HVAC: LG MULTI V Refrigerant & Oil Acid Testing (Nu-Calgon Oil Test Kit/Qwik Check 2-Second QT2000)

Sdílet
Vložit
  • čas přidán 11. 08. 2023
  • HVAC: LG MULTI V Refrigerant & Oil Acid Testing (Nu-Calgon Oil Test Kit/Qwik Check 2-Second QT2000) #jumpermantech #hvac
    QwikCheck Acid Test Kit (2 Second Acid Test):
    Detects inorganic acid in 2-seconds down to 1 part per million in HVAC/R systems. Fast, accurate, and easy to use, QwikCheck provides an early warning of acid problems. The Yellow to Red color change allows you to easily and clearly communicate the need for action to the equipment owner. Works with all refrigerants and oils. Meets EPA venting regulations. For use, simply insert the valve core depressor into the center of the suction-side, vapor-service/Schrader valve while system is operating.
    The concentrate of acid in refrigeration oil is expressed as an acid number in mg of KOH per gram of oil (milligrams of potassium hydroxide per gram of oil). The acid number is a measure of the amount of hydroxide solution needed to neutralize the acid in the oil. The more acid there is in the oil, the more potassium hydroxide is needed to neutralize it and, so, the higher the acid number.
    Nu-Calgon Phase III Acid Test Kit:
    In the Phase III test, an acid number of 0.05 mg KOH per gram of oil has been set as the maximum acceptable acid concentration in mineral oil and alkylbenzene oil. In polyol esters, the number is generally accepted as 0.16 mg. Mineral and alkylbenzene oils with an acid number less than 0.05 mg or POE’s with an acid number less than 0.16 mg are acceptable and will cause no change in the color of the test kit’s acid indicator. However, if the respective oils have an acid number greater than these limits, it will cause the acid indicator to change from purple to pink or clear indicating that the oil is contaminated.
    GoPro HERO8 Black (Camera Used In This Video)
    amzn.to/3q4FmEz
    Veto Pro Pac TECH MC
    amzn.to/3gURJyZ
    Fluke 902 FC HVAC True-RMS Clamp Meter
    amzn.to/39wvwiK​​
    Fieldpiece ADK7 Deluxe Silicone Test Lead Kit
    amzn.to/3VNYXDv
    Klein Tools ET600 Megohmmeter Insulation Tester
    amzn.to/409iNvu
    Supco M500 Insulation Tester/Electronic Megohmmeter
    amzn.to/42oy0ua
    Fluke 1AC-A1-II VoltAlert Non-Contact Voltage Tester
    amzn.to/3FcWElQ
    Fieldpiece JL3KR4 HVACR Charge Kit (Digital Gauges/Probes)
    amzn.to/3E4W0Fr
    Fieldpiece SPK2 Folding Pocket In-Duct Thermometer
    amzn.to/3mi8Fih
    Fieldpiece SPK3 Folding ROD Dual Temperature Thermometer
    amzn.to/3FbDufQ
    Milwaukee M12 2-Tool Combo Kit 2598-22
    amzn.to/3CtCRNC
    Milwaukee Cut 1 Dipped GLOVES L
    amzn.to/3s8H18O​
    Milwaukee 2351-20 M12 LED Stick Light
    amzn.to/3rVJKEK
    Milwaukee 48-22-1985 Fastback Hawk Bill Folding Knife
    amzn.to/3e53ygW
    Milwaukee 48-22-1500 Fastback Compact Folding Utility Knife
    amzn.to/3qazJkC
    Milwaukee 48-22-4041 Iron Carbide Core Large-Looped Jobsite Scissors
    amzn.to/32fxC6I
    Milwaukee 4932459097 Billet Torpedo Level
    amzn.to/30Dh6Nw
    Milwaukee Wide Blade Magnetic Tape Measure 16 FT
    amzn.to/3yEN7kL
    Milwaukee Fine Pt. Markers Black
    amzn.to/3e4fH5W
    Streamlight 66604 MicroStream USB 250-Lumen Rechargable Pocket Flashlight
    amzn.to/320XiEF
    Klein Tools 11-in-1 Screwdriver / Nut Driver
    amzn.to/3s3o8ql
    Klein Tools 32561 Multi-Bit Screwdriver / Nut Driver 6-in-1
    amzn.to/3e4ur4x
    Klein Tools 32807MAG 7-in-1 Nut Driver, Magnetic Driver
    amzn.to/321n4bW
    Klein Tools 600-4 1/4-Inch Keystone Cushion-Grip Screwdriver
    amzn.to/3J11hS1
    Klein Tools 32581 4-in-1 Electronics Screwdriver Set
    amzn.to/3yEj3WC
    Klein Tools LLK12 L-Style Hex Key Caddy Set 12-Piece (Metric/Sae)
    amzn.to/3yRUiGJ
    Yellow Jacket 18975 Charge Tool
    amzn.to/3J4pfvJ
    Yellow Jacket 60613 Service ratchet Wrench
    amzn.to/3E8iYeZ
    Yellow Jacket 19173 5/16" Female Quick Couplers x 1/4" Male Flare
    amzn.to/3q0TQ4M
    Cooper Bussmann BP-FP-2 Cartridge Carded Fuse Puller
    amzn.to/3e0USrY
    Crescent 2 Pc. X6 4-in-1 Black Oxide Spline Ratcheting SAE Wrench Set
    amzn.to/3qqKlw7
    Crescent 4" Adjustable Cushion Grip Wrench
    amzn.to/3J4qsmL
    Knipex 09 08 240 SBA 9.5-Inch Insulated Ultra-High Leverage Lineman's Pliers (1000v)
    amzn.to/30EQmw5
    Knipex 09 11 240 9.5-Inch Ultra-High Leverage Lineman's Pliers with Fish Tape Puller and Crimper
    amzn.to/3H9iYAu
    KNIPEX Tools - Long Nose Pliers With Cutter, 1000V Insulated
    amzn.to/3e3IEi7
    KNIPEX Tools - Long Nose Pliers With Cutter
    amzn.to/3gUSE2i
    KNIPEX Tools 98 62 02, Flat Nose Plastic Pliers 1000V Insulated
    amzn.to/3p6lFsZ
    KNIPEX - 74 08 200 - High Leverage Diagonal Cutters, 1000V Insulated
    amzn.to/3mh8K5U
    KNIPEX - 74 01 200 Tools - High Leverage Diagonal Cutters
    amzn.to/3F1VScb
    KNIPEX Tools - Cobra QuickSet Pump Pliers, 1000V Insulated
    amzn.to/3sftr5Q
    KNIPEX Tools 3 Piece Cobra Pliers Set
    amzn.to/3FbRwy7
    KNIPEX Tools Pliers Wrench 3-Piece Set
    amzn.to/3nnRLfW
  • Věda a technologie

Komentáře • 59

  • @user-io5zo3to7r
    @user-io5zo3to7r Před 4 měsíci +3

    Hey Jumper man, I love watching your videos. I'm an LG startup tech and would like to share some info with you. Just so you know LG VRF systems can operate, on the low side, down to a low pressure of 43psi if outdoor temps are close to 5° F. Those low pressures can be normal IF other parameters are met. Like; High pressure trace in line with its high pressure target ,inverter discharge temperature in range, EEV's indoor and outdoor are in normal range (with good airflow across coils), compressors and fans operating in their range. I would advise getting an LGMV wifi module and download the free software from LG onto your laptop, that way you could see other things like oil sensors and thermistor info. Also, you can directly control ALL the IDU's, from your laptop, connected to the ODU on the roof. Let me know if you would like more info. I could send you a parameters chart. Thanks

  • @HVAC544
    @HVAC544 Před 11 měsíci +5

    Looks like you finally found out why they are failing. VRF can be rather hard to determine issues as they can be multi layered. Going back and trying to figure out if they were installed and commissioned right is very time consuming. I have experience with the Gen 5 LG VRF's we have a few problem sites my company installed. We kept losing compressors and no one could figure it out. Turns out airflow was never set on the ducted airhandlers and they specced high static units with large spiral duct. The additional charge for lineset lengths may not also be correct too. Our compressors were being nuked in heating these things really run hard and hot in heating mode.
    Those indoor units look terrible and no doubt causing issues with the compressors.
    I wish people would install the outdoor up on a platform like that around here and do all the piping out the bottom. They always pipe out the front and it makes it annoying to get the compressors out.

  • @aungthiha5050
    @aungthiha5050 Před 11 měsíci +3

    Thank you so much bro. Worth following the channel. Keep it up

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci +1

      You're very welcome & thank you for watching/supporting 🙏🔧⚡️

  • @thesilentonevictor
    @thesilentonevictor Před 11 měsíci +2

    This building keeps on giving 😂jmt professional work

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci +1

      The gift that keeps on giving 😂 Thank you!!

    • @thesilentonevictor
      @thesilentonevictor Před 11 měsíci

      @@JumpermanTech do you work on co2 systems and ammonia as well

  • @Carloshernandez-kk7dp
    @Carloshernandez-kk7dp Před 3 měsíci

    Great video thanks!

  • @samuelsteffan6987
    @samuelsteffan6987 Před 11 měsíci +1

    What i have seen when working on VRV. Is when you have flood back to the compressor, that liquid pushes your oil from the compressor. Meaning, with no oil you get extremely high discharge temps. Almost in all cases, we change the discharge thermister with every compressor changout along with the inverter board. If acidity is present, we always install a liquid line drier.

  • @stevencossaboon3237
    @stevencossaboon3237 Před 11 měsíci +1

    Nice work Jumper man.

  • @ILoveKittys78
    @ILoveKittys78 Před 11 měsíci +2

    you truly are phenomenal 💚😻

  • @scottmaz4063
    @scottmaz4063 Před 11 měsíci +5

    You gotta get the owner to give you the ok to clean all those units. Wow those units are dirty.

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci +3

      Facts. They definitely need the cleaning a preventive maintenance program afterwards. Units are all in that condition. They have around 135 air handlers inside. No wonder there are complaints and many failures 🔧⚡️ Thanks for watching & commenting!

    • @scottmaz4063
      @scottmaz4063 Před 11 měsíci

      Get him to sign up for annual tune ups. Preventive maintenance. Great job

    • @briancarlisi2224
      @briancarlisi2224 Před 11 měsíci

      Despite this being SSDD, I’m finding something new to learn. Thanks for taking the time to video. I certainly appreciate these!

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci +1

      @briancarlisi2224 What is SSDD? Glad you're learning. You're very welcome & I appreciate you & your time🙏🔧⚡️

    • @briancarlisi2224
      @briancarlisi2224 Před 11 měsíci

      @@JumpermanTech SSDD… same sh*t, different day, lol

  • @zekenzy6486
    @zekenzy6486 Před 11 měsíci

    Great Video. Nice Work. Good job. Thank you for sharing

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci

      Thank you very much! You're very welcome & thank you for watching/commenting. Appreciate all your support 🔧⚡️

  • @Laker4life760
    @Laker4life760 Před 11 měsíci +1

    I just changed a compressor on one of these. 24hr vac 👍👍👍

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci

      Thats awesome. Hard work right there. Definitely need a long deep vacuum for a system like this. Thanks for watching & commenting🔧⚡️

  • @christopherleubner6633
    @christopherleubner6633 Před 3 měsíci

    The pink chemical is phenothaline, it is pink in base, yellow in acid
    A stupidly cheap source of it is mylanta gas relif tablets ❤️

  • @oldmetalguy4577
    @oldmetalguy4577 Před 11 měsíci +3

    Scenario: You tell them how to fix the issue, they don't fix the issue, you keep coming out to replace compressors and boards...it would be gravy if it were only at ground level LOL!

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci +1

      Haha facts! Ground level would be amazing. Entering the building we must go down a flight of stairs so just entering the building is a nightmare with all the equipment. Gotta do what you gotta do though. New York City problems. Thanks for watching & commenting 🙏⚡️🔧 Much appreciated metal guy🤙

    • @oldmetalguy4577
      @oldmetalguy4577 Před 11 měsíci

      @@JumpermanTech Man, I am such a primadonna. All these years of ground level or one level up, I watch this east coast stuff and realize pretty quick just how spoiled I've been in TX. Great channel and great work.

  • @jrh86
    @jrh86 Před 11 měsíci +2

    Yep JM airflow restriction as you say, lovely jubbly 😆

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci +1

      Definitely air flow issues and liquid migration considering the entire building is in this shape. Thank you for watching & commenting!

  • @shine-cg9uf
    @shine-cg9uf Před 11 měsíci

    🇺🇸👍❄️💪 nice work. Solve the problem not the symptom

  • @NewDestinationEng
    @NewDestinationEng Před 11 měsíci +2

    Nice work JMT! Have you checked the system alarms? It might help to diagnose the main issue there

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci

      Thank you!! Haven't checked any alarms. Do you mean like a history of error codes? Not sure how that's done. Maybe with the LGMV tool? Appreciate the feedback 🙏

  • @jrh86
    @jrh86 Před 11 měsíci +1

    WOW again !

  • @sontungle2641
    @sontungle2641 Před 3 měsíci

    Tell the building manager to install Daikin VRV IV H :))).

  • @thomasvlaskampiii6850
    @thomasvlaskampiii6850 Před 11 měsíci

    After watching another HVAC tech that lives out in California work, this whole situation makes me feel claustrophobic lol

  • @kheansovannrith6907
    @kheansovannrith6907 Před 3 měsíci

    Great work Sir, May you recommend me the type of oil compressor for LG multi-v?

  • @jrh86
    @jrh86 Před 11 měsíci +2

    From my time in the industry its Installation and no or poor PPM maintenance that most problematic issues develop from.

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci +2

      This is definitely a mix of poor installation, poor service practices & no maintence for 12 years!! Everytime I cleaned a unit, they had to cut down the ceiling just to get access. It's been a ticking time bomb since day 1. Thanks for watching & commenting 🔧⚡️

    • @jrh86
      @jrh86 Před 11 měsíci +2

      Thank you for your time and chanell it's great 😃👍👍👍💯

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci +2

      @@jrh86 You're welcome🙏 Thank for you the kind word and time as well. Stay tuned for new videos every week⚡️

  • @johnwalker890
    @johnwalker890 Před 11 měsíci

    Good job Jumper, I think the system is running high pressure, because the condenser coil and evaporator coil being dirty, I could be wrong, not sure.

  • @DxTalmus
    @DxTalmus Před 11 měsíci +2

    Are there no elevator you can use on that building?

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci +2

      There's an elevator but you need to walk up 2 stories to reach these units on that fire escape/staircase. Thanks for watching & commenting 🔧⚡️

  • @jonnyrottenshvacrchannel5884

    I'd always tell them pay it now or definitely pay more later

  • @jaimegutierrez9930
    @jaimegutierrez9930 Před 11 měsíci +1

    Hey awsome videos bro i live here in nyc. I have a question did you went to a HVAC school ? im looking to get any training hvac related any recommendations? Any good training courses that you know of ? Would help alot. Also is there anyway to contact you through email ? I would like to buy you a nice peter luger steak lol so i could pick your brain? Also have you hear of “Boland” training on VRF ?

  • @arielhernandez2911
    @arielhernandez2911 Před 10 měsíci

    Are you the owner of the hvac company ? If you are that’s dope and the customer never listen especially when system go off on high head pressure cuz they don’t want to pay to get pm done amh

  • @DxTalmus
    @DxTalmus Před 11 měsíci +1

    Can you do a video of the car right now?😃

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci +1

      Ill make a video on that! Thanks for the idea 💡

  • @christopherleubner6633
    @christopherleubner6633 Před 3 měsíci

    Have a come to Jesus meeting with the property manager or owner regarding the unit air handlers being in desperate need of cleaning. They were terrible 😮

  • @user-mk3np8wi8z
    @user-mk3np8wi8z Před 6 měsíci +1

    That piping looks very crappy. If they don't clean the indoor units, the compressor is going to be killed again.

  • @aquaticspecialities5382
    @aquaticspecialities5382 Před 11 měsíci

    Man those units are filthy.

    • @JumpermanTech
      @JumpermanTech  Před 11 měsíci +1

      Facts. The entire building is in this shape. We are talking about 135 air handlers 🤯

    • @aquaticspecialities5382
      @aquaticspecialities5382 Před 11 měsíci

      @@JumpermanTech that’s insane hopefully they approve you for the bid 💪🏻 😂

  • @Cisco132
    @Cisco132 Před 11 měsíci

    LG is the worst VRF ever made, and since they are cheaper than Daikin and Mitsubishi so they get installed by non-professional mom-and-pop shops that don’t send techs to classes to learn how to run nitrogen and install them properly.

    • @sontungle2641
      @sontungle2641 Před 3 měsíci

      In Vietnam we usually install Daikin VRV IV & Panasonic FSV VRF 😎😎😎.

  • @AutoDudes
    @AutoDudes Před 11 měsíci

    LG should be banned from making units.