Generac Generator Not Testing! See Why

Sdílet
Vložit
  • čas přidán 17. 08. 2023
  • I ran a service call for this Generac generator a year earlier for issues involving it not starting. Last time it was battery issues and mice, this time it's something else. My videos are made for people in the field not for the homeowners. If you have problems, please call your authorized Generac generator dealer. Be sure to see my video on how to service your generator and how to choose a dealer that is going to have the ability to do your work above and beyond what you're looking for.
    - Purchase your tools at www.trutechtools.com/?AffId=13 and use the offer code SURVIVAL to save 8% on your total purchase (exclusions may apply) -
    - TOOLS I USE -
    FULL LIST ON THIS PAGE - kit.co/hvacrsurvival
    💥 Amazon Store: www.amazon.com/ref=as_li_ss_t...
    SHORT LIST IS BELOW
    Ideal Industries Inc 34-001 - Fuse Puller - amzn.to/3sjaCB7
    RIDGID 31305 Model E-110 9.5" Offset Hex Jaw Pipe Wrench - amzn.to/3Bar08y
    Klein Tools Ratcheting Box Wrench 1/4 x 5/16 amzn.to/3GOpBrG
    KNIPEX Tools - 10" Pliers Wrench amzn.to/3U7RRJf
    KNIPEX Tools - 10" Cobra Water Pump Pliers amzn.to/3Wje8Wn
    Knipex Tools - Mini Pliers in Belt Pouch amzn.to/3WguyyH
    KNIPEX Tools - 4" Cobra XS Water Pump Pliers amzn.to/3UaQiKA
    Bahco -6" Wide Mouth Adjustable Wrench amzn.to/3sHIsMV
    Bahco - 8" Big-Mouth Adjustable Wrench with Rubber Handle - amzn.to/3SPhDB7
    Knipex - 9.5-Inch Ultra-High Leverage Lineman's Pliers amzn.to/3DTLJ2h
    Klein Tools Diagonal Cutting Pliers with Angled Head - amzn.to/3zuBVJb
    Klein Tools Stripper, Crimper Tool - amzn.to/3gQQ6Su
    Klein Tools Wire Cutter and Wire Stripper - amzn.to/3Fs627W
    Klein Tools Kurve Wire Cutters, Heavy Duty Wire Stripping Tool - amzn.to/3FseIuW
    Klein Tools Heavy Duty Automatic Wire Stripper - amzn.to/3SQdZab
    Klein Tools Crimping and Cutting Tool - amzn.to/3TPIgXU
    Klein Tools Screwdriver Adjustable 4 to 8-Inch amzn.to/3Nl6KWz
    IDEAL INDUSTRIES Digital Circuit Breaker Finder - amzn.to/3DoBFwm
    Fluke 376FC AC/DC Clamp Meter with iFlex - amzn.to/3UaNyx2
    Fluke 62 Max Industrial Infrared Thermometer - amzn.to/3SNdwWg
    Fluke 902 FC HVAC True-RMS Clamp Meter - amzn.to/3Ws7OfB
    Fluke 87V MAX - amzn.to/3U6Rlv9
    Fluke Networks Pro3000 Tone Generator - amzn.to/3WedklG
    Fluke - FLUKE-52 Dual Input Digital Thermometer amzn.to/3zwFdf1
    Ideal Safe-T-Grip Fuse Puller - amzn.to/3zsw2w4
    Klein Tools Canvas Zipper Bag - amzn.to/3WgnJxq
    Uni-Paint PX-20 Oil-Based Paint Marker - amzn.to/3sE3R9T
    5 Gallon Bucket Topper and Organizer - amzn.to/3sGi2Ll
    Stabila Magnetic Pocket Level PRO with Holster - amzn.to/3FtYLo0
    Clip & Carry Kydex Multitool Sheath for LEATHERMAN SURGE - amzn.to/3TPJfHA
    Kydex Multitool Sheath for LEATHERMAN WAVE & WAVE + PLUS - amzn.to/3sJlhlg
    Cooper Atkins Thermistor Thermometer - amzn.to/3DLeHkC
    GEARWRENCH Internal/External Ratcheting Puller 7 Ton 2 or 3 Jaw - amzn.to/3FxTU5l
    - CONTACT INFO -
    hvacrsurvival@gmail.com
    - FOLLOW ME -
    Instagram - / hvacrsurvival
    Facebook - / hvacrsurvival
    Warning Notice Disclaimer - Video content listed on the channel HVAC*R Survival is for entertainment purposes only and not meant to be a substitute for not contacting a competent HVAC/R PROFESSIONAL. Do not attempt anything said or seen on my videos, The tasks that are shown are dangerous and deadly without proper training.
    This page contains affiliate links, which means that if you click on the link and make a purchase, I’ll receive a small commission. HVAC/R Survival is a participant in the Trutechtools, Amazon Services Associates Program.
    #hvacrsurvival #hvaclife #hvacservice #hvacr #refrigeration #troubleshooting
  • Zábava

Komentáře • 79

  • @bradmironik6137
    @bradmironik6137 Před 11 měsíci +3

    Every time you have one of these generator videos, I am glad i don't own one. Thanks for sharing the HF tool. I will check it out.

  • @InsanePacoTaco
    @InsanePacoTaco Před 11 měsíci +4

    Dude on the tractor was like "I have a need for speed!"

  • @peterking1134
    @peterking1134 Před 11 měsíci +3

    Miss these gen vids!!

  • @nathanhurst5155
    @nathanhurst5155 Před 11 měsíci +1

    The genny vijayos are for some odd reason, some of my favorites that you do. 👍

  • @rupe53
    @rupe53 Před 7 dny +1

    Would agree that the controller is NG here, but in my 25 years working for a LARGE Generac dealer (15 techs) I never saw that particular issue. Typically, they seem to either have a burned-out display (can't read it) or the clock drops several hours over the course of 6 months between services. (for that vintage) The newer units don't seem to have those issues. BTW, bugs in a TS are because the electrician didn't seal the cable openings. I have actually had to replace many 200 amp contactors due to bugs inside the guts.

    • @HVACRSurvival
      @HVACRSurvival  Před 6 dny

      Thank you! I learned the most when I took the Generac Comercial class. They were easier to work on in my opinion. Better instructors as well

  • @sheepdog3828
    @sheepdog3828 Před 3 měsíci +1

    Oh BTW, place a few ear tags in there to keep critters out or to a minimum!

  • @Enitii
    @Enitii Před 11 měsíci +7

    I didn't know there was a commercial at the beginning because I use CZcams premium

  • @johnwalker890
    @johnwalker890 Před 11 měsíci +4

    Good job Rick, They should, the manufacturer, should make some kind of shrink tube or insulation to cover the grounded conductor, so it doesn't come in contact with any other circuits, or the installer or customer, it just doesn't look safe, with raw wire sticking out, I know a person could tape it, but it would look a lot better with it insulated or safer.

    • @HVACRSurvival
      @HVACRSurvival  Před 11 měsíci +1

      I agree, that's kind of why I unhooked the ground before I pulled it out. The new generators have a side panel that comes off. All these old generators I keep showing are all problematic but they have made improvements since then.

    • @johnwalker890
      @johnwalker890 Před 11 měsíci +1

      You're right, I've seen those new panels, but haven't installed them yet.

    • @nspro931
      @nspro931 Před 5 měsíci

      @@HVACRSurvival That has been the mantra with Generac as long as I have been in the business, "They are not as bad as they used to be!" Heard it for decades now.

  • @Minitrucker231
    @Minitrucker231 Před 11 měsíci +1

    Just a random tractor hauling ass in the middle of a job 😂 Gotta love it!

    • @HVACRSurvival
      @HVACRSurvival  Před 11 měsíci

      That's my side of the county where I grew up 🤣👍👍

  • @frankspliff7037
    @frankspliff7037 Před 11 měsíci +3

    I like the veto bag

  • @FPHA697
    @FPHA697 Před 11 měsíci +1

    Good informative video.

  • @danpresson
    @danpresson Před 11 měsíci +1

    Awesome video always look forward to your video

  • @fshn76
    @fshn76 Před 11 měsíci +1

    Great video as always Rick! Glad I don’t work on generators.

  • @dougking7592
    @dougking7592 Před 11 měsíci +3

    Hay brother generator work is not as simple has you make seem, lately I have had a few gensets that have overcrank due to not getting fuel bad regulators and air pockets in gas lines for some odd reasons, and couple controllers nice video brother

    • @HVACRSurvival
      @HVACRSurvival  Před 11 měsíci +2

      No it's not that easy, it'd be nice if I did them everyday, most of this I'm going off memory. I hardly work on these things anymore. I had a lot of issues in the beginning of learning three because it wasn't the greatest training. I hate reading a book trying to figure things out.

  • @fernandogonzalez6617
    @fernandogonzalez6617 Před 7 měsíci +1

    Nice video info. How you did that took fuse out main breaker on ats still in on position and generator transfers power to home. How is that never seen that?

    • @HVACRSurvival
      @HVACRSurvival  Před 7 měsíci

      Because it’s likely not the safest thing to do.

  • @countryside8122
    @countryside8122 Před 11 měsíci +4

    It's not surprising, the way Generac treats it's employes, The people see problems and bring it to the attention of leads and they ignore the problem. I worked there for awhile.

    • @HVACRSurvival
      @HVACRSurvival  Před 11 měsíci

      Awesome, thanks for sharing! Feel free to vent😃👍👍

    • @deepsleep7822
      @deepsleep7822 Před 6 měsíci +1

      Always boils down to money.

  • @robertconville6269
    @robertconville6269 Před 7 měsíci +2

    Does not look like the owner ever does any up keep on the unit! I open mine at least once a month to clean and look around!

  • @kcMan7938
    @kcMan7938 Před 5 měsíci +1

    That tractor was crusin at WOT !!!

  • @jeffsignore7953
    @jeffsignore7953 Před 11 měsíci +3

    Hey Rick. What type of fuse holder is that? Looks like it grips perfectly on those fuses. The one I have is to loose. Thanks!

  • @craiggcrefrigeration8537
    @craiggcrefrigeration8537 Před 11 měsíci +2

    Great video Rick, I must ask why is there a need for a generator for a home where you are? Just interesting as we only use them for back up power in the UK. My guess is seasonal extra power for the A/C etc.

    • @HVACRSurvival
      @HVACRSurvival  Před 11 měsíci +4

      For when the power goes out. ? If you're in the country you don't have heat, water, etc

    • @joeyf504327
      @joeyf504327 Před 11 měsíci +5

      back-up generators, are used for back-up. No to run the a/c in the summer. Standard house service in the US is 200A 240V or 48kW. Most back-up generators are under 20kW.

    • @craiggcrefrigeration8537
      @craiggcrefrigeration8537 Před 11 měsíci +2

      Ah thanks guys, makes sense, just don’t see any on domestic properties over here. Usually just light some candles and suffer 😂

    • @comp20B
      @comp20B Před 11 měsíci

      ​@@craiggcrefrigeration8537For work from home and for refrigerators. We went 7 days one year after a snow storm.

    • @sandy1653
      @sandy1653 Před 8 měsíci

      @@craiggcrefrigeration8537 Candles and suffering are all well and good, but when it's 90f (32c) and 80% humidity, and there's no hope of power for 2+ weeks, you'll be glad you've a backup generator.

  • @sheepdog3828
    @sheepdog3828 Před 3 měsíci +1

    No matter what make, of a genset, TLC is a must.
    But common sense is not so common.

  • @harrydickson4575
    @harrydickson4575 Před 11 měsíci +1

    👍👍👍

  • @BOB12349307
    @BOB12349307 Před 27 dny +1

    highly abused best generators ever made!!

  • @gtpforever
    @gtpforever Před 11 měsíci +3

    The three LEDs on a generac generator are simple and they're listed like this as a caveman......
    Green= good
    Yellow= good-maintenance
    Red= bad

    • @gtpforever
      @gtpforever Před 11 měsíci +1

      There's also a dealer code to get into it further if you need it.

    • @gtpforever
      @gtpforever Před 11 měsíci +1

      Shut down was normal. The squeakiness is a read valve inside the valve covers or as generac calls them the head. It always makes a squeaky noise when they shut down.

    • @gtpforever
      @gtpforever Před 11 měsíci +2

      Also everyone be very careful with any of the micro-spades when plugging them in on the micro switches because the micro switches are brittle. Lol

    • @rupe53
      @rupe53 Před 7 dny

      @@gtpforever if the yellow light is on the display should say "due for service" so no code necessary.

    • @gtpforever
      @gtpforever Před 7 dny

      @@rupe53 never says due for service on generac residential generators. Open the lid and will ask things like... Checked air filter? Changed spark plugs? Checked oil level?

  • @KgiMedia601
    @KgiMedia601 Před 11 měsíci +1

    Dude im over wrenching these things, there so annoying to deal with at this point 😂

    • @HVACRSurvival
      @HVACRSurvival  Před 11 měsíci +2

      I feel exactly the same way, why do you think I'm so negative in the generator videos. I asked the office to get someone else trained and it still hasn't happened.

    • @CM-ou4zr
      @CM-ou4zr Před 11 měsíci +1

      @@HVACRSurvival how do you get certified to work on these? I remember you talking about a generac class. Curious because I do HVAC for a big college and we have a million of these things and hate subbing out the work. What steps would you recommend to actually get good at them? I have the manual for every different one on campus and will read front to back and can play with the ones that are on buildings not being used.

    • @KgiMedia601
      @KgiMedia601 Před 11 měsíci

      @@CM-ou4zryour employer will pay for it and set it up(atleast thats how it was for me) and then you take these pre reqs online which are like presentations then a quiz at the end, then theyll setup a school date at a certified dealer where youll go for 2 days get a manual for the generator ie aircooled, liquid cooled etc and youll fix problems the teacher sets up. Theyll also teach u how to use genserve and give you a tech id for warranty repair type stuff

  • @btomas225
    @btomas225 Před 6 měsíci +1

    6:47- Diode drop.....

  • @OverKillPlusOne
    @OverKillPlusOne Před 5 měsíci +1

    Bet that controller has a coin cell for the clock that’s failed.

    • @OverKillPlusOne
      @OverKillPlusOne Před 5 měsíci +1

      Whether or not that’s serviceable is a whole different question.

    • @rupe53
      @rupe53 Před 7 dny

      they do not have an internal battery. If you remove all power (ac and dc) the clock & calendar, go to a default reading. Also, all of the trouble codes and run monitors in storage are lost.

  • @AD17709
    @AD17709 Před 11 měsíci +1

    That thing needs a wipe down.

  • @joehead1294
    @joehead1294 Před 11 měsíci +1

    Mighty grimy battery for only a year. 🤨

    • @HVACRSurvival
      @HVACRSurvival  Před 11 měsíci

      The whole generator was grimy. I can't believe the lady wasn't out there with her sweeper and Windex keeping it clean 😃

  • @BOB12349307
    @BOB12349307 Před 27 dny +1

    let me guess you charge like $500.00 for the $50.00 module?

    • @HVACRSurvival
      @HVACRSurvival  Před 26 dny

      Our cost on that module I think is somewhere around 400 bucks so it probably did sell for 500. If you can get it for $50 I’ll take 10 of those and for the comment down below about being the best generator built🤣🤣 Well, just look at all the other videos I’ve done on these…. The 2006 through 2014 generators were total shit. Generac no longer lets you go through the assembly plant because you’ll see how poorly they’re thrown together. I’ve had motors go bad in less than five hours. I’ve had bad coils, bad modules, bad regulators. I’ve had them blew everything up in the house because the voltage regular went bad. Everyone entitled their opinion but not their own facts.

    • @user-kp2fc2dp8e
      @user-kp2fc2dp8e Před 8 dny

      @@HVACRSurvival I'm looking at 25Kw generators now with an ATS. The reviews on the "home owner" grade units are all over the place. They sure appear to be cheap crap. I almost went for a Generac. But after hurricane Beryl many people had generator failures. I think I'm going with a open Kubota driven 4 pole 1800 RPM machine sitting on a 100 gallon Diesel tank. It will be placed in a newly constructed water well/generator house.

    • @rupe53
      @rupe53 Před 7 dny

      @@user-kp2fc2dp8e as a 25 year generator tech, I can tell you that any small out-building / shed / etc will eventually be a service nightmare, not to mention issues with code compliance, especially it it's constructed of wood or is damp inside. Buy a gen set that comes with and is designed to be inside a cabinet that is UL approved as an assembly. Install it on a concrete pad, at least 5 feet from anything flammable, following mfgr's instructions and you will avoid issues with your homeowner's insurance as well. It will also be quieter, cheaper, and last longer than anything you can build. (if you bother to count your time)

  • @Eddy63
    @Eddy63 Před 11 měsíci +2

    I hate a generator you can't trust Thx

    • @HVACRSurvival
      @HVACRSurvival  Před 11 měsíci

      🤣👍👍

    • @BrianD-ds4dx
      @BrianD-ds4dx Před 9 měsíci +1

      Then don’t buy a Generac! Simple solution! Generac’s focus is on marketing, not engineering. Their market share is dependent entirely on marketing volume not reliability. I’m in the generator business and rank as follows for air cooled units:
      1) Cummins
      2) Briggs and Stratton
      3) Kohler
      4) A guy on a bike like the WWII movies pedaling to make power
      5) Literally anything other than a Generac
      The bottom of the list is a joke obviously but the top is not. We don’t do Champion in Texas due to their small size and our rather large AC inrush. Also for anyone watching this video out here please be aware that a lot of your generator run issues can be tied to a poor install. Just yesterday we went behind electrician originally only for the purpose of doing the low-voltage and the start up and commissioning of the Cummins unit the customer installed. Upon further inspection, the electrician had used the meter as a raceway and had also installed the ATS within three feet of the gas regulator, which is a big no no due to fire code.
      Good thorough video I especially like the discussion of the functional limitations of the air cooled unit here

    • @nspro931
      @nspro931 Před 5 měsíci

      @@BrianD-ds4dx Cummins are all Chinese air cooled now, had 3 fail this year out of a not very large population. Breaks and Scrappem build quality do not inspire confidence, their new stuff is all different than their old stuff which was really bad. Kohler is the only one with a heritage and actually a support system that helps when we call.

    • @BrianD-ds4dx
      @BrianD-ds4dx Před 5 měsíci

      @@nspro931 I’m going to 100 percent disagree with you on the Cummins air cooled being made in China. I only know this because I had to dig real deep within company contacts to find out where they come from.
      You are on the right continent but a little far north.
      What area you installing in, out of curiosity? Not completely opposed to Kohler but I dislike the controller on them, and, like the Generac I find them loud AF

    • @BrianD-ds4dx
      @BrianD-ds4dx Před 5 měsíci

      @@nspro931 oh and from a managed load perspective….Briggs load management design and the synchrony switch are so much better than Kohler and Generac. Cummins could be just as good but you have to hardwire that sh** in which makes it a way bigger pain installing than the Briggs load management devices