How to solve Error E3 [ Daikin Aircon ] RZR60LVVM

Sdílet
Vložit
  • čas přidán 12. 09. 2024

Komentáře • 51

  • @sv6k0a39
    @sv6k0a39 Před rokem +2

    Classic dirty coil service call. Nice work!

  • @gowthameditz1367
    @gowthameditz1367 Před rokem +1

    First like and first comment. Thank u sir for ur videos🙏🙏🙏

  • @comeonwindows7
    @comeonwindows7 Před rokem +1

    Very nice thank you uncle Bon

    • @BonMj
      @BonMj  Před rokem

      You are most welcome

  • @salimagwan9672
    @salimagwan9672 Před rokem +1

    👍🔧 nice job sir

  • @rahatislam9583
    @rahatislam9583 Před rokem +1

    Thanks for valuable video...

  • @w0lvez1
    @w0lvez1 Před 10 měsíci

    When PVE oil get contaminated with POE oil it will cause restriction & sludging according LG manual which also uses PVE oil like Daikin. It clearly says not to use POE oil even on flare connection. When manifold gauge is connected to a R410a & R32 systems ridiculous amount of oil gets in the hose.

  • @JuanTodoli
    @JuanTodoli Před rokem +1

    My mentors used to say: 50% of the time of a good tech is to keep clean the systems.

  • @mdzakariaimtiaz9116
    @mdzakariaimtiaz9116 Před rokem +1

    Very good explain. ❤

  • @rekabersaturesources
    @rekabersaturesources Před rokem +1

    Hello mr bon nice job

  • @karaors8970
    @karaors8970 Před rokem +1

    Good job bro. 🧿👍👍🇹🇷👋

  • @mojeshmeenuga8432
    @mojeshmeenuga8432 Před rokem +1

    Thanks sir

  • @cantaronaenriquejr9907
    @cantaronaenriquejr9907 Před rokem +1

    NICE SIR BON

  • @MuhammadMinhajulAbidin
    @MuhammadMinhajulAbidin Před 5 měsíci +1

    Hi Mr Bon, do you conduct any courses?

    • @BonMj
      @BonMj  Před 5 měsíci

      No, sorry

  • @Marcoguima45
    @Marcoguima45 Před rokem +1

    Good Job 😎🇧🇷

  • @saret490
    @saret490 Před rokem +1

    I like your video ❤❤❤❤

  • @bunyamingul9607
    @bunyamingul9607 Před rokem +1

    👍👍

  • @ddxxbb1
    @ddxxbb1 Před rokem +1

    I have daikin 2.0T unit that started to lose performance, it's two years old only in a dusty environment of Dubai, when checking the app the discharge temp for outdoor unit reach 106c, does that mean the condenser coil needs cleaning? There's no error codes but only lost cooling performance, before it can cool my room to 18c quickly and now barley 23c. What could be the problem?(it also uses more power)

    • @BonMj
      @BonMj  Před rokem +2

      May outdoor temperature too high , what is the outdoor intake temperature

    • @ddxxbb1
      @ddxxbb1 Před rokem

      @@BonMj
      Madoka thermostat set to max(21c) Room temp stuck at 24c, it should be 18c.
      Indoor Unit
      Th1
      INLET AIR TEMPERATURE 26 °c
      Th2
      HEAT EXCHANGER TEMPERATURE (LIQUID PIPE) 16 °C
      Th3
      HEAT EXCHANGER TEMPERATURE (GAS PIPE) 19 °C
      Outdoor unit
      Th
      OUTDOOR AIR TEMPERATURE
      48 °c
      Th2
      HEAT EXCHANGER TEMPERATURE
      57 °c
      Th3
      DISCHARGE PIPE TEMPERATURE
      94 °c

  • @electrolatif
    @electrolatif Před rokem +1

    Like always good job and best repair

  • @karimchiu7527
    @karimchiu7527 Před rokem +1

    ty sir

  • @toufikmatib9855
    @toufikmatib9855 Před rokem +1

    I was working on an AC unit today and it only did the heating and not the cooling. What could be the problem? No error code showing. Please can you help me? Many thanks

  • @sv6k0a39
    @sv6k0a39 Před rokem +1

    Isn't 90psi too low for R410A?

    • @sv6k0a39
      @sv6k0a39 Před rokem

      I see it went up to 110psi towards the end of the video. I usually like to see around 115-120 psi for R410A. But you have more experience than me. Perhaps this is normal for Daikin Inverter systems?

  • @koonsinkok4750
    @koonsinkok4750 Před 4 měsíci +1

    所以原因是CU的coil肮脏?

    • @BonMj
      @BonMj  Před 4 měsíci

      这个case是

  • @toufikmatib9855
    @toufikmatib9855 Před rokem +1

    When I put the remote on cooling mode it was still blowing hot air.

  • @janshaw5472
    @janshaw5472 Před rokem +1

    从后面coil 看起来不是很脏。。。。

    • @donovandavis5310
      @donovandavis5310 Před rokem +1

      Diesel particulate soot dosent reveal itself on the surface of a condenser coil.
      At our company we stress the importance of cleaning a CU twice annually when the is high road traffic areas.
      IT WORKS 😏😏😏

    • @BonMj
      @BonMj  Před rokem

      对,里面很肮脏,用洗最好

    • @BonMj
      @BonMj  Před rokem

      👍👍👍