    This video is about programming a Sequence Output Instruction in RSLogix 500. It shows both the setup and operation.
    ‪@KletteTech‬

Komentáře • 36

  • @mtbtrailbuilding6813
    @mtbtrailbuilding6813 Před 4 lety +2

    Great video. It was able to fill the gaps in my self taught understanding and give me a finished product. Thank you

  • @Olavotemrazaodenovo
    @Olavotemrazaodenovo Před 4 lety +1

    Excellent. Congratulations from Brazil.

  • @navdeepsatia8572
    @navdeepsatia8572 Před 5 lety

    Very nice Explanation. I would not have guessed that I will understand this instruction that easy.
    Thanks.

    • @KletteTech
      @KletteTech  Před 5 lety

      I am happy to hear that! Thanks for the feedback

  • @leehomeschooling4644
    @leehomeschooling4644 Před 3 lety +1

    Very good teach , help a lot to understand the program for troubleshooting

  • @kevin00861
    @kevin00861 Před rokem

    Thanks a million times Sir !

  • @johnreyalforque5577
    @johnreyalforque5577 Před 8 měsíci

    Very useful video! what plc tool are you using? Where can we download that software?

  • @liridonosmani5834
    @liridonosmani5834 Před 3 lety +1

    👍👍👍

  • @BayMacDre415
    @BayMacDre415 Před 5 lety +2

    Well done thanks for making this. Only question I have is how to get back to step 0 if you wanted to reset all of the outputs... (I guess you could have an extra step at the end which loaded zeroes for each bit) and also I was wondering if the control input needs to be anything in particular, or just something unique for that particular instruction. Thanks!

    • @KletteTech
      @KletteTech  Před 5 lety +1

      Great questions. There is no way to get back to step 0. If you want all of the outputs to go to zero your need to program that or program in a clear that activates at the right time.
      The control input can be any input that make the rung logically true when you need the program to sequence.
      Hope this helps!

    • @BayMacDre415
      @BayMacDre415 Před 5 lety

      Sorry, I meant the Control parameter within the instruction block (R6:0 used in this example)

    • @BayMacDre415
      @BayMacDre415 Před 5 lety +1

      Not the toggle bit, or enable bit

    • @moisesmolina95
      @moisesmolina95 Před 5 lety

      @@BayMacDre415 you would use the control instruction R6:0/DN to activate a ( "move" instrucion) and put a zero so that it moves it to control instruction R6:0/POS that way it start from zero position.

    • @kevin00861
      @kevin00861 Před rokem

      Simply use RES instruction and address it with R6 control parameter,
      e,g you used R6:0 in the SQL instruction then use RES addressed with R6:0 and toggle it with input bit

  • @joellumbala5684
    @joellumbala5684 Před 5 lety

    how did you get the " light board " i can not seem to find a software for that i already have rslogix micro

    • @KletteTech
      @KletteTech  Před 5 lety +1

      That is actually real I/O in my shop. I use picture and picture to to show it on the screen. Thanks for watching.

  • @amolchandanshive323
    @amolchandanshive323 Před 2 lety

    Thanks for the video... 😇 i have a question to ask... Can we use sequencer for counting function.. Like i have to perform counting operation but not using counter.. So should I able to use sequencer for that?

    • @KletteTech
      @KletteTech  Před 2 lety +1

      You might be able to but it would a lot of work to set it up. A counter would be easier

  • @navdeepsatia8572
    @navdeepsatia8572 Před 4 lety

    Hello Klette Tech
    I am making a program on RS Logix Micro to control a traffic light. I got kinda stuck when I tried to control the crosswalk. For example, If I want to turn on Northbound Light with Northbound crosswalk I put a simple push Button which would turn on crosswalk same as Northbound light. Now the problem is if Northbound Light is already on and then somebody comes and presses push Button for crosswalk, Crosswalk then would turn on immediately instead it should turn on next time northbound light come on. I tried so many different ways to make it work but I could not. Could you please give me any suggestions in this regard.

    • @KletteTech
      @KletteTech  Před 4 lety +1

      That is a big questions. Have you tried to use a FLL instruction to move it into the storage location. Or Latch the sequences in subroutines and have the crosswalk instructions activate which subroutine is needed. Does this help.

    • @navdeepsatia8572
      @navdeepsatia8572 Před 4 lety

      @@KletteTech Hello KletteTech Thanks for replying.
      Eventually, I was able to accomplish the desired result by calling internal bits and manipulate them into the program.
      Since I am not familiar with the instructions that you have mentioned above. But I will love to learn them and then approach the same problem with that instruction.

    • @KletteTech
      @KletteTech  Před 4 lety +1

      @@navdeepsatia8572 Awesome job. If I get a chance I will try and make a video on it.

    • @navdeepsatia8572
      @navdeepsatia8572 Před 4 lety

      @@KletteTech ok Thank You very much!

  • @jeromenote9739
    @jeromenote9739 Před 5 lety

    I need some information on RS Logix programming for AB Micrologix 1200.
    If suppose, we have a sensor in field connected to the Digital Input of the controller. This sensor is connected to a conveyor, this gets signal ON and OFF contentiously every second or less than a second. I need to activate an output relay port only if the input is constantly ON for more than 5 seconds. Please advise how this can be done.

    • @KletteTech
      @KletteTech  Před 5 lety

      Great Questions. Create a TON with the sensor being the input. no memory. If the sensor is on for preset of the timer lets say 5 seconds the done bit goes true. Have the done bit activate the relay. Does make sense?

    • @jeromenote9739
      @jeromenote9739 Před 5 lety

      ​@@KletteTech Thank you for your reply. "No Memory" this means the timer will get reset to "0" every time the input changes its state from ON to OFF ?
      Please explain how to set this timer property "no memory" in RSLogix 500 timer.

    • @KletteTech
      @KletteTech  Před 5 lety

      @@jeromenote9739 Yes. if you have memory on the timer's input anytime the input goes true the timer will finish timing and the done bit will go true. If you want the output to activate when the input is only on for 5 seconds (lets say the conveyor stopped and it was not suppose to) then no memory in parallel with the input. does that make sense? Did i read you question correctly?

    • @KletteTech
      @KletteTech  Před 5 lety

      This video might help. czcams.com/video/A4dewWWMnVA/video.html

    • @jeromenote9739
      @jeromenote9739 Před 5 lety

      @@KletteTech Thank you, that was an excellent explanation about timers in RSLogix 500.