HVAC PRESSURISATION UNIT EXPLAINED

Sdílet
Vložit
  • čas přidán 6. 06. 2019
  • PRESSURIZATION UNITS CAME IN DIFFERENT SHAPES AND DESIGNS BUT THEY ARE ALL IN THE MARKET JUST TOO.......

Komentáře • 46

  • @njwareing6408
    @njwareing6408 Před 2 lety +1

    Great video thanks

  • @kirannettath
    @kirannettath Před 3 lety +2

    Good explanation.. I watched it in 2x play speed.

  • @thebestthereishe
    @thebestthereishe Před 2 lety +2

    Thanks for the clear explanation, Mihai.
    Aris

  • @mohammedkirmanisyed7960
    @mohammedkirmanisyed7960 Před 4 lety +1

    Method of explaining awesome

  • @itaukeiveteran2805
    @itaukeiveteran2805 Před 3 lety +2

    Very clear. Cheers Bro👏👏👏

    • @TechnicalChallenger
      @TechnicalChallenger  Před 3 lety

      Thank You
      I am learning my self
      I am not professional but I think all technicians need information

  • @polocotto43
    @polocotto43 Před 2 lety +1

    amazing video

  • @asifalikalody1722
    @asifalikalody1722 Před 2 lety

    Good explanation bro ❤️

  • @hasybro4798
    @hasybro4798 Před 2 lety

    Grete

  • @johnmiranda4587
    @johnmiranda4587 Před 2 lety +2

    Thank you so much for the clear explanation of the system. Learned a lot from it and decided to subscribed. Just one question is there a way to calculate the pump flowrate?

    • @TechnicalChallenger
      @TechnicalChallenger  Před 2 lety +1

      Dear Sir
      The pump flow rate is stipulated on its batch .
      The installation flow rate is calculated taking in consideration many aspects .
      The heat exchanger have also its flow rate calculated already .
      The choice for the pump will be done accordingly to the flow rate .
      The flow-rate will be calculated for heat exchangers ,tank filling etc.
      Can you tell me please what do you need it for ?

    • @johnmiranda4587
      @johnmiranda4587 Před 2 lety +1

      @@TechnicalChallenger Well i was talking about the pump illustrated in the pressurization system. Is the pump built-in inside the pressurization unit or a stand alone one? I was curious how much fluid is the pump providing to the system when it detected a pressure loss?

    • @TechnicalChallenger
      @TechnicalChallenger  Před 2 lety +1

      @@johnmiranda4587
      Hi John
      The pressurisation unit have the flow rate stipulated on its batch .
      There are two pumps that are alternating .
      The pumps does not have a big flow rate as it is not a recirculating pump.
      Also the pressurisation unit is just compensating the pressure loss governed by the loss of water .
      Because the pressurisation unit pump have such small flow rate when I fill the unit for the first time I always use the bypass .
      Technically you do not have to calculate a flow rate for pressurisation unit.
      The pressurisation unit is just injecting water in to installation to compensate the water loss because of air valves eliminators or tiny temporary leaks.
      When you buy the pressurisation unit you must choose the one that satisfy your designed system .
      They are pressurisation units that works inline with the main cold water using just a pressure reducer if the main pressure is huge.
      Other pressurisation units are equipped with a small water tank and pumps .
      07946487538
      This is my mobile no.
      Call me if you need more help .
      Kind regards .
      John

  • @l.d0135
    @l.d0135 Před 2 lety +2

    Am I right in thinking that using this example we would have to shut and drain down the system in order to check the expansion vessel charge? If so, should there not be another IV and DOV fitted in-between before it reaches the main line?

    • @TechnicalChallenger
      @TechnicalChallenger  Před 2 lety

      Yes you are very right .
      Thank you for that observation .
      I made this video explaining only the issues that could be generated by the inappropriate settings .
      Technically speaking you are perfect right .
      To segregate the system you need valves .
      Make sense .
      What can I say .
      I am privileged to met people with eagle eyes like you .
      Al my respect.

  • @arnelada6216
    @arnelada6216 Před rokem

    Let’s say Pressurization pump kicks in at 0.5 Bar. How about from 1.5 Bar , the operating pressure becomes 0.8 bar only and not reach yet the 0.5 Bar? Does expansion tank also kicks in through gravity and return the expanded water to the system? Or just wait the pressure to 0.5 Bar to make the pump compensate the pressure loss?

  • @MM-mk6rg
    @MM-mk6rg Před 9 měsíci

    I have a system where the boiler is in the red at about 3bar causing the prv to realise water.the press unit digital screen says 1.1bar and when this kicks in to fill the heating through loss of water it goes from saying 1.1 bar to 2.3bar.what would my problem be.

    • @TechnicalChallenger
      @TechnicalChallenger  Před 9 měsíci

      Check the pressure vessel inside the boiler and see if it is faulty or ifnit is correct presurised .
      See if the temperature is gowing above 90’C

  • @wasabnasir9766
    @wasabnasir9766 Před rokem +1

    Is any different between pressure vessel and expansion tank?

    • @TechnicalChallenger
      @TechnicalChallenger  Před rokem

      Yes it is .
      They are both keeping the pressure in control but they are different features .
      One in open vented an the other one is closed circuit

  • @Selvanbaskaran
    @Selvanbaskaran Před 3 lety

    life advice " watch the video @ x1.5 "
    but good content tho

  • @nikhilharane262
    @nikhilharane262 Před 3 lety +1

    How much water can collect the pressurisatoon tank? If the pressure in the line increases because of decrease in load and so that the ahu unit gets off with its valve?

    • @TechnicalChallenger
      @TechnicalChallenger  Před 3 lety

      Hi NiKhil
      The pressurisation unit should not compensate the water volume unless there is an accidental leak in to the system.
      The well calculated pressure vessels should be able to keep the pressure within the limits if the
      relation between the cold and hot agent volume has been well evaluated .
      If you have a tall building you must consider the starting pressure and then you must add the appropriate pressure vessels to compensate the volume increase generated by the rise in temperature .
      If the volume will not be compensate then the pressure will rise and if the go over the Pressurisation unit high set point if the system is well integrated it should stop.
      If the pressurisation unit’s high set point for alarm is set above the PRV’s set then the PRV will be triggered to save the system.
      If the system was well design then check the pressure vessels and see if they are properly pressurised and if they have the bellows inside healthy.
      If water poor out trough the air charging port then the pressure vessel must be replaced.
      So just to make one think clear.
      You can interfere with the pressurisation unit to fill the system hundreds times but that is not a healthy idea.
      Also you can ignore a PRV leak due to the incorrect temperature volume ratio but that is not what a good engineer is doing .
      If your system is very complex then use a vessel and fit it under the PRV.
      Then Rise the water temperature from the whatever it is until it reaches the working one used to heat the building.
      See how much water you are loosing trough PRV until the PRV stop leaking .
      Then repair the pressure vessels or get the appropriate one that are capable to reduce the pressure variation until it will stay within the anticipated bandwith.

    • @nikhilharane262
      @nikhilharane262 Před 3 lety

      Let me tell one thing there are total 37 AHUS each is having capacity of 98GPM(flow rate) if I will stop all of them. Then what will happen?

    • @TechnicalChallenger
      @TechnicalChallenger  Před 3 lety

      @@nikhilharane262
      If the pressure vessels are properly designed it should be ok .
      When you refer to stopping them you talk about heating or the pumps ?

    • @nikhilharane262
      @nikhilharane262 Před 3 lety

      I am talking about stopping flow from them. At that time the system Pressure will get increase?

    • @TechnicalChallenger
      @TechnicalChallenger  Před 3 lety

      @@nikhilharane262
      Nope
      You have flow and return
      The flow will equalise with the return
      It should not happen anything

  • @wasabnasir9766
    @wasabnasir9766 Před rokem

    Could you send me any video/ drawing for showing the connection between expansion tank, pressurization unit and air separator along with all safety and automation.

    • @TechnicalChallenger
      @TechnicalChallenger  Před rokem

      Dear Sir
      I have more videos about pressurisation units and boiler systems .
      If you will scroll trough my videos you will find more information .
      I did not really targeted expansion tanks systems as they are too simple .
      If you will dean with vented systems that imply expansion tanks make sure the tanks will be fitted at a reasonable hight so there will be enough pressure in to the system
      Send me your e mail to see what can I do .

  • @prithwishdey6708
    @prithwishdey6708 Před 4 lety +1

    #sir please one video make on hvac compressor part winding cannection

    • @TechnicalChallenger
      @TechnicalChallenger  Před 4 lety

      Prithwish Dey
      I shall make for both
      Star Delta and Part Winding

    • @prithwishdey6708
      @prithwishdey6708 Před 4 lety

      Thanks sir

    • @TechnicalChallenger
      @TechnicalChallenger  Před 4 lety

      dear sir
      Part winding connection is simple and there are a lot of video about it .If you really want one I ll do it with pleasure but there are a lot of very good ones .I can help you with some explanations if you need some guidance .

    • @prithwishdey6708
      @prithwishdey6708 Před 4 lety

      Bitzer compressor contractors are take ranning amps 50,50 either 60,40 in part winding. How do it happen? and how will know actual ranning amps?

    • @prithwishdey6708
      @prithwishdey6708 Před 4 lety

      What for reson when chiller start at first unloading start/open, then compressor running....?