Trip circuit supervision relay function | TCS

Sdílet
Vložit
  • čas přidán 20. 08. 2024
  • Trip circuit supervision relay function ( TCS )
    the following question are going to see in this video
    1.What is Trip Circuit Supervision Relay?
    2.Working Principle of TCS?
    3.Application of TCS?

Komentáře • 85

  • @somanathanraju847
    @somanathanraju847 Před 2 lety +1

    You explanation is very simple and knowledgeable. Any body a bit electrical knowledge can learn.

  • @umerali1956
    @umerali1956 Před 2 lety +1

    Thanks a lot. One of the best videos for Electrical Engineers.

  • @JoelLopez-mc3zl
    @JoelLopez-mc3zl Před rokem

    Thank you Sir for sharing great additional knowledge for me being working in the Oil Gas Refinery. God bless you more

  • @sra1649
    @sra1649 Před 3 lety +3

    Dear Brother, thanks for making such a useful videos. If one has little bit experience can also be able to gain knowledge from you. In running plants or unit went for shutdown every one can't get access to protection system. In this channel you are sharing your knowledge and experience , thank once again for your efforts. Some of your subscribers may discourage due to lack of their experience in the relevant field/ language problem , pl don't bother.
    We are enjoying your videos, pl go ahead.

  • @switchgearguru
    @switchgearguru Před 7 měsíci +1

    very well explained....to the point...

  • @akhilsm6840
    @akhilsm6840 Před 2 lety +1

    Super bro keep going

  • @tusharkantasatapathy2770

    Very Nice Sir !! Really I learned about TCS Relay !! Thanks a lot !!

  • @kurapatianwesh9114
    @kurapatianwesh9114 Před 3 lety +1

    Very good explanation sir..

  • @debatoshbhowmik
    @debatoshbhowmik Před 4 lety

    Super Anna.... Ur explanation are really good

  • @emreistek8685
    @emreistek8685 Před 3 lety +1

    So compact study. Thanks.

  • @petarsimic2303
    @petarsimic2303 Před 4 lety +5

    Excellent explanation!! Can we get more videos about configuring and parameterizing relays?

  • @andhbhakt5552
    @andhbhakt5552 Před 3 lety +1

    Explained very nicely.
    Please share video of LBB protection.

  • @mohsantufail4997
    @mohsantufail4997 Před 4 lety +1

    Excellent work 👍

  • @cricketinformationcapsule

    Sir your explanation is very good.I have one request plz make series wise all video and explain in english. Thanks

  • @malirahulpr
    @malirahulpr Před 4 lety +1

    Thankyou sir it's helpful

  • @georgeabalon6481
    @georgeabalon6481 Před 4 lety +1

    Nice video brother. Very helpful keep up the good work!!! Kudos!!

  • @assamelectricaltechno8732

    Good job sir

  • @ILAYARAJAraja
    @ILAYARAJAraja Před 3 lety +1

    Super anbu

  • @arun4846
    @arun4846 Před 2 lety +1

    Superb 👍

  • @dhrupadsaha4171
    @dhrupadsaha4171 Před 4 lety +1

    Thanks you so much Sir 🙏🙏

  • @mohanrajk6517
    @mohanrajk6517 Před 4 lety

    Excellent explained

  • @dhanjayrai1146
    @dhanjayrai1146 Před 3 lety +1

    Nice, explanation sir,
    Please make a video of generator protection.

  • @najeeb1578
    @najeeb1578 Před 2 lety +1

    Useful momentz thankz alot do you have VAX31ZG0750BA model wiring diagram

  • @ravi4453
    @ravi4453 Před 2 lety +1

    Can you explain AVR drawing of 300MW Alternator....

  • @yousefalotaibi8343
    @yousefalotaibi8343 Před 4 lety +1

    Thank you

  • @sajeshkannnur
    @sajeshkannnur Před 2 lety +1

    Dear bro how to avoid this mal alarm during closing and open because every time it will record fake alarm in scada

    • @baranitech1026
      @baranitech1026  Před 2 lety

      we have to make TCS blocking logic during open and closing time bro ..

  • @gurpreetsinghee
    @gurpreetsinghee Před 3 lety +1

    Tell us about numerical supervision relays, e.g. avana, jvs etc

  • @pritamsinghchauhan1338
    @pritamsinghchauhan1338 Před 4 lety +2

    Why are TCS Relay failure reason.
    TCS relay indicator not glowing Green or Red.

  • @safsaf1222
    @safsaf1222 Před 4 lety +1

    What will be happen if the drop voltage which supplied the A& B coils became near the nominal voltage as the series resistances value became not stable or failed? Maybe tripping coil of c.b will operate. Or ? What will happen?

    • @safsaf1222
      @safsaf1222 Před 4 lety +1

      Also, I am facing the issue for transformer 33kv c.b was opening many times during load without any indication, is that has relation to TCS or not ? Plz advise

    • @baranitech1026
      @baranitech1026  Před 4 lety

      NO

    • @electricalsubstationmainte7671
      @electricalsubstationmainte7671 Před 3 lety +1

      If resistance failed i.e open circuit. isn't it? in that condition Tcs relay will not work.

  • @mohammediqbal9729
    @mohammediqbal9729 Před rokem

    Sir can we connect indication in series with pre close and post close circuit in series with Shunt trip coil, instead of tcs relay

  • @PC_Affairs
    @PC_Affairs Před 4 lety

    If breaker trip continuously TCS showing healthy or not

  • @kundanlal9077
    @kundanlal9077 Před 3 lety +1

    Relay trip coil ko kitni votage deti hai

    • @baranitech1026
      @baranitech1026  Před 3 lety

      approximately it will be 80% but you have to check Pickup and drop test to find this value.

  • @vishnu218177
    @vishnu218177 Před 4 lety +1

    What will happen if both A and B coils got failed....
    It will also account as faulty trip coil .Is it right?

  • @smrutiranjanbeheraelectric6394

    Sir
    In case of Preclosing condition,both A& B coil closing??

  • @MrJamalodeen
    @MrJamalodeen Před 4 lety

    Brother are you giving training to the engineers through training center?

  • @Mhdmnr68
    @Mhdmnr68 Před 4 lety

    👍👍👍

  • @Mhdmnr68
    @Mhdmnr68 Před 4 lety

    Can u explain in 110v dc system how we getting 55v posetive to earth or negative to earth.(normally we ge 110v between + to- .then how geting 55v respect to earth)
    How getting return path when any erth fault occure in 110v dc system

    • @rajeshtk1246
      @rajeshtk1246 Před 4 lety +1

      The DC battery system is to be kept ungrounded normally to avoid leakages. In battery charger, the mid point of the battery cell system is earthed via a high resistance.(Equivalent to not grounding the dc system). This will help you get the +55 V when you test betwen a positive point in the circuit and the earth. Likewise is the case with the -ve and earth. i.e, the return path is via the earthed high resistor.

  • @shihabahmed5399
    @shihabahmed5399 Před 4 lety

    Please could you zoom ?it's not clear, information

  • @yousefalotaibi8343
    @yousefalotaibi8343 Před 4 lety

    Can you explain the Directional oc & ef relay

  • @electricalwithkapil7137

    Sir ,i have one question If we can do preclose connection in post close and vice versa what should be happen?

    • @electricalwithkapil7137
      @electricalwithkapil7137 Před 4 lety

      @@baranitech1026 Sir that's mean there is no effect on TCS indication and trip circuit working.

    • @rajeshtk1246
      @rajeshtk1246 Před 4 lety

      It will cause in TC burn out as the Post Close Supervision path will have a trip supply from the Master Trip relay in the event of a fault. So, after the breaker is opened, the Trip supply will directly come to the TC and it will remain there continuously causing TC burn out. Also, your post close and preclose TC healthy indication will not b available.

    • @adnansworld744
      @adnansworld744 Před 4 lety +2

      @@baranitech1026 & @kapil prasad
      Coil "C" will pick up only when Trip coil open or DC supply fail only.
      During intermittent time , that is CB open to close or open to close - Coil "C" will not pick up , because the coil "C" ( contact ) have inherent delay for Pick up. Hence no alarm will not come during transaction period .

    • @adnansworld744
      @adnansworld744 Před 4 lety

      @@baranitech1026
      Coil C ( Contact) have inherent Pick up delay. Hence coil 'C" never pickup during CB operation transaction period. ( Open to Close or Viceversa)
      It will pick only in Three conditions
      1) DC supply fail
      2) Trip coil open
      3) Loose connection in Trip circuit .
      Thanks Engr. Barani
      Can share your Email ID

    • @electricalsubstationmainte7671
      @electricalsubstationmainte7671 Před 3 lety

      pre close and post close wire ko agar aap breaker end pe change karte hai to kuch problem nahi hoga agar aap TCS relay me change karte hai to TC coil burn ho jayega fault condition me breaker off hone ka baad usse hamesha +ve milte rahega.tc burn ho jayega.

  • @eletricalkingdom7612
    @eletricalkingdom7612 Před rokem +1

    Hindi language

  • @nrathore1908
    @nrathore1908 Před 4 lety

    English k chakkar me short circuit ho jayega sir hindi me bhi bna diya kro

    • @viveksingh3989
      @viveksingh3989 Před 3 lety

      czcams.com/video/alOIhZU7kUU/video.html
      Hindi walo ke liye specially

  • @dilipsahusahu680
    @dilipsahusahu680 Před 4 lety

    Hindi

  • @vijayhotkar1977
    @vijayhotkar1977 Před 3 lety +1

    Hindi nahi aati ky aapako

  • @narendersharma5523
    @narendersharma5523 Před 4 lety

    भाई जी हिंदी में समझाओ

  • @jkj1459
    @jkj1459 Před 4 lety

    WHAT IS A & B PLEASE EXPLAIN FIRST COMPONENTS OF CIRCUIT FIRST BEFORE EXPLAINING THE CIRCUITRY. UP T 1.23 YOUR EXPLANATION WAS GOOD AFTER THAT YOU DID NOT TELL DETAILS "A" AND "B" AND ITS FUNCTION . VERY POOR EXPLANATION SIR . SORRY .

    • @rajeshtk1246
      @rajeshtk1246 Před 4 lety

      A Coil is for Post Close Supervision of Trip Coil. B Coil is for Pre Close Supervision of Trip Coil. If A coil or B coil picks up, the C coil will pick up.