Calculating Voltage Drop

Sdílet
Vložit
  • čas přidán 27. 07. 2024
  • #AccessToPower #AccessElectric
    accesstopower.com
    In this episode of AccessToPower we will discuss how to calculate voltage drop in a circuit using the Tables in Chapter 9 of the National Electrical Code (NEC). We go over how to use Table 8 to calculate the "K" or the constant value of copper and aluminum. We show you how to use the "K" Value to calculate the voltage drop of a circuit using nothing but Table 8 in the NEC. We then look at my preferred method which uses Table 9 in Chapter 9 of the NEC to calculate voltage drop using the "Z" or Impedance values of Copper and Aluminum conductors given for each size in various kinds of Conduit.

Komentáře • 59

  • @Jayson8181
    @Jayson8181 Před 4 lety +7

    There is so much garbage out there, I'm really happy to find someone who is clear, easy to understand and stays focused on the question at hand. Thanks and keep on doing what you're doing!

  • @KevinCoop1
    @KevinCoop1 Před 4 lety +3

    As a designer for a contractor and doing thousands of calculations over the years, I always wanted to know the wire size needed in one calculation. I did not want to keep guessing until I got less than 3%. Less complicated method. 2xKxampsxLdivided by 3% of voltage= cm. Conductor properties table will give you needed wire size. Also, for balanced 3 phase 3 wire multiply single phase calculation at end by .86. 1.73/2=.865. And for balanced three phase 4 wire, multiply single phase calc at end times .5. If balanced load, then no neutral current. 1/2=.5.
    Respectfully submitted, Kevin

  • @12mandingos
    @12mandingos Před 5 lety +2

    Thank you for putting these videos together! For someone getting underway in the trade I find these videos very helpful. Shout out to the 209 too!

  • @jeremiahwoodhull6122
    @jeremiahwoodhull6122 Před rokem +1

    Thank you for your time in making this video. It is easy to follow along and understand. Especially on impedance. Once again thank you.

    • @AccessToPower
      @AccessToPower  Před rokem

      Thanks for commenting. I appreciate the feedback.

  • @energyexecs
    @energyexecs Před rokem +1

    ...Nice learning video. I also like using Z (the impedance) because it provides a glimpse for the human that impedance plays an important role in voltage delivery to the end point.

  • @frankvieira764
    @frankvieira764 Před rokem

    I think you're Portuguese, but I love you're videos. Thank You.

  • @georgegenteroni6645
    @georgegenteroni6645 Před 2 lety

    Thank you for the clear discussion abou voltage drop.

  • @ethanbrewer14
    @ethanbrewer14 Před 3 lety +1

    Thank you for this video! It helped me a lot in understanding and feeling confident in my calculations.

  • @davidjackson4112
    @davidjackson4112 Před 10 měsíci

    Thanks for your help in solving voltage drop calculation.

  • @bcv3934
    @bcv3934 Před 5 lety +1

    Another good informational video👍
    Your doing such a good job for those who want to learn more and improve.

  • @victorvasquez5418
    @victorvasquez5418 Před 15 dny

    Good job thank you for your help

  • @peterponcedeleon3368
    @peterponcedeleon3368 Před 4 lety

    Thanks!! Keep them coming.

  • @elc2k385
    @elc2k385 Před 3 lety +1

    Awesome! Thank you once again.

  • @azscib
    @azscib Před 4 lety +1

    That was such a WELL done video. So clear and precise! great job. Others should follow as some ramble through their videos. Again ~ thank you!!!!

  • @yasirjohny
    @yasirjohny Před 5 lety

    Thanks A lot , your method of teach is very unique I completely understand of VD calculations. 🌹🌹🌹

  • @ernestocortez2957
    @ernestocortez2957 Před 4 lety +1

    Thank you! Im getting ready to take my state test here in CA this Saturday. I'm ready for a voltage drop question.

    • @AccessToPower
      @AccessToPower  Před 4 lety +1

      Ernesto Cortez, thanks for the comment. Good luck on your test.

  • @Buhzuka
    @Buhzuka Před 4 lety +1

    Super Helpful! Good Informational video!!

  • @bojitti
    @bojitti Před 4 lety +1

    Thanks a lot. I find this very useful.

  • @tedecacao
    @tedecacao Před rokem +1

    Thank you so much for this video! Subscribing now

  • @crisrobersonsantos9192
    @crisrobersonsantos9192 Před 3 lety +1

    Thank you very much for the very clear, detailed and straight forward video lesson. This helps me a lot on my studies.
    NEC Table 9 have a title of:
    Alternating-Current Resistance and Reactance for 600-Volt Cables, "3-Phase", 60 Hz, 75C (167F) - Three Single Conductors in Conduit
    May I kindly consult if we can use NEC Table 9 for 1-Phase circuits?
    even though the title indicates "3-Phase"
    Thanks again and more power to your channel.

  • @rickydags
    @rickydags Před 2 lety +1

    Thank you for this video. Question for you about the impedance for the single phase case. The Chapter 9 Table 9 of the NEC says in the title that it is for three phase power, but you used it in the single phase case. Is there something in the NEC that indicated that table 9 can be used on the single phase case or is there another table for the single phase case?

  • @ankitpanchal5766
    @ankitpanchal5766 Před 2 lety +1

    Great video. But can we use Vd = 2*L*R*I / 1000 formula?

  • @amadogomez436
    @amadogomez436 Před 4 lety +1

    Great

  • @aimansado3457
    @aimansado3457 Před 4 lety +2

    where can I get the formula book? internet?

  • @reyniernunezbeltran2730
    @reyniernunezbeltran2730 Před 11 měsíci +1

    Both methods should give equivalent results. The reason why using table 9 gives you a slightly different result is because eddys current (Q) losses is not taken into account. But if (Q) is used both methods should be 99.9 % equivalent.

  • @washingtonmazzini9120
    @washingtonmazzini9120 Před 10 měsíci

    GOOD AFTERNOON, I HAVE THE FOLLOWING QUESTION: IF A THREE-PHASE FEEDER IS INSTALLED IN A METAL WIREWAYS, TABLE 9 IS APPLIED TO CALCULATE THE VOLTAGE DROP?

  • @pululunguente
    @pululunguente Před 3 měsíci

    And what about you having 2 sets of conductors with Z method? Please Help!!

  • @matthewgaskey4954
    @matthewgaskey4954 Před 3 lety

    good video! a couple questions tho. How did you get 2.75% from 13.20 in the single phase method (15:27) and your applied voltage cell reads 480. thanks

    • @AccessToPower
      @AccessToPower  Před 3 lety

      Matthew Gaskey also, this calculator may be helpful. www.calculatorsoup.com/calculators/algebra/percent-difference-calculator.php

  • @bluesolarmx
    @bluesolarmx Před 3 lety

    If using meters, for example with a 10AWG cable, would it be the same? 4.070*10380/1000m?

  • @bryanbecker
    @bryanbecker Před 7 měsíci

    When would one use the “coated” section?

  • @christopherestevez6375

    Only thing is i couldnt find where to find chapter 9 table 8 in my nec book

  • @rowellcanillo7469
    @rowellcanillo7469 Před 3 měsíci

    Is table 8 is only applicable in DC system?

  • @562sela8
    @562sela8 Před 3 lety

    nice vedios

  • @josemarti8642
    @josemarti8642 Před 3 lety +1

    How do you factor in multiple runs of conductors into that Voltage Drop equation?

    • @rupe53
      @rupe53 Před 3 lety

      Jose ... you need to figure the drop for each run separate then add up the results for the whole run. If the numbers are too high (percentage of drop) then you need larger wire. You will almost never have a problem if you stick to 80% loading of a branch circuit and stay under 100 ft in a run. To ease the brain work use one of the voltage drop calculators on the web. You plug in wire size, load, and run length. They will tell you voltage drop and percentage. After you use it a few times you will get a feel for where you need to be.

  • @Rabb_L_Rouser
    @Rabb_L_Rouser Před 11 měsíci

    Why does no one bring up how to find voltage drop of wire larger than 4/0? I need voltage drop of 850ft run of single conductor aluminum 750kcmil, 3000A.

  • @omargarcia4401
    @omargarcia4401 Před 3 lety

    Great video only issue with using the table 9 formula with impedance (z value) is that the impedance of Table 9 is only good for 3phase - Three single conductors in conduit as per the title of that Table so I’d assume it’s not totally accurate for use with Single Phase Voltage drop calculations. Sorry to be that guy.

  • @Studi314
    @Studi314 Před 4 lety

    Is the second formula 2xZxDx(I /1000) the way you have it written or is it really ( 2xZxDxI)/1000?

    • @AccessToPower
      @AccessToPower  Před 4 lety

      Studi314, I’m not sure what you’re referring to because I have a written (2xZxDxI)/1000.

    • @Studi314
      @Studi314 Před 4 lety

      At the time 13:00, the formulas do not have any parenthesis in them.

    • @AccessToPower
      @AccessToPower  Před 4 lety

      Studi314 , I see what you’re saying. It would’ve been helpful to have the formulas with parentheses. But also under the rules of orders of operation in math, multiplication always comes before division. So the formula is correct with the parentheses or not but it is more helpful with the parentheses

  • @hoovie3000
    @hoovie3000 Před 2 lety

    Why can't we use Chapter 9, Table 9 of the NEC?

  • @johnnytotheworld4802
    @johnnytotheworld4802 Před 4 lety

    Which cable is affected by the voltage drop?

  • @oscar27ization
    @oscar27ization Před 4 lety +2

    You said single phase formula but the voltage drop was 480??? Wasn’t suppose to be 120v

  • @josericardomarin6911
    @josericardomarin6911 Před 4 lety +2

    Hola boss this Is José Marín can you please maje a vídeo for load calculacions for motors.
    Thanks

    • @AccessToPower
      @AccessToPower  Před 4 lety

      hey Jose. hope all is going well with you... I will try and do a video on that subject.

    • @mikechan-nel8390
      @mikechan-nel8390 Před 4 lety

      @@AccessToPower sir what is the formula to get the percent?

  • @veritasaequitas9875
    @veritasaequitas9875 Před 4 lety

    CM in the equation. What are Circular Mills?

    • @veritasaequitas9875
      @veritasaequitas9875 Před 4 lety

      It's ok. Got it. Just wondering what's wrong with square mils. Or even square inches.

    • @AccessToPower
      @AccessToPower  Před 4 lety

      circular mills is the circular cross section of the wire we are examining. You can find the CM for each size of wire in Chapt 9, Table 8 of the NEC. Check minute mark 12:38 and you will see that table.