Danfoss Drives: Understanding EMC & Common Mode (Frequency Converters)

Sdílet
Vložit
  • čas přidán 4. 07. 2024
  • Dive into the intricacies of Common Mode and Electromagnetic Compatibility (EMC) in variable frequency drives in this educational video from Danfoss Drives.
    ▬▬ Contents of this video ▬▬▬▬▬▬▬▬▬▬
    00:00 Introduction
    00:29 Frequency Converters
    01:11 Rectifier
    01:40 IGBTs
    02:36 Switching Frequency
    06:06 Floating Frequency Converter
    07:08 Reducing Common Mode Problems
    08:09 Earth Fault Warning System
    11:15 High Frequency Capacitor Filter
    ▬ Explore how frequency converters transform the incoming supply frequency to control motor RPM and torque, and the challenges posed by common mode and EMC.
    ▬ Discover the role of diode rectifiers, IGBTs, and Pulse Width Modulation in generating AC, and how the neutral point's movement affects motor operation.
    ▬ Learn about the impact of stray capacitance, the benefits of good motors and cables, and solutions like isolating transformers and high-frequency capacitor filters to mitigate common mode issues.
    ▬ Whether you are dealing with onshore or offshore installations, grasp the measures to protect your supply grid from common mode disturbances.
    The frequency converter is a device that provides a simple and effective solution to convert alternating current (AC) into direct current (DC). By using a rotating magnetic field to produce radio waves and interference, the frequency converter can be used to store energy in situations where there is not an abundance of available power. This can create a self-sustaining system and is especially useful in areas where there is no electricity or other sources of power. However, caution should be taken to ensure that a balanced neutral point is used to prevent EMC-causing magnetic fields from forming. Using a frequency converter can be a great way to benefit from energy storage and efficient power conversion.
    #EMC #CommonMode #DanfossDrives
    ▬ About Danfoss Drives 🌐 ▬▬▬▬▬▬▬▬▬▬▬▬
    Danfoss Drives, a member of Danfoss Group, is a global leader in AC/DC and DC/DC power conversion, as well as variable speed control for electric motors. We deliver solutions to meet all your connectivity needs while helping you create an electric motor or power conversion system that has higher energy efficiency and sustainability.
    Follow us on LinkedIn and visit our website for more insights and innovations:
    🔗 / danfossdrives
    🔗 www.danfoss.com/en/about-danf...
    Want to stay updated? ✉️ Subscribe to our newsletter for the latest news and updates! www.danfoss.com/en/campaigns/... 📨
    Thanks for watching. If you found value in our video, please consider subscribing and sharing: czcams.com/users/danfossdriv...
  • Věda a technologie

Komentáře • 35

  • @velmuruganperumal5322
    @velmuruganperumal5322 Před 10 měsíci +2

    Well, your demonstration is very systematic and well designed. Your hard work and interest in teaching make the listeners benefitted, wish you good health and good life.

    • @danfossdrives
      @danfossdrives  Před 10 měsíci

      Hi Velmurugan
      Thanks a lot for the kind words about our video :) We're glad you found it useful.
      Kind regards
      Danfoss Drives Social Media Team

  • @michaelabiera
    @michaelabiera Před 3 lety +3

    That's the best video I've seen so far on Common Mode

    • @danfossdrives
      @danfossdrives  Před 3 lety +2

      Thank you for the positive feedback Michael!
      Best regards
      Danfoss Drives Social Media Team

    • @suodrazah6015
      @suodrazah6015 Před 3 lety +3

      Agreed, @@danfossdrives Great video!

    • @danfossdrives
      @danfossdrives  Před 3 lety +1

      @@suodrazah6015 Thank you very much Harold :)

  • @jameserayburn
    @jameserayburn Před 6 lety +4

    I appreciate you sharing some very good information. Thank you sir.

  • @ibd1977
    @ibd1977 Před 6 lety +1

    Very informative video. Thank you.
    Can you please advise on a how common mode chokes installed in the VSD output effects the floating neutral (star) point in the motor? Will that reduce the voltage and current being capactively coupled through the motors frame and bearings? This is in reference to the Coolblue cores or other chokes and how they actually work to protect bearings.

    • @danfossdrives
      @danfossdrives  Před 6 lety +4

      When chokes are connected on the VSD output between drive and motor it is called a dU/dt filter. It is usually a 1,2% impedance choke with also some small RFI caps on the motor side. Purpose is to increase the voltage rise time on the Pulse Width Modulation (PWM). Unfiltered the voltage rise time is about 2000 volts in one micro second. Stray capacitance in cables and motor will react to this fast voltage change and create HF currents with several negative consequences. The dU/dt filter will be a low pass filter for this HF currents. On the motor side this will result in slower/ longer voltage rise time. Maybe to only 200 volts per micro second. Slower increase rate of voltage in each PWM pulse result in lower HF current leaking to stray capacitance. For the neutral star point in the motor it still is a rotating potential. However, with the slower voltage rise time the stray capacitance in the motor casing will not draw that much HF current as without dU/dt. Less currents flowing trough bearings, less stress on insulation, less HF EMC.

    • @ibd1977
      @ibd1977 Před 6 lety

      Danfoss Drives thank you.
      On another note. In regards to the floating neutral point in the motor. I assume this occurs with motors connected in star? How about motors in delta? Is there a floating neutral in a delta connected motor that has no star point?

    • @danfossdrives
      @danfossdrives  Před 6 lety +2

      Even though there is no physical star point in Delta there is an artificial one as formed by the summary of voltage potential in the 3 phases. So to speak the summary of voltage in the stator winding is rotating just like when in Star.

  • @Sharp_Stone
    @Sharp_Stone Před 15 dny

    Hi, I'm busy with a graduation project about baering currents. Is there any data about implementing a Common Mode Filter to reduce baering currents?

  • @arashsss85
    @arashsss85 Před měsícem

    at time 11:30, it says that if power source is not grounded like ship, those Y high frequency caps are not allowed to be used or they will cause problems. Any explanation why? And how to reduce the common mode voltage seen from DC link +/- terminals to ground or from line A/B/C to ground at input of rectifier?

  • @algoteslaengineering4357

    Thank you.

  • @rogeronslow1498
    @rogeronslow1498 Před 5 lety +1

    The problem is that the pwm outputs are not edequately filtered to reduce cost and vfd drive volume (size). With filtering the high dv/dt waveforms and edges are greatly reduced limiting the capacitive currents. Older drives had better filtering but were bigger and a bit more expensive.

    • @AcrodesignerLNSNI
      @AcrodesignerLNSNI Před 3 lety +1

      Hello Roger. It is true that older drives had slower voltage rise times on the PWM pulses. And the issues with common mode and also voltage stress between winding layers were less with this older drives. However, the slower voltage rise times produced more heat losses on IGBT's. The drive needed more cooling for same motor power, thus bigger size drive and bigger losses. As evolution of drives are towards smaller physical size and less heat losses, the IGBT technology is pushed for higher voltage rise times. A modern drive with low losses will actually stress the motor and cabling with PWM voltage stress way more than an old drive. Thus the issues with both common mode and PWM voltage stress are more important to cope with today than previous years. Also modifying the IGBT switching pattern to produce a more balanced common mode increase the losses and decrease the efficiency of the drive. Which makes the drive less value for the money when valued only for power, size and efficiency. Simplified You could say that to produce a better drive we push more issues over to the motor. More need for robust motors and dU/dt filters, low stray capacitance cabling etc.

    • @rogeronslow1498
      @rogeronslow1498 Před 3 lety +1

      @@AcrodesignerLNSNI I agree 100%.

  • @nileshkubal6649
    @nileshkubal6649 Před 5 lety

    We have a installation with TNS system where common mode filter (ferrite core) is melting due to excessive common mode current.
    The VFD manufacturer is suggesting to convert TNS to IT system.
    Will it help? Since there is a PE conductor running from VFD to motor which will provide return path for common mode current.
    Pls. advise. It's an AFE drive.

    • @danfossdrives
      @danfossdrives  Před 5 lety

      Hi Ishaan
      Regardless of the type grid (TN/IT) you are using, a PE and screened cables are always required. Changing the grid type will not solve your problem.
      About the common mode filter/coils, it is essential that you use coils intended for this purpose. The common mode voltage is 3x Fsw, where Fsw is the switch frequency of the drive. This mean that we are dealing with a high frequency signal. Traditional common mode ferrit cores allow low frequency signals of 50/60 Hz to pass through, but filter out higher frequencies - if exposed to VFD output signal, coils will go into saturation and become really hot (burn).
      The common mode filter needs to be of nanocrystalline magnetic core type in order to allow high frequency PWM signal pass. More info: www.danfoss.com/en-us/products/ac-drives/dds/vlt-common-mode-filters-mcc-105/

    • @nileshkubal6649
      @nileshkubal6649 Před 5 lety

      @@danfossdrives
      Yes, the link shared by you is helpful. How to select the suitable model?
      In our application,
      Motor KW = 560
      Voltage rating = 690V
      Cable size = 3 runs x 3C x 185 sq. mm
      Cable length = 450m (each run)
      Our VFD manufacturer has installed common mode filter on DC bus. He says common mode filter rating is 50A.
      They measured the common mode current with filter in place at DC bus as 150A.
      So we asked him to replace the 50A filter with 150A. But he says 150A filter is not possible to manufacture.
      Is it true? Can you pls. advise on this and also which model of Danfoss MCC 105 to select for above requirement..

    • @danfossdrives
      @danfossdrives  Před 5 lety

      Hi Ishaan
      I'm really sorry, but we can't offer such detailed support here on CZcams. Could I ask you to contact your local Danfoss service office? You can find it here: www.danfoss.com/en/contact-us/contacts-list/?filter=type%3Adanfoss-sales-service-center%2Csegments%3ADDS

    • @nileshkubal6649
      @nileshkubal6649 Před 5 lety +1

      @@danfossdrives
      Thank you for your support.
      We have initiated it with local Danfoss here.

    • @danfossdrives
      @danfossdrives  Před 5 lety

      @@nileshkubal6649 Great to hear, thank you

  • @hans-joachimpoess3728
    @hans-joachimpoess3728 Před 7 lety +3

    Hi I like this simple and very good explanation of Common Mode Current Source. If there is an interest, I can give some Information for suppressing Common Mode Currents by Nanocrystalline Cores (CoolBlue) which are working in the Motorcable as Inductive Absorbers.

    • @danfossdrives
      @danfossdrives  Před 7 lety

      Hi Hans-Joachim, thanks for your reaction. We do supplyh high-frequency common mode cores that
      reduce electromagnetic interference and protect against bearing currents.They are light blue coloured. Is that the ones you are referring to? Rgds Hans

    • @hans-joachimpoess3728
      @hans-joachimpoess3728 Před 7 lety

      Yes, they are already an Option for your drives and I helped to design them in Denmark ;=) Some background regarding Impedances, Absorption the improved design is available. We do have now improved versions of it they do have a (+) at the Number. If you are interested we can have a phone talk about the possible Improvements together with NALa which are line Absorbers for reducing the ringing of dU/dt of the IGBT´s. BR Hans-Joachim (Alias Jochen ;=)

    • @danfossdrives
      @danfossdrives  Před 7 lety

      Okay Jochen, I am not very much into this (as a simple digital marketer), so I don't know much about it. I am also not really sure who in our organization is dealing with this. Are you able to give me your contact details. Then I will try to find and inform a couple of people and advise them to get in contact with you. Rgds Hans

    • @hans-joachimpoess3728
      @hans-joachimpoess3728 Před 7 lety

      At this time the development was done with Norbert Hanigovszki, my contact is hpoess@magnetec.de. If there is some interest, feel free to contact me or to share my contact data. more info´s under www.magnetec.de/fileadmin/pdf/pb_cb.pdf Rgds Jochen

    • @danfossdrives
      @danfossdrives  Před 7 lety

      Thanks Jochen, I have forwarded your message to Norbert and advised him to get in touch with you. Rgds Hans

  • @kamilziom9059
    @kamilziom9059 Před 3 lety +1

    What about motors connected in delta?

    • @AcrodesignerLNSNI
      @AcrodesignerLNSNI Před 3 lety

      Hello Kamil, delta coupling does not change the commond mode issues in the motor much. Simplified You can look at all the copper in the stator windings as one big galvanic lump of copper where the 3 motor phases are connected to the drive. Measuring the DC resistance between motor phases it is small values in the 0,1-0,3 ohms range. So for DC voltage it is like one lump of copper. Impedance for AC current is of course high, otherwise it would be like an short circuit also for the base AC. However, regarding common mode which initially is a pure voltage phenomen, all the copper in the stator windings will be lifted to the sum of voltage in the 3 motor phases. And this sum of voltage keeps jumping around when measured towards PE ground, aka the metal casing of the motor. Regardless of delta or star coupled motor phase windings. To draw a leakage current between copper and PE induced by this common mode voltage the path between is the stray capacitance. Stray capacitance current will be an AC current with the frequency same as the drive switching frequency, typical 3-4 kHz. An AC current of that high frequency emits an magnetic field, EMC noise, that is harmful for other electrical equipment. So we do all kind of measures to reduce the negative effects. Reducing the stray capacitance to a minimum is important. Also keeping the 3 phases and all of its "lumps of copper" inside a faraday cage shielding. The shield, weather it is the cable shield or motor and drives metal casing, need to be bonded together galvanic to get best effect of the faraday cage.

  • @nishan729ei
    @nishan729ei Před 5 lety

    Pls put a lecture on how emc filter acts in vfd & how to select emc filter for a vfd

    • @danfossdrives
      @danfossdrives  Před 5 lety

      Hi
      Thank you very much for your input. For the moment, if you have a question about this topic, please reach out to your local service center: www.danfoss.com/en/contact-us/contacts-list/?filter=type%3Adanfoss-sales-service-center

    • @AcrodesignerLNSNI
      @AcrodesignerLNSNI Před 3 lety

      Hello Nishan, emc filter on motor cables like dU/dt filter please see explanation how it works in one of the comments above here, from ibd1977. Another measure to mitigate negative effects of the PWM voltage rise time is to produce the motor windings with "form windings". Instead of spinning the copper wire randomly around each iron pole, the wire is installed more organized in separate layers. This will not reduce common mode, however it will increase the motor robustness for insulation failures. PWM voltage rise time impose a risk of getting high voltage differences between each strand of copper wire. The insulation is pretty thin on each wire so a high voltage difference can stress the insulation and risk flashing over. Mitigating this a dU/dt filter helps a lot. But an alternative to utilizing a dU/dt filter is to produce the motor with form windings to avoid wires with high voltage differences to be laid close to each other. We see form windings mostly on permanent magnet motors where total drive train efficiency do not like to include the losses of dU/dt filters. Losses on the dU/dt filter is the voltage drop of 1,2% multiplied with the current.