Control Valve Calibration | Partial Stroke Test of Control Valve

Sdílet
Vložit
  • čas přidán 8. 09. 2024
  • In this video, we are Explain the Control Valve Stroke Test Procedure.
    They are available in various classes as per requirement from PN16 to 1000. The Control Valve is the Final control
    the element that is responsible for controlling the process parameters.
    Connect the multimeter at the valve position feedback output as shown in the setup figure.
    Select the Source function in the universal calibrator and the knob will help to vary the mA (4 to 20mA).
    Select 4mA in the calibrator the control valve will show a 0% valve position. We can verify the valve position on the
    scale provided on the control valve.
    Regards:
    Aadil Chohan
    Please Subscribe us
    / @learnoilandgas
    How to read blueprints
    • How to read blueprint ...
    Pressure transmitter calibration procedure in hindi
    • Pressure Transmitter C...
    Flow meter calibration setup
    • Video
    Follow us on facebook
    / adilchohan44
    subscribe us
    / aadilchohan

Komentáře •