavala2330 Před 6 lety

    Can you leave the gauges open when pressure testing

    • @acservicetechchannel
      @acservicetechchannel  Před 6 lety

      I wouldn't. I want as much control as possible that take out of play a possible leak in the nitrogen regulator or gauge set. Remember that when the handles are shut then the pressure is just going straight to the gauges but if the handles are open then it connects to the service hose and regulator, thanks

    • @ergarzavala2330
      @ergarzavala2330 Před 6 lety

      Thanks for the explanation

  • @user-ki3lt1yp8e
    @user-ki3lt1yp8e Před 2 lety

    لماذا لاتخبرهو الخصائص الغاز الخطيرة السام ...والقابل للشتعال .....

  • @julianomartinez6080
    @julianomartinez6080 Před 11 měsíci

    Question for anyone: as you can see, the technician in the vid is using the refrigerant gas gauges for the process of injecting Nitrogen to 50 PSI first, and then up to 300 PSI into the system. However those are not Nitrogen gauges. They're rather gauges for the specific refrigerant gas of that air conditioner. The only valid Nitrogen gauges are the ones connected to the Nitrogen bottle. So when he's reading "50 or 300 PSI of Nitrogen" at the refrigerant gauges, he may not have that pressure at all. The question is: what's the actual pressure he should read at the refrigerant gauges for 50 and 300 PSI of Nitrogen, respectively, and why?

    • @kinetic1259
      @kinetic1259 Před 7 měsíci

      As long as you purge your gauges and hoses with.... Wait for it... Nitrogen 😂
      Beforehand, you're good to go, what you're talking about is mixing different refrigerants.
      Also, some refrigerants operate under different pressure ranges.

  • @throttlebottle5906
    @throttlebottle5906 Před 7 lety

    you could have gotten away with saying "pounds" vs psig.

  • @goru426
    @goru426 Před 5 lety

    Is it not dangerous for a person to release so much Nitrogen so close to himself? After all Nitrogen can displace oxygen from your lungs.

    • @acservicetechchannel
      @acservicetechchannel  Před 5 lety +1

      Nitrogen is roughly 80% of the air and this was outside so it was fine but it also very controlled as well. You want to make sure to not shoot the rubber grommet from the end as well, thanks!