Water Load Accident ❌ Big Generator Load Trial 1010KVA | 4K

Sdílet
Vložit

Komentáře • 43

  • @alisaad4913
    @alisaad4913 Před 5 měsíci +8

    Hello bhai generator safe hai na

  • @billmoran3812
    @billmoran3812 Před 5 měsíci +8

    That drum is way too small for the kind of power being dissipated. Way too much salt too.
    Boiling that hard will further concentrate the salt causing a runaway condition. Essentially that’s what happened when they pulled the electrodes out. Very salty water dripping off close spaced electrodes caused the arcing. Extremely dangerous.
    They need a tank of water about 10 times larger for a generator that size. And much bigger electrodes spaced at least 2-3 feet apart.

    • @surajdieselgenerator
      @surajdieselgenerator  Před 5 měsíci

      Actually the problem occur was due to our engineer put salt on the backalite. It should have been properly dissolved in the water. That salt did the spark

  • @PortableGeneratorServices
    @PortableGeneratorServices Před 5 měsíci +3

    That blue tank is maybe large enough for a 15kw unit for a short time.
    You do not want the water boiling like that. With the water boiling like shown the plates can not stay 100% in contact with the water. The water is being blown away from the plates due to the boiling. Boiling allows air pockets Resulting in the fluctuating amperage.
    Salt is not necessary if the tank is large enough. I did 2 such load bank jobs in a fresh water river.
    Never remove the plates until the breaker is opened.
    The separation of the plates needs to be much greater - we separated our plates about 16”.
    Whoever was in charge should be fired - very dangerous setup.

    • @surajdieselgenerator
      @surajdieselgenerator  Před 5 měsíci +1

      I appreciate your review. But the salt here is used to Check the load on instant. The mistake here happened was. While we were not available our 1 engineer put salt on the Backalite. And that salt didn’t dissolved. You might hai seen dropping salt many times. That’s because we have changed water and added fresh water again. My motive here of uploading video was. In india this technique is used since 1990s. I want to teach our brothers that these kind of accidents can take place.
      Thank you 😊

    • @JPcostarica27
      @JPcostarica27 Před 4 měsíci +1

      Is ok that plates are in line? I mean, should they be placed forming a triangle to guarantee a load balanced?

    • @PortableGeneratorServices
      @PortableGeneratorServices Před 4 měsíci

      @@JPcostarica27 for a resistive load not needed

  • @sree6127
    @sree6127 Před 2 měsíci +2

    No safety

  • @unknowncoder2037
    @unknowncoder2037 Před 4 měsíci +1

    Sir kya bliss ka jo engine ata tha kirloskar electric dg set me bo engine achha hei long lasting hoga plz help kijiye mujhe me kharidna chata hun ek admi se isiliye ouch raha hunn engine kesa hei alternotr kesa hei 62 kva ka dg set hei plz reply

    • @surajdieselgenerator
      @surajdieselgenerator  Před 4 měsíci

      Aap whatsapp kijiye photos. Ham bata denge uski condition
      +919033353459

  • @patel6228
    @patel6228 Před 9 měsíci +2

    😱

  • @argosy440
    @argosy440 Před měsícem +1

    What happens when it arcs like that? Does the generator automatically switch off?

    • @surajdieselgenerator
      @surajdieselgenerator  Před měsícem +1

      If the ACB breaker contains Earth Fault Relay.
      The Breaker will shut down.
      But Generator won’t stop you have to stop it.

  • @teresashinkansen9402
    @teresashinkansen9402 Před 2 měsíci

    480VX421A=202kW If that water barrel holds 190L at 20C° that means it will reach 100C° in about 5 minutes or about 1 minute at full power. That water resistor is way undersized. Also do not take out the electrodes with power on! that's why such thing happened.

    • @surajdieselgenerator
      @surajdieselgenerator  Před 2 měsíci

      Basically the load varies.
      But the calculations you gave is top notch.
      We will consider it.

    • @tjc-gaby9687
      @tjc-gaby9687 Před měsícem

      480v ou 400v ?

  • @zs6vl
    @zs6vl Před 3 měsíci +4

    Those guys are a walking accident.

  • @ghostcrusher5169
    @ghostcrusher5169 Před 4 měsíci +2

    Is this Cummins Genset?

  • @bigmuller1
    @bigmuller1 Před 5 měsíci +4

    That is not a good way to do a load test

    • @surajdieselgenerator
      @surajdieselgenerator  Před 5 měsíci +1

      Yes we know. But the load banks are way too costlier to purchase and to maintain. So we have this alternative. Which is risky. But the footage you saw is rare of rare incidents happened.

    • @urboydexter
      @urboydexter Před 5 měsíci +1

      ​@@surajdieselgenerator so do you guys plan to get the one which is safe

    • @surajdieselgenerator
      @surajdieselgenerator  Před 5 měsíci

      @@urboydexter Yes we are planning to make one instead of buying.

  • @vikrammalviya7917
    @vikrammalviya7917 Před 9 měsíci +4

    Sir esa ku hogya.

    • @surajdieselgenerator
      @surajdieselgenerator  Před 9 měsíci +4

      Excessive Salt Use ho gaya. Salt dalne wale ne Salt ko paani me nhi milaya. Usse BAKALITE me blast ho gaya. Or Load Bank Pighal gaya

    • @vikrammalviya7917
      @vikrammalviya7917 Před 9 měsíci +3

      @@surajdieselgenerator sir i really appreciate your work and your response 👍👍

    • @surajdieselgenerator
      @surajdieselgenerator  Před 9 měsíci +3

      @@vikrammalviya7917 thank you 😊

  • @nothing12299
    @nothing12299 Před měsícem

    V16 turbocharged?

    • @surajdieselgenerator
      @surajdieselgenerator  Před měsícem +1

      Yes. V16 Turbocharged
      3067 Litres of displacement.

    • @nothing12299
      @nothing12299 Před měsícem

      @@surajdieselgenerator ok thanks for the information

  • @sahilshaikh6290
    @sahilshaikh6290 Před 4 měsíci +2

    Mccb trip huva ki nahi

  • @wiltonsurya4600
    @wiltonsurya4600 Před měsícem +1

    too much salt