-6°F Out... Now They Both Don't Have Heat

Sdílet
Vložit
  • čas přidán 27. 12. 2022
  • Friday Dec 23rd 2022 Is the following day after the USA got nailed with a major cold snap. It was 35-45* F the day before and now its -6F outside resulting in the build at 59* and the house was in the lower 50* area. This was just two of the calls that day.
    - Purchase your tools at www.trutechtools.com/?AffId=42 and use the offer code SURVIVAL to save 8% on your total purchase (exclusions may apply) -
    - TOOLS I USE -
    FULL LIST ON THIS PAGE - kit.co/hvacrsurvival
    SHORT LIST IS BELOW
    RIDGID 31305 Model E-110 9.5" Offset Hex Jaw Pipe Wrench - amzn.to/3Bar08y
    Klein Tools Ratcheting Box Wrench 1/4 x 5/16 amzn.to/3GOpBrG
    KNIPEX Tools - 10" Pliers Wrench amzn.to/3U7RRJf
    KNIPEX Tools - 10" Cobra Water Pump Pliers amzn.to/3Wje8Wn
    Knipex Tools - Mini Pliers in Belt Pouch amzn.to/3WguyyH
    KNIPEX Tools - 4" Cobra XS Water Pump Pliers amzn.to/3UaQiKA
    Bahco -6" Wide Mouth Adjustable Wrench amzn.to/3sHIsMV
    Bahco - 8" Big-Mouth Adjustable Wrench with Rubber Handle - amzn.to/3SPhDB7
    Knipex - 9.5-Inch Ultra-High Leverage Lineman's Pliers amzn.to/3DTLJ2h
    Klein Tools Diagonal Cutting Pliers with Angled Head - amzn.to/3zuBVJb
    Klein Tools Stripper, Crimper Tool - amzn.to/3gQQ6Su
    Klein Tools Wire Cutter and Wire Stripper - amzn.to/3Fs627W
    Klein Tools Kurve Wire Cutters, Heavy Duty Wire Stripping Tool - amzn.to/3FseIuW
    Klein Tools Heavy Duty Automatic Wire Stripper - amzn.to/3SQdZab
    Klein Tools Crimping and Cutting Tool - amzn.to/3TPIgXU
    Klein Tools Screwdriver Adjustable 4 to 8-Inch amzn.to/3Nl6KWz
    IDEAL INDUSTRIES Digital Circuit Breaker Finder - amzn.to/3DoBFwm
    Fluke 376FC AC/DC Clamp Meter with iFlex - amzn.to/3UaNyx2
    Fluke 62 Max Industrial Infrared Thermometer - amzn.to/3SNdwWg
    Fluke 902 FC HVAC True-RMS Clamp Meter - amzn.to/3Ws7OfB
    Fluke 87V MAX - amzn.to/3U6Rlv9
    Fluke Networks Pro3000 Tone Generator - amzn.to/3WedklG
    Fluke - FLUKE-52 Dual Input Digital Thermometer amzn.to/3zwFdf1
    Ideal Safe-T-Grip Fuse Puller - amzn.to/3zsw2w4
    Klein Tools Canvas Zipper Bag - amzn.to/3WgnJxq
    Uni-Paint PX-20 Oil-Based Paint Marker - amzn.to/3sE3R9T
    5 Gallon Bucket Topper and Organizer - amzn.to/3sGi2Ll
    Stabila Magnetic Pocket Level PRO with Holster - amzn.to/3FtYLo0
    Clip & Carry Kydex Multitool Sheath for LEATHERMAN SURGE - amzn.to/3TPJfHA
    Kydex Multitool Sheath for LEATHERMAN WAVE & WAVE + PLUS - amzn.to/3sJlhlg
    Cooper Atkins Thermistor Thermometer - amzn.to/3DLeHkC
    GEARWRENCH Internal/External Ratcheting Puller 7 Ton 2 or 3 Jaw - amzn.to/3FxTU5l
    💥 Amazon Store: www.amazon.com/ref=as_li_ss_t...
    - CONTACT INFO -
    hvacrsurvival@gmail.com
    - FOLLOW ME -
    Instagram - / hvacrsurvival
    Facebook - / hvacrsurvival
    Warning Notice Disclaimer - Video content listed on the channel HVAC*R Survival is for entertainment purposes only and not meant to be a substitute for not contacting a competent HVAC/R PROFESSIONAL. Do not attempt anything said or seen on my videos, The tasks that are shown are dangerous and deadly without proper training.
    This page contains affiliate links, which means that if you click on the link and make a purchase, I’ll receive a small commission. HVAC/R Survival is a participant in the Trutechtools, Fenix-Store & Amazon Services LLC Associates Program.
    #hvacrsurvival #hvaclife #hvacservice #hvacr #refrigeration #troubleshooting
  • Zábava

Komentáře • 277

  • @MaximumEntropyLLC
    @MaximumEntropyLLC Před rokem +25

    "It's negative 6 today and I'm not wasting time.... " hahahahahaha... Stay warm my friend!

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +7

      I edited so much out of this video 😂... Your not hearing a 1/10 of what I said.

    • @ryans413
      @ryans413 Před rokem

      Normal day in Canada actually it gets colder then that’s believe it or not. Right now it’s really warm for January it’s 15 Fahrenheit about -10 Celsius

  • @chatrkat
    @chatrkat Před rokem +14

    That’s beyond brutal, I’ve worked up on my roofs over the last 30 years as a tech fixing other than mechanical equipment. You do just what is required to make it work. No deluxe repairs when it’s that cold.

  • @spencerdelossantos9373
    @spencerdelossantos9373 Před rokem +8

    anyone notice the yellow snow at 5:28 ..... haha

  • @pizzapale
    @pizzapale Před rokem +6

    2:57 gotta make sure to kick some fresh snow over that yellow snow to hide the evidence this time of year 😂😂

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +2

      Normally I do but I forgot to cut that out...lol

  • @stephenwolinski4651
    @stephenwolinski4651 Před rokem +3

    Mikey pipes said hvac is the road to riches , days like this give me a second thought on that 🥹

  • @markh.6687
    @markh.6687 Před rokem +2

    Nice work! Especially the Scotty "I can jury-rig the furnace, but I canna tell ye how lang it will last, Captain!" job in that basement.

  • @MikeB9771
    @MikeB9771 Před rokem +12

    For a while there I thought that old furnace was just toying with you. One thing I hate is having to brave the cold to get others warm. Good job Rick.
    Would love to see the unedited version of this video.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +8

      You would think differently about me after seeing it. I had to cut a lot of shit out.

    • @donaldpainter956
      @donaldpainter956 Před rokem +2

      @@HVACRSurvival I know your frustrations I had a couple of those outbreaks myself over the weekend

    • @jsmith7286
      @jsmith7286 Před rokem +1

      @@HVACRSurvival I personally love rheem furnaces but I have had my run around with the ol 90% Achievers. No doubt the pressure issues are trouble.

  • @carolinafrog4365
    @carolinafrog4365 Před rokem +3

    totally sucks to be out there in that kinda weather doing that kinda work, but Thank You for being The Man with The Plan and The Skills to git r dun! i can only imagine what a man of your skill will be able to earn in another 10yrs as the industry ages up with less ppl to fill the need!

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Thanks frog, there is a lot to learn and not enough people willing to learn it is a real issue👍👍

  • @Kangenpower7
    @Kangenpower7 Před rokem +3

    During the hour long drive to get parts, the home warmed up to 58F 15C, it will take a long time to reach a comfortable 68F or 20C.
    With certain Cities wanting us to install the very smallest furnace to keep the home warm, they seem to forget on very cold days it will take hours to reach a comfortable temperature when starting at 30F. My guess is that the home has very little insulation between the very cold basement and the living space? That does not help at all!
    If they have a electric stove, I would recommend running the oven, but not with a gas oven.

  • @chaseherigstad8576
    @chaseherigstad8576 Před 6 měsíci +2

    I appreciate that you don’t sugar coat anything. I can empathize with your thought process, and have learned quite a bit from you. Between you and Chris from HVACR, you guys saved my bacon in my first couple years. Hard to imagine you can get mentors from CZcams.

    • @HVACRSurvival
      @HVACRSurvival  Před 6 měsíci

      Thanks Chase, I needed a little boost when I got into refrigeration full time and NorCal and Jim Pettinato were my helpers.

  • @watermanone7567
    @watermanone7567 Před rokem +3

    Thanks for a good video. I changed a compressor for a computer room on Christmas Eve. many years ago in an alley way up on a mezzanine .It was about 10F. Never again. Thanks

  • @roberthayes6654
    @roberthayes6654 Před rokem +3

    Yeah been doing hvac for 25plus years . Have to do what you have to do in this cold. New subscriber stay warm brother..

  • @michaelcoonts6253
    @michaelcoonts6253 Před rokem +2

    I worked through that winter storm as well. Was at a kfc with no heat. One unit went off on roll out when birds nest that was in it caught fire. Lol😂

  • @Brisket9392
    @Brisket9392 Před rokem +5

    "Obviously you can't leave it like this unless you wanna die." Good stuff. LOL.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      I'd have the HVAC CZcams police on me if I didn't say it🙈🤣

  • @MileticPVP
    @MileticPVP Před rokem +5

    The good old quick piss on the roof @ 5:20 . I'm always having to piss at the worse time too lol

    • @m9ovich785
      @m9ovich785 Před rokem +2

      I usually look for a vent Pipe or a Roof Drain and Pee down that.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +4

      No one's going up there other than the 10,000 plus viewers that have watched it😂

  • @4D0m45
    @4D0m45 Před rokem +2

    3:25 yellow snow storm :D

  • @Boodieman72
    @Boodieman72 Před rokem +2

    Bearings on my house furnace sounded like that and within 2 days it locked up and ended up with a whole new furnace.

  • @leosthrivwithautism
    @leosthrivwithautism Před rokem +2

    I am beyond grateful for all who work in HVAC. And service contractors too. Long story short I want on vacation in the mountains during Christmas. The Well pump was frozen shut when the heater breaker tripped out on the pump. So No water for a week. And half way through, the Aux. Heat on the AC tripped out too. Very nice sleeping in a cabin that was 48 degrees at night. The heat pump just couldn't keep up. The people called where not happy but we understood and provided them with some food to show gratitude otherwise the entire Trip would of been ruined for us in a frosty cabin.

    • @leosthrivwithautism
      @leosthrivwithautism Před rokem +1

      The Pump company was scheduled out over a week in advance. The owner begged them to place this as emergency and even so they where still out more than 3 days due to the large number of emergencies and low number of crews available. HVAC company was more than 3 weeks booked out. And Emergency calls where the same. This cold causes a really bad situation for everyone in those fields.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      Thanks for sharing your story, I'm glad they were able to get it going.

  • @fredlogan3849
    @fredlogan3849 Před rokem +1

    tHANKS FOR THE WARNING LOL

  • @joehead1294
    @joehead1294 Před rokem +2

    Got cold in Texas, 16 degrees F. Lennox heat pump kept up, 79 degrees for my mum. She's 90 years old.

  • @coldking8383
    @coldking8383 Před rokem +2

    My hat goes off to you Rick! Was 33 degrees here in Florida -I didn’t even want to get out of bed. But work never stops ……..Stay warm

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +2

      😂😂33*👍👍. That's perfect weather, but we would go broke if it didn't get cold like it does.

    • @TheFrenchPug
      @TheFrenchPug Před rokem +1

      50 here in So Cal and I'm not getting out of bed. Lol

  • @stevencossaboon3237
    @stevencossaboon3237 Před rokem +5

    Great work Rick. I hope you and the family had a good Christmas. Stay warm brother.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      Thank you, hope yours was as well! It was good 👍. I'm very blessed.

  • @caidhg
    @caidhg Před rokem +2

    You know a telecom tone generator/wand would be a great way to figure out which unit goes to what thermostat

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      I showed how to use a toner in an earlier video where I did just that.

  • @philipmariaegeanga7984
    @philipmariaegeanga7984 Před rokem +2

    sometimes pressure switches shows good in tester but due to carbonization on contacts they dont really close the circuit when in operation same as amplifier relays they dont have an output yet when you test them they are ok

  • @Willy12927
    @Willy12927 Před rokem +1

    I know it is an efficiency thing, but they make everything so complicated. You would think that someone could manufacture a simple, high efficiency furnace. During my 75 years on this earth I can't remember having to have a service call on a furnace. All that was required was to change the air filter and an occasional fan belt. Also, the blower fan and motor had oil cups, which if oiled periodically, would very rarely fail. Hey, times change, and I guess we have to be thankful that there are people like you that understand these new systems and are willing to brave the elements in order to keep us warm in the winter and cool in the summer.

  • @rcstl8815
    @rcstl8815 Před rokem +2

    For those playing along at home... make sure the port at the inducer casing is clear. It is the first place for FOD (like drywall dust), to try to get out and if blocked, even partially, It will not have the draw to close the pressure switch(es). If it is clogged, it will make the switches look bad. I carry small bits, orifice sized, to clear the port.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      That's why I checked the actual draft being created by the IDM with the monometer, it was about 50% higher than needed to close the switch.

    • @rcstl8815
      @rcstl8815 Před rokem +1

      @@HVACRSurvival When the port is restricted, it will not allow enough suction to pass quick enough to close the switch. The draft will look great but it can't draw through the port orifice. I had a spider web stop one, the kind of spider that clogs grill orifices.

  • @henrybucki7813
    @henrybucki7813 Před rokem +2

    cut the thermostat off and see if the blower stops /make sure you number the rtu before leaving job

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      I mentioned that but cut that out of the video

  • @jhill.7216
    @jhill.7216 Před rokem +2

    Oh my ! Man oh man I’m about to Graduate hvac school upcoming may 2023 ! I’m from the south but this is absolutely something watching this! Thanks for what you do 👏🏽👏🏽

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      Congrats! I appreciate the feedback!

    • @markh.6687
      @markh.6687 Před rokem +1

      Don't worry; with climate change soon you'll be working in snow and cold as well as heat and humidity down South.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      @@markh.6687 yep we're all gonna die 7 years ago thanks to stupid humans living on earth👍👍.

  • @ianicus123
    @ianicus123 Před rokem +1

    Man working like that with the blower running, risky wow.

  • @johnwalker890
    @johnwalker890 Před rokem +1

    Good job Rick, Merry Christmas and Happy New Year.

  • @thesilentonevictor
    @thesilentonevictor Před rokem +1

    Good touch on the old lady Rick

  • @retsbew8954
    @retsbew8954 Před rokem +2

    Thanks for the videos. BTW, I ordered that exact same manometer from Tru-tech using your code. Keep up the great work!

  • @theunit5939
    @theunit5939 Před rokem +1

    Wow crazy how the flue was not glued in, playing with fire on that one,

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Not really, I rather see it siliconed then glued for easier service.

  • @harrydickson4575
    @harrydickson4575 Před rokem +4

    Excellent work 👍👍👍

  • @donaldpainter956
    @donaldpainter956 Před rokem +2

    14 of the calls were high efficiency gas furnace the drain lines were frozen easy fix but driving around to all of them took alot of time I had bad inducer fans bad boards bad indoor blower motor bad capicater

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC Před rokem +1

    I don't miss the cold and snow....i moved to TX from Buffalo....so i definitely know about the cold and snow. We had 1 day, that was cold (13°) the rest have been 60°+. Today was 75° and glorious.....sorry wasn't trying to rub it in.....well maybe a little bit. Lol. Great video as always Rick.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      lol I was inside all day today and it was warm at 35*

  • @shifter8207
    @shifter8207 Před rokem +2

    I had to take many a piss on the roof this week too😂😂😂

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      There's something about the cold that brings it out🤣

    • @joehead1294
      @joehead1294 Před rokem +2

      @@HVACRSurvival But you didn't autograph it.🤣🤣🤣👍

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      @@joehead1294 This was my first edit with my new computer and I had several issues, also this was my first 4k video, I stayed up until 2am correcting things that got screwed up.

    • @joehead1294
      @joehead1294 Před rokem +1

      @@HVACRSurvival Didn't you ever write your name in the snow as a kid? 😆

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      @Joehead1294 I probably peed outside more times than I have inside, I'm pretty sure I did 😁👍👍

  • @mikropower01
    @mikropower01 Před rokem +1

    That he used some oil for the motor to fix the noise of the bearings temporary, this is nice.
    But he should give the owner a list with some tips how they can improve their system.

    • @markh.6687
      @markh.6687 Před rokem +1

      Item 1: Remove old furnace and bury in abandoned mine shaft. :)

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +2

      @Mike I know I talk fast but if you listen to what I said you'll hear me say I told the customer about it and he said it's been like that forever and he did not want it repaired beyond what it took to get it running. I don't go into all the details in the video so give me the benefit of the doubt, he also told me that he wanted to sell the house next year, not that that makes it right but there's nothing I can do if these people don't want to spend the money. How about just being glad I made the video.

  • @bbasham46
    @bbasham46 Před rokem +1

    I used to live in Columbus Ohio and I have one word of advise for you, Florida! : )

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Yeah Columbus is only 90 minutes away, the wife won't let me leave this god forsaken state. At least for now until more things change of course I probably won't be in the field by then 🤦🏻😂

  • @marknaravas318
    @marknaravas318 Před rokem +2

    You have a high tolerance for screechy belts and inducer motors!😊

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      A little. Probably losing some more hearing 🫣. I would have rather aligned the belt but not when it's that cold 😁

  • @Eddy63
    @Eddy63 Před rokem +2

    I admire all you guy's that brave this kind of weather ... My hat's off to you ... I almost feel guilty enjoying a cold 🍺 and a shot of Tequila ... I said '' Almost '' 🤣😅😂 Thx Rickster

  • @randomrefrigeration4564
    @randomrefrigeration4564 Před rokem +2

    Enjoy your videos Rick
    Just watched one on the Generac with lose throttle screw and bad compression
    Man your super thorough
    Appreciate you man

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      Thanks for the feedback! I have a lot of different types of videos if you liked those.

  • @christopherkidwell9817
    @christopherkidwell9817 Před rokem +3

    Bad thing is that many people who call in for their next fuel delivery like myself are at a higher chance of running out of fuel due to the cold snaps making us use much more fuel.

  • @gregbowman3598
    @gregbowman3598 Před rokem +1

    Good one Rick👍

  • @hugh007
    @hugh007 Před rokem +2

    Great video. Thanks. Your alligator clip lead looks just like the ones I used years ago from Western Electric. Looks like the same label too.
    Happy New Year.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      I built them from silicon test leads and added my name on a label.

    • @markh.6687
      @markh.6687 Před rokem +2

      "Keeping your phone system the best in the world" -- Bell System ad slogan, 1970's. I just took a photo of an old Bell System ground-level buried cable tag on a utility pole; most of it was still readable. Quality?? THAT was quality!

  • @natepeterson7145
    @natepeterson7145 Před rokem +2

    Heat wave coming today, going to be 59. My in laws are kinda close to you and usually get our weather a day later. Beats that deep freeze from last week.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      It's 46 right now @ 8:13am est 12/29/22👍👍

  • @EverythingHVACR
    @EverythingHVACR Před rokem +1

    Nice job Rick! We got hit hard as well

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      Any video? It's not true without it🤣🤣🍺🍺🍺

  • @jasontexter1721
    @jasontexter1721 Před rokem +2

    So I know on the nests, idk about the ecobee, but if you jumped out red to white or yellow or green it would cause the thermostat to error out, and it would open the circuit. They use transistors/solid state switches instead of mechanical relays and they read the resistance/voltage drop on the circuit and when you jump it out it freaks them out and they'll lock out when you change resistance it was used to seeing

    • @jasontexter1721
      @jasontexter1721 Před rokem +1

      The nests are notorious for the cooling circuit failing if you have a loose connection to the contactor or any chattering that can cause high amp draw on the y wire or even if it's trying to run a large contactor or multiple contactors or had any thing close to a short to ground it would fry the transistor/solid state relay. So when you read voltage at the contactor control side it when it's connected you'd get 50-500 MV but if you disconnect and read sometimes it would be 9-24V but the current carrying capacity would be severely reduced when it fails. I think they even list the maximum amps each control leg coming out of the nest at like 200-500 MA and it's a hard rating... I've even had a sticking reversing valve fry one once that was a kick in the butt, after changing the valve and getting ready to run in cooling nothing happens 🤣🤣

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      You would think it wouldn't be like that being these technically are not a power stealing thermostat because they have a common wire but this was a huge issue when they didn't have Commons required. The old power stealing stats were able to be powered off just r&w, total pieces of crap usually, I wouldn't be surprised if they used a capacitor to keep the display up and going while that circuit was closed.

  • @chillybinbob
    @chillybinbob Před rokem +2

    I moved to South Florida in 1997. I have forgotten how to do heating calls!

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +2

      🤣😁 ya ya ya

    • @chillybinbob
      @chillybinbob Před rokem

      @@HVACRSurvival Thats okay, I spent the day working on a 5 ton split where a brain surgeon who installed it thought that 3 X 8" flex would be the appropriate supply duct run. The air handler is rated at .5"WC. We need more Ricks down here! It has 3 X 12" now, tomorrow I will recover some charge from it. It also has 100 ft line set, no liquid solenoid valve, no suction accumulator, no crankcase heater. Cap tube A coil... that proves how tough a scroll can be!

  • @m.koehler7716
    @m.koehler7716 Před 11 měsíci +1

    For some reason it was acceptable to reduce flues at the wall.

  • @ToyManFlyer1100
    @ToyManFlyer1100 Před rokem +3

    Now, if only Auto mechanics could actually know what they doing and actually fix stuff like you do...

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +2

      If it doesn't have a computer many of them are lost.

    • @ToyManFlyer1100
      @ToyManFlyer1100 Před rokem +2

      @@HVACRSurvival ....True dat...True dat....Auto mechanics want $100/hr to fix my car, but, in the end...It's still broken....Clueless as to what the problem is....

  • @davidtillwach5542
    @davidtillwach5542 Před rokem +1

    The wind-chill way colder than -6 outside.Rtu you freeze your butt off in the winter fixing them

  • @elBusDriverKC
    @elBusDriverKC Před rokem +3

    Any time I take on a commercial account, or even a residential account, I start labeling everything. I service 200 units over 5 locations (large commercial buildings) and have spent a lot of time labeling the units so I don't have to guess. I craft spreadsheets and unit maps with all unit information. Don't get me wrong it definitely takes a long time, but definitely worth it.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      I fully agree, I think some people believe keeping that information hidden makes it easier to confuse others later but even if I don't have it, I'll get it eventually, people are just jerks

    • @elBusDriverKC
      @elBusDriverKC Před rokem +1

      @@HVACRSurvival Sometimes I'm too busy, or maybe sick, and we have others go out there and work on units. I always e-mail them my unit sheets and get very cheerful responses. Keep up the good work out there!

    • @markh.6687
      @markh.6687 Před rokem

      Looks like his paint marker froze trying to label the unit; Sharpies work better because they're alcohol-based. (Come to think of it, so are some HAVCR techs). :)

  • @roberttraylor1392
    @roberttraylor1392 Před rokem +1

    awesome video i enjoy your video new subscriber happy holidays

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      Thanks for saying hi Robert! Thanks for the sub!

  • @toetagsbodybags
    @toetagsbodybags Před rokem +1

    i was on the roof on that day -28 windchill i was like running nope ok lets guess and come back later... dropped portable heaters. heating board was the issue the following week had it on the truck....... I fell ya

  • @picklerix6162
    @picklerix6162 Před rokem +3

    It’s hard to be chipper at -6 degrees. Most people wouldn’t want to get out of bed.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      What I didn't say was they cancelled work that day but we had to run the emergency calls, Its just life for a service guy but it still sucks,

  • @sterlingarcher46
    @sterlingarcher46 Před rokem +7

    Hats off to you guys , man .
    The week before last it got to around 25-30 F and the only thing people could talk about was how " cold " it was 😄
    On a more serious note though, extreme cold is still not an excuse to be using them bloody channel locks to undo flat sided nuts Sir !!
    🤣🤣 please don't kill me ...

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +2

      You bloody Yanker! 🤣🤣🤣🤣

    • @throttlebottle5906
      @throttlebottle5906 Před rokem

      yeah, rounded off nuts and bolts are bad 🥳

    • @jarikoltuniak1181
      @jarikoltuniak1181 Před rokem +2

      Channel locks??! First off he's using the correct tool. A Knipex flat jaw pair of pliers that I also have in every size, you can buy four pairs of "channel locks" for the price of those Knipex. Secondly they are called slip joint pliers, Channellock brand pliers have blue handles. Channellock is a brand.

  • @donaldpainter956
    @donaldpainter956 Před rokem +1

    I did learn Rheem furnace doesn't have the safety on it. That shuts the burners off if it can't drain like a Trane and Goodman and I think carrier Rheem will back up and drain out of the furnace whoever installed this furnace put a small pan under AC coil but not under furnace so his ceiling had water pouring from it

  • @berylwhite2983
    @berylwhite2983 Před rokem +1

    God bless you my friend no one really appreciates you like they should

  • @jeffgrant6914
    @jeffgrant6914 Před rokem +1

    Good video 👍 buddy

  • @bassman34516
    @bassman34516 Před rokem +1

    Yeah that day it was not fun whatsoever, it never is when it’s that cold. I spent 3/4 of it un gelling diesel reefers, trucks, jumpstarting and thawing ice in air brakes not a treat. Glad you made it through the deep freeze as well.

  • @donaldpainter956
    @donaldpainter956 Před rokem +1

    That's what I tell the customer that motor is gone I'll have the office order one

  • @stephenbullock1443
    @stephenbullock1443 Před rokem +1

    Good fix on the residential furnace.I never liked 90% efficiency furnace the heat exchanger fail to soon and when the warranty ends they so pricey

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Most have a limited lifetime on the HX, at a minimum 20 years usually.

  • @jackdaniels615
    @jackdaniels615 Před rokem +2

    If they keep the fan in auto just use the "G" wire as your common wire.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      That is an option if the customer is willing. 👍👍

    • @rambos420
      @rambos420 Před rokem +1

      This does work

  • @fredlogan3849
    @fredlogan3849 Před rokem +1

    that add a wire, are never friendly when they work ok but when they do not good luck! in some cases that is all you can do, guys use 8 wire or more it helps the next tech out of a jam in the future the cost is minimal it could be you. thanks. this one was a pistil multiple issues good work

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      I agree, I prefer one or two extra conductors for future repairs or accessories

  • @joshwf41
    @joshwf41 Před rokem +1

    I'm in Manitoba, Canada and -6F is nothing to me. I was out on a roof trying to fix a York this winter in -30C with a windchill of -40C(-40F)

  • @josht593
    @josht593 Před rokem +1

    3:43 I bet that was cold to do ;)

  • @snaplash
    @snaplash Před rokem +1

    My heat failed on the 24th. When I checked out the basement installation, I found the condensate pump constantly running (with humidifier bypass water), I just thought the float switch was stuck and unplugged it. (Should have looked closer at this.)
    Turns out that the pump has a safety switch that shuts down the whole furnace when it overfills. I didn't know this. My old pump would just overflow onto the unfinished basement floor, which I prefer, since it doesn't kill the heat or A/C.
    The actual problem was that the outlet hose had frozen. I fixed this with a new hose and an inside air break to make sure the outside part of the hose always empties fully when the pump shuts off.
    Service guy sorted out the pump problem, and ended up breaking off the hose barb while trying to just pull off the old hardened vinyl hose. He should have known it would require some heat to soften it first.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      He sounds like a real champ😉. I only hook up the safety if it's on a finished ceiling or floor. Otherwise I'll only kill the air conditioning, never the heat for that reason you found out. More things get broken when the heat doesn't run than will a little water on the floor.

    • @snaplash
      @snaplash Před rokem +1

      @@HVACRSurvival Yea, the safety was connected by the original installers about 8 years ago. They also failed to set the heat pump's furnace lockout, so it was burning gas nearly every time heat was called for. This was for years until I finally found out about lockouts and set it myself to 35f, no problems. (Bryant Evolution control) If I ever replace the system again, I think I'll find someone else.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      I don't like locking the gas out much lower than 45. I prefer setting the thermostat to run a minimum of 20-25 min before switching to aux heat.

  • @goldie1088
    @goldie1088 Před rokem +1

    I'm having flashbacks to my Friday while watching this.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      How would you like to live inside the video...lol

    • @m9ovich785
      @m9ovich785 Před rokem +2

      Digging Satellite Antenna's out of 3 Feet of Snow drifts too.

    • @goldie1088
      @goldie1088 Před rokem +1

      @@HVACRSurvival unfortunately I lived it too! I'm still a pretty new service tech, only been at it for about a year. I appreciate guys like you putting up content and sharing knowledge and experience! It really helps us new guys out. Keep up the great work and thanks for all that you do!

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      @Steven cool to hear👍👍. I wish I had this tool called CZcams back in 95. I had only a few people that were willing to help me learn, a lot of them just faked it till they made it 😂🤦🏻

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      @m9 You work for dish?

  • @liam3284
    @liam3284 Před rokem +1

    surprised enthalpy wheels are not used

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      Normally heat recovery units are dedicated systems ducted into the system. Some places have them and others don't.

  • @hvacrnortheastern2110
    @hvacrnortheastern2110 Před rokem +1

    Great job yep nobody label any equipment l remember those days in winter not any more l operate a utility plant inside work.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Someday I'll likely have to change over. I got a few years to go yet, God willing.

  • @donaldpainter956
    @donaldpainter956 Před rokem +1

    I had a few calls last Friday but Saturday it started at 2 am and I worked till 11 pm Saturday night no heat calls wouldn't stop coming in

    • @guytech7310
      @guytech7310 Před rokem +1

      The nerve of old man winter enabling a freeze right before christmas :)
      I am not in the trades, but I when to Lowes on Monday that the plumbing section was packed with people dealing with busted pipes. Lots of people still buying CPVC pipes. I am sure they be back when the next freeze hits again.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Luckly I just ran that Friday, my on turn on call was a week or two earlier

  • @donaldpainter956
    @donaldpainter956 Před rokem +1

    I hate finding multiple units and none are marked I mean put a number on it when you install it I always label them when I either maintenance them or work on one I'll label that one then a simple number on the tstat a number on the unit

  • @ThatFlyinRyan
    @ThatFlyinRyan Před rokem +1

    oh hell no im a florida boy i would be charging arm and legs and a Tooth lol

  • @christiansommer914
    @christiansommer914 Před rokem +2

    Time code 2:58😉

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      When you Got to go you got to Go😂

    • @christiansommer914
      @christiansommer914 Před rokem +1

      @@HVACRSurvival true story.. I see it as my duty to mark my territory on the roofs😂😂

  • @walkingfreak
    @walkingfreak Před rokem +1

    Glad i'm not the only one whos grumpier than shit in cold nasty weather.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Nope I had to cut so much shit out of that video.

  • @throttlebottle5906
    @throttlebottle5906 Před rokem +1

    who was chipper in that nasty howling wind and sub zero schmutz? I stayed in the house except for Christmas day, the poor old furnace here was fighting a losing battle, at one point it hit 65F inside running non stop. too many walls open and insulation out during construction work. 😬🥶

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      People can be aholes and they judge me for everything I say and I know I'm pissed off and negative while I'm doing this kind of bull

  • @christian4567ish
    @christian4567ish Před rokem +1

    I saw yellow snow 😂

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Yep, a couple people lost there minds over it.

  • @billmiller5075
    @billmiller5075 Před rokem +1

    Great job, miserable temperatures

  • @donaldpainter956
    @donaldpainter956 Před rokem +1

    I agree I've found rollout switch bypassed hi limit bypassed alot of stuff the neighbor got my unit running is what they say then I tell them how dangerous they left the unit then they want to get mad

    • @natepeterson7145
      @natepeterson7145 Před rokem +1

      People don't realize how a dead homeowner affects a business but what do we know. I bypassed an electric furnace temp cutout and learned my lesson when the customer didn't answer the phone when the part came in. Never again, don't care how cold it is. That bothered me for a while until I had to tell myself I was just trying to help someone out in - wind-chill.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      @Nate are you trying to do a confession here on the internet? Did you already do the time?

  • @SoutheastHVAC
    @SoutheastHVAC Před rokem +1

    I don’t see how y’all handle that weather. It got down to 16° in Florida last week and I didn’t think I was gonna make it

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Not many options but put on extra clothes and work fast.

  • @vampirel1983
    @vampirel1983 Před rokem +2

    Great video Rick. I just replaced a pressure switch on one of my houses because it throws a code saying switch is bad and i can visually see the error. I still couldnt quite follow how you determine the one on the left is faulty. is it because that one is on the pressure switch circuit? so the one on the bottom will never be a problem?

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      Because only one of the pressure switches were on the pressure sensor circuit, the other one just broke power to the gas valve.

    • @JP-sd2cw
      @JP-sd2cw Před rokem +1

      @@HVACRSurvival hey sorry to bug you I was trying to understand this as well

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      The best way to check a pressure switch is to put a tee in line with the pressure switch and draft motor, then measure it with a manometer. If you're lucky the pressure switch will have a rating on the side of it, you normally want to be one and a half times more than what it is rated at but that's just something I've noticed. You definitely don't want to be right at the rating.

  • @Bob.W.
    @Bob.W. Před rokem +1

    Why wouldn't the maintenance men have diagrams of which units feed which ducts? Seems elementary.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Each place I work at has maintenance people with a wide range of skills, some might know where everything is and others are just janitors.

  • @chrisduck685
    @chrisduck685 Před rokem +1

    Did you find the source of the yellow snow on the roof?

  • @throttlebottle5906
    @throttlebottle5906 Před rokem +1

    ecobee and other inline trash delete and regular t-stat on the wall, solved. the power going out while trying to diagnose it, would have made me blow a gasket 100%.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem +1

      Yeah he wanted me to pick up another one while I was getting parts, I was like aaaaa...no,

  • @danielprose5878
    @danielprose5878 Před rokem +2

    Which mini splits would you recommend as a pro service mecanic in terms of reliablility and quality ? Are the daikin models a good choice ? Servus from Germany

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Mitsubishi is what we sell, I don't like anything I have seen from Daikin

    • @danielprose5878
      @danielprose5878 Před rokem +1

      @@HVACRSurvival Thanks. What uyou dont like on Daikin ? I thought Daikin and Mitsu are near the same quality and reliablility?

    • @natepeterson7145
      @natepeterson7145 Před rokem +1

      @@danielprose5878 Most techs don't like Goodman which Daikin is a part of. They can be ok if this install is done properly.

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Technical support is the big thing with any of those mini splits, I don't like working on them because I don't know them very well, I do too many different things to be specialized in it. Each guy at our shop has a niche that they're really good at and that's not one of mine. Mine is the ice cream related machines and generators but even generators I'm not that great at anymore because I don't work on them very often.

  • @SoCaL884
    @SoCaL884 Před rokem +1

    Wow, I was cold for you in California. COVID happened

  • @rockystelone21
    @rockystelone21 Před rokem +1

    The extreme cold or heat will break a weak HVAC system.

  • @itwasthepudding
    @itwasthepudding Před rokem +1

    Lol i just walk outside in shorts and bare feet. It works

  • @klbonnell
    @klbonnell Před rokem +2

    Those ecobee with the fast stat is trash.

  • @tonychristianson9186
    @tonychristianson9186 Před rokem +1

    Was this in Minnesota?

  • @naturekid1335
    @naturekid1335 Před rokem +1

    Zoom spout oiler

  • @BobKemp
    @BobKemp Před rokem +1

    great video, where are you located with a -6 degree temp outside?

  • @roberts.3712
    @roberts.3712 Před rokem +1

    The heating systems are being taxed to the max during the big freeze....I don't envy your job...lol...

  • @danielprose5878
    @danielprose5878 Před rokem +2

    WTF is this unit? it burns what ? Gas to warm the heat exchanger thats warms the air ventilated into the hotel ? Never seen some of that units here in Germany ! America is the badest Mofo in co2 emissons wow ! These units must be so ineffective in using energy ! Lossing so much on exhaust heat , blow by heat and so on . Crazy these engineers 🤣
    Your videos are nice ! And u are really a specialist service mecanic. Firms here in Germany for air conditioning, and heating would pray for specialits like you ! Really ! We have so bad problems finding good staff on these jobs. Its really bad.

    • @guytech7310
      @guytech7310 Před rokem +1

      LOL! Germany burns coal to make electricity or imports electricity from eastern Europe coal fired plants. That's like burning a home down to keep warm! Without Russia energy Germany & most of the EU economy will be going kaputt soon!

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      BINGO Brother!

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      Wow, thanks for all the compliments after telling me how bad we are to the earth...You have to take a step back and think to yourself, are we really having all these problems from fossil fuels... & Don't forget how the government has lied about so many things. They want to control everything and I believe the energy is just another way to control us, and don't forget how your country has allowed themselves to be held over a barrel for energy,

    • @danielprose5878
      @danielprose5878 Před rokem +1

      @@guytech7310 Man thats all right! I only meant that on these climate control units in the video. And yes after 2022 Germany does a lot Co2 too. Everything right .

    • @danielprose5878
      @danielprose5878 Před rokem +1

      ​@@HVACRSurvival Climate change and all these problmens which come with it we have from burning fossil fuels thats clear. But yes u are right, the Government is a mess. The German Government since years ...absolute aweful horroble too.

  • @dissociativecat7495
    @dissociativecat7495 Před rokem +1

    wind chill was -30 in ohio

  • @stephwaylonwells3218
    @stephwaylonwells3218 Před rokem +1

    👍

  • @theashgamer400
    @theashgamer400 Před 5 měsíci +1

    what state

  • @randysterling4700
    @randysterling4700 Před rokem +1

    Anyone else notice the Easter egg @3:42

    • @HVACRSurvival
      @HVACRSurvival  Před rokem

      You didn't see the hot dog flying around? 😂

  • @illestk24civic
    @illestk24civic Před rokem +1

    Is hard to stop a trane, -6 degrees let me take care of that for ya