It’s A Wonder I Could Get It Going!

Sdílet
Vložit
  • čas přidán 28. 08. 2024
  • In this video I visit a house where a tree landed on the power to the house. #hvacguy #hvaclife #hvac #heatpump #airconditioner #hvactrainingvideos #hvactroubleshooting #furnace #hvacinstall
    Merch Store: hvac-guy-2.cre...
    HVAC LIFE FB Group: / 521086622906115
    Here are links to the tools I use, And it costs you nothing extra to buy from this list:
    Yellow Jacket Tubing Expander: amzn.to/3EvEQnF
    Yellow Jacket 60278 Flaring Tool: amzn.to/3FPjlyY
    Veto Pro Pac Tech MCT Blackout: Amzn.to/3iCieJK
    DeWalt work table: amzn.to/3fKChoB
    Inficon D-tek Stratus: amzn.to/3zNg7IO
    3 Amp Lil’ Popper: amzn.to/3D5lt3e
    Inficon D-Tek Stratus: amzn.to/3RvnXOl
    Fielpiece SC680 Clamp Meter: amzn.to/33rhxvE
    Fieldpiece SC480 Clamp Meter: amzn.to/33kfgCB
    Fieldpiece SMAN 480 Digital Manifold: amzn.to/3twfVvA
    Fildpiece SVG3 Vacuum Gauge: amzn.to/3udursu
    Fieldpiece DR58 Leak Detector: amzn.to/3nt1TXw
    Fieldpiece JL3KM2 Bluetooth Manometer set: amzn.to/3blMrJR
    Fieldpiece Blutooth Scale: amzn.to/3Gzveab
    Fieldpiece SDMN6 Manometer: amzn.to/3qwk9RP
    Fieldpiece MR45 Recovery Machine: amzn.to/3cUFX5h
    Fieldpiece 8CFM VP87 Vacuum Pump: amzn.to/3qC2wA2
    Yellow Jacket Tubing Expander: amzn.to/3sjuK3a
    Milwaukee M12 Impact Driver: amzn.to/37xXkqk
    Makita XDT16: amzn.to/3riXuaJ
    Makita 18V Light: amzn.to/3Fw4GW4
    Makita Wet/Dry Vacuum : amzn.to/3tw4dAL
    Makita 18V Battery Mounts in Van : amzn.to/3GxpVID
    Makita Jobsite Radio: amzn.to/3HuVp2u
    DIY Vacuum Attachment for drains: amzn.to/3tDpfNU
    Fieldpiece Smart Probe Kit : amzn.to/34NG3HL
    Klein Heavy Duty Wire Strippers : amzn.to/3I8YNzT
    Klein Needle Nose Crimpers/Stippers: amzn.to/3fuwXlw
    Klein Knee Pad: amzn.to/3cy6FB0
    Klein 7in1 Flip Socket: amzn.to/3bpabwG
    Klein Journeyman Pliers: amzn.to/3tvB60w
    Milwaukee Slim Packout On My Torch: amzn.to/3KeLm3j
    Aluminum Packout Wall Mount on torches : amzn.to/3Kf9hQg
    Milwaukee Tool Box: amzn.to/322iyK9
    Veto Pro Pac Tech MCT: amzn.to/3nwwQdA
    Milwaukee Hook Blade Knife: amzn.to/33F3m5T
    Testo 300 flue gas analyzer: amzn.to/3IcS3Bd
    Western Nitrogen Regulator: amzn.to/3rmdKrx
    Klein Canvas Bucket: amzn.to/3FyzKVf
    Flag Velcro Patch Kit: amzn.to/3K8Eswx
    Supco Magnetic Door Switch Holder: amzn.to/34IcXcL
    Milwaukee Magnetic Light: amzn.to/3FulCfF
    Milwaukee Rechargeable Headlamp: amzn.to/3nuXsvf
    SS2 Float Switch: amzn.to/3K7LJMW
    3-Amp Breaker: amzn.to/3nxaSXJ
    Appion Valve Core Removal Tool: amzn.to/33CFArw
    Appion G5 Twin Recovery Machine: amzn.to/33Dvd6C
    Yellow Jacket Large Tubing Bender: amzn.to/3qwJv1U
    Similar Small Tubing Bender: amzn.to/3fJsziJ
    Fluke Twist Guard Test Leads: amzn.to/3216R6j
    Fluke 975 Air Meter: amzn.to/3GwD9oM
    Honeywell T-4, 2-Heat, 1-Cool Programmable Thermostat: amzn.to/3qtIuaX
    Kidde Carbon Monoxide Alarm: amzn.to/3qtIIyP
    SolderWeld Flame Resistant Magnetic Blanket: amzn.to/3qtJ4Wb
    Malco 1/4 - 5/16 flip bit : amzn.to/3nr67yU
    Quick Check Acid Test: amzn.to/3GA2XAy
    Wiha Torqe Screwdriver : amzn.to/3u1swH6
    Wiha Torqe Screwdriver 1/4” adapter: amzn.to/3IH22Pw
    Compressor Tote: amzn.to/3H8xHst
    Inspection Mirror: amzn.to/3r9PERV
    Wiha TorqueVario-S 10-50 in/lb Torque Screwdriver : amzn.to/3GbKAku
    1/4” adapter for Wiha Torque Screwdriver : amzn.to/3u8g0pq

Komentáře • 141

  • @edwardmissouri2216
    @edwardmissouri2216 Před 14 dny +1

    Good job. I'm sure there are some bad companies that would have said "the whole thing is shot". It's nice to see a honest technician. I wouldn't want that big hunk of tree hanging there. I would think the power company would remove that, being near their wires. You saved those people a lot of money.

  • @electricboyo
    @electricboyo Před 2 měsíci +1

    Thanks again for showing us “how to do it right” And for showing the step-by-step method to resolve multiple electrical faults.
    An office I previously worked in was randomly blowing the 3 amp fuse in the furnace when the thermostat called for cooling. The HVAC contractor replaced the fuse several times over the course of several weeks. Finally he was about to replace the contactor in the condensing unit. But I said “Wait a minute - contactors hardly ever short out their 24V coils. I suggested maybe there was an intermittent short in the 25 ft of thermostat wire between the furnace and condensing unit. So the HVAC guy said “sure, I’ll run a new wire. That’s cheaper than a contactor.” The problem never came back.

  • @GoatzombieBubba
    @GoatzombieBubba Před rokem +4

    "Electrician" should of replaced the disconnect while he was at it.

  • @OGHVAC
    @OGHVAC Před měsícem +1

    I had the exact same issues on a gaspak 10 years ago. Damn "electrician" did not do the client any favors. Nice job T/S/R Curtis!

  • @sadude88
    @sadude88 Před rokem +3

    You would never find a package unit on a residential property in Australia. Theyre all hi-wall splits or in ceiling split ducted. All that ever fails on them are PCBs (boring).
    Pick up your cable tie off-cut mate 😂. Good job the repair.

  • @charlesphillips6455
    @charlesphillips6455 Před měsícem +1

    You have taught me so much about patience and perseverance, two qualities I struggle with.

  • @jamiepatterson1214
    @jamiepatterson1214 Před rokem +1

    If it's done right the first time then the next person to work on things has an easier time getting the work done. And sometimes, the next person to work in it is you.
    A person who just want to get the work done and leave, isn't the person for the job. Because once they're done, the odds that someone will have to redo their work is high.
    There needs to be more people in all fields with you work ethic Curtis.

  • @MCRD115
    @MCRD115 Před rokem +5

    My name is Shannon I'm a Semi Truck Owner. I love watching your Channel great videos. I watch your Channel more than I watch Sports on TV. No I'm a CDL License holder but I enjoy watching repair and replace HVAC Systems. Keep making the videos.

  • @georgiapatriot4575
    @georgiapatriot4575 Před rokem +1

    That took a bit of persistence, logical thinking, and a bunch of knowledge to work your way through that one.

  • @franciscotejeda1461
    @franciscotejeda1461 Před 2 měsíci +1

    Exclent video Mr Curties , it shows all those years of experianse .

  • @janchristensen7993
    @janchristensen7993 Před dnem

    You are unreal Curtis. 👍

  • @berated4541
    @berated4541 Před rokem +13

    Just wanted to take second to thank you for all your content. I started out watching your videos to better get my head wrapped around HVAC as an installer and have since moved in to service. Your videos have helped me on numerous service calls and I appreciate you not only sharing your knowledge with the CZcams community, but taking us along on your adventures!

  • @Donhvac
    @Donhvac Před rokem +3

    PROFESSIONAL TROUBLESHOOTING AND REPAIR

  • @robalexander7348
    @robalexander7348 Před rokem +3

    Nice detective work Curtis,well done 😉

  • @Bradleyscience
    @Bradleyscience Před 6 měsíci +1

    Well done, surprising that it was not more damaged! Cheers

  • @w5cdt
    @w5cdt Před 2 měsíci +1

    Good job cleaning up a mess!

  • @earlking4299
    @earlking4299 Před rokem +4

    Not a hvac technician. But I like watching.

  • @savagenomore
    @savagenomore Před rokem +1

    I like the videos like this as well as the others, watching you is helping me chose an HVAC Service tech that is an honest ethical person because I'm learning how things work and they can't blow smoke up my butt and charge me nearly $500 service call to change a capacitor anymore.

  • @Iceehotair
    @Iceehotair Před rokem +3

    Nice work Curtis 👍🏻

  • @federicovalenzuela1201
    @federicovalenzuela1201 Před 9 měsíci +2

    You’re very good 👍 I congratulate you

  • @roberturena2712
    @roberturena2712 Před rokem +3

    Remember working on so many of those Rheem a/c’s and Rudds 😅

  • @WSmith2024
    @WSmith2024 Před rokem +3

    Good detective work. Thanks for the video.

  • @dashcamandy2242
    @dashcamandy2242 Před rokem +3

    10:41 - No need to apologize, that is a pretty shoddy wiring "repair" for an "electrician."
    20:00 - You forgot to retrieve a piece of zip-tie. 🤪
    Nice job on the DIY inline fuseholder! That is, after all, exactly what's under the molded rubber of a store-bought one.

  • @MikeB9771
    @MikeB9771 Před rokem +4

    Brought it back like Lazarus, good job Curtis

  • @jhatfield2755
    @jhatfield2755 Před rokem +5

    Offer them a surge protection device on disconnect. Good work

    • @johncspine2787
      @johncspine2787 Před rokem +1

      I put surge protection on my main incoming service panel, and the downstairs panel that has a line run outside to my chicken coop..wanted all my bases covered..

  • @carlmasi1063
    @carlmasi1063 Před rokem +3

    You did it again you are the best thank you
    for the great video I love watching you do
    The best job you can do thank you

  • @ginny8765
    @ginny8765 Před rokem +3

    Love watching you work? miss my daddy and helping him do all kinds of work .

  • @61espo
    @61espo Před rokem +2

    Excellent trouble shooting! Great job! Subscribed!

  • @samyz1660
    @samyz1660 Před rokem +2

    Not just learning but also enjoying your professional work. Great job Curtis

  • @stevencossaboon3237
    @stevencossaboon3237 Před rokem +3

    Excellent job Curtis.

  • @anthonyelectric6045
    @anthonyelectric6045 Před rokem +6

    Wow lots of little things went wrong. Customer got lucky it wasn’t worse like you said. Nice repairs 👍

  • @davidseymore3411
    @davidseymore3411 Před rokem +2

    Nice job.

  • @wiedapp
    @wiedapp Před 2 měsíci +1

    Nice Pontiac in the background, needs some love but otherwise cool!

  • @roberts.3712
    @roberts.3712 Před rokem +4

    Excellent!

  • @robertk4629
    @robertk4629 Před 11 dny

    wow loved that video.... Master AC Guy ...great job

  • @christhompson7612
    @christhompson7612 Před rokem +4

    I really like how you have started explaining what you are doing when you read voltage and what you are checking for. It really helps to understand how the system is operating and what problems you are looking for. Thanks for the time you put into these videos.

  • @dondokulil2193
    @dondokulil2193 Před rokem +1

    love watching your stuff

  • @dalescott838
    @dalescott838 Před 9 měsíci +1

    Very good video. Enjoyed your methodological methods. You take the time required to do a very good job.

  • @bilalcoaker9882
    @bilalcoaker9882 Před 8 měsíci +1

    Excellent job, and troubleshooting skills

  • @ginny8765
    @ginny8765 Před rokem +3

    Was work? Cuz you look like you're having fun 😊

  • @Iosksnwjwnijujw8
    @Iosksnwjwnijujw8 Před rokem +1

    What a job 👍

  • @kens.3729
    @kens.3729 Před rokem +2

    That’s either a “Black Widow” Spider or a “Brown Recluse” Spider. There is NO such thing as a “Brown Widow”. 😬👍

    • @HVACGUY
      @HVACGUY  Před rokem +1

      google them. I’m not making it up.

  • @KenKen-ui4ny
    @KenKen-ui4ny Před rokem +2

    Storms, lightning, acts of god and gravity, like falling trees in this case. Can do a lot of damage to unprotected equipment, like blowing start capacitors and what not, even without physical contact to the unit. It just has to be attach or using an outside source of power at the wrong time.

  • @BrokenRRT
    @BrokenRRT Před rokem +2

    That wasn’t an electrician that did that. It was a backyard mechanic.

  • @josem2468
    @josem2468 Před rokem +7

    Curtis you're going to be the New Spider-Man. Bit by a spider. lol

  • @snugglebunnyhaven7258
    @snugglebunnyhaven7258 Před rokem +4

    Good work. Although I do have one concern. When you changed the compressor connection, i did kinda bite my tongue when you zip tied the leads to the compressor high side line. That tube gets really hot and i'd be a bit nervous that at some point the wire may wear through and then short. It can then punch a hole through the line causing the gas to vent. Over time the insulation can thin with the heat of the line. Also, in the even of a nearby lightning strike, induction from it or if it runs into the system, it can arc right through the insulation. As an old veteran tech, i'd not ever tie electrical wires to any of the refrigerant lines of any system.

    • @thomashoward6792
      @thomashoward6792 Před 7 měsíci

      retired with 60 years commercial refrigeration and HVAC commercial and residential
      agree with above comment 110%

    • @Todestelzer
      @Todestelzer Před měsícem

      He used 2 zip ties. No direct contact to the tube. I don’t think it’s an issue.

  • @549BR
    @549BR Před rokem +5

    It could have been worse, but not by much. I'm presuming that the homeowner's insurance will pay for your work and the electricians; minus a deductible. Very nice repair work. 😎

    • @johncspine2787
      @johncspine2787 Před rokem +1

      Except most ppl save on insurance with a very high deductible..and I just had my first major experience w insurance, Farmer’s, I had an attic fire..zero help, never sent an agent even though there are local offices within two minutes of the house..they took down my ceilings, packed out my stuff, then allowed the contractors to skip to another job for two months..I have story after story about what a freaking nightmare the whole thing was..instead of listening to me, and looking at my photos, they overpaid the contractor even after I documented them “not” doing what they said in the estimate, they actually gave them more money, but forced me to pay from my account..I swear, the thing felt like fraud, fraud, fraud…and I couldn’t do anything about it..check your policy..even then..good luck..

  • @Joseph77716
    @Joseph77716 Před rokem +1

    Awesome work 👏

  • @billlaporte8255
    @billlaporte8255 Před rokem +1

    Nice work, love watching your vids man!

  • @mr-oq2kq
    @mr-oq2kq Před rokem +2

    Nice job Cutis!

  • @zekenzy6486
    @zekenzy6486 Před rokem +1

    Great Video. Thank you for sharing

  • @chuckquinn8026
    @chuckquinn8026 Před rokem +3

    Excellent work Curtis! 👍👍

  • @tonydelgrego2906
    @tonydelgrego2906 Před rokem +4

    A professional troubleshooting and repair. Great video

  • @JohnSmith-ug5ci
    @JohnSmith-ug5ci Před rokem +2

    Good job.

  • @notyoung
    @notyoung Před rokem +1

    Your "inline fuse" is familiar. I've found that much easier (and faster and cheaper) than searching for and wiring in a "real" fuse holder.

  • @roberturena2712
    @roberturena2712 Před rokem +3

    Since I’ve retired from the a/c world I love watching your videos it keeps me a/c sharp, tho I miss working on a/c but not so much during our summer desert temperatures of 118 to 120 degrees it can get very dangerous very quick out here I do get a little bored not working on units that sometimes I just can’t wait to service my a/c Lol also you have great work ethics of (NCC) “no cutting corners” sometimes short cuts can cause some tech’s a costly service call, great job 👍

  • @ervingoss5442
    @ervingoss5442 Před rokem +2

    Good job, Curtis. I agree with you on the the tree. I would have someone come out to get rid of that thing.

  • @Empty7775
    @Empty7775 Před rokem +2

    Good job dude, nice fix

  • @Hvac-dude
    @Hvac-dude Před rokem +2

    That's crazy !!

  • @DanO181919
    @DanO181919 Před rokem +3

    The connectors that you used on the common and run connections. Do you have a part number. Very interested in those. Thanks.

  • @Bass.Player
    @Bass.Player Před rokem +2

    Neat old house but it needs a lot of work looks like...

  • @davehowell4111
    @davehowell4111 Před rokem +2

    Nice troubleshooting 🤙

  • @stephenbullock-yn3vh
    @stephenbullock-yn3vh Před rokem +2

    Excellent fix 👏 👍 👌 😀

  • @patricspointofview7188
    @patricspointofview7188 Před rokem +2

    Nice job on this one, Curtis. 👍

  • @gregfisher216
    @gregfisher216 Před rokem +2

    Good hard work Curtis, good content, keep it coming!

  • @user-ql2bz8on7m
    @user-ql2bz8on7m Před měsícem

    Nice work

  • @coldiez1464
    @coldiez1464 Před 5 měsíci +1

    Very impressive work Curtis. Your video quality and attention to detail match your tech work ethic. Great content

    • @HVACGUY
      @HVACGUY  Před 5 měsíci

      Much appreciated!

  • @OnusBones
    @OnusBones Před rokem

    I think that might be the most complex one I've seen you do so far; lots of things broken. Like you, I have to wonder what the electrician was doing; perhaps a little more than expected in some ways (like not saying "call the AC guy"), yet he missed some obvious burnt wires when he fixed others.

  • @RayRay-nb7tn
    @RayRay-nb7tn Před rokem +3

    Good man for the job fir sure. So an electrician installed new stat wire and you put unit in, and he went into panel of unit do you warranty the unit still on parts ? If another tech or anyone for that matter worked on unit I don't stand behind the warranty.

  • @gregorywoodcock2472
    @gregorywoodcock2472 Před rokem +1

    You need to get Wago connectors they're better than the screw-on caps thousand percent also makes your job look more professional.

  • @John-cb6wn
    @John-cb6wn Před rokem +1

    You’re very well organized always enjoy your videos

  • @HailoiHailoi
    @HailoiHailoi Před 6 měsíci

    This video is fire! I finished hvac school 1 years ago, and did install for a year.trying to get into service. ! your video help me grow and learn so much . I paused and trying to solve and learn through videos like this! keep them coming!

  • @Aerospace_EdC
    @Aerospace_EdC Před rokem +1

    Great troubleshooting, you found all the problems and got it working including repairing the shoddy electricians work. I bet it makes you feel good you got the system back in order !!

  • @user-pu6ov7cg3l
    @user-pu6ov7cg3l Před 6 měsíci

    Great job!

  • @robertgwalsh5878
    @robertgwalsh5878 Před 4 měsíci

    Nice job

  • @colinkolb3524
    @colinkolb3524 Před rokem

    Great video!

  • @brandoncorrea511
    @brandoncorrea511 Před rokem

    Do more like that . Pls

  • @kain93
    @kain93 Před rokem

    Curtis just one great tech can’t say much more but the word great but also smart. God bless you Curtis .. thanks for the videos.

  • @m9ovich785
    @m9ovich785 Před rokem +2

    I see a future Fail point. The black & White Line Wires are up against the edge of the hole in the Sheet Metal .

    • @search_eternal
      @search_eternal Před rokem +3

      That hole the edge is rolled over and not sharp. Seen many Ruud units with the wires ran like that and never any problems.

  • @focusedelectronics
    @focusedelectronics Před rokem

    Not sure how many spades you put on like those but there’s a ratcheting crimp tool that makes them easy (will do both wire and insulation crimp.

  • @John-dp3ln
    @John-dp3ln Před rokem +2

    Maybe Forgot to put bushing back for compressor wiring. Otherwise great job.

    • @HVACGUY
      @HVACGUY  Před rokem +4

      Bushing broke. I used the other slot that had a bushing in it.

    • @bobboscarato1313
      @bobboscarato1313 Před rokem +3

      @@HVACGUY Curtis those helicopter folks need to be told everything!

  • @stex1985
    @stex1985 Před rokem +1

    👍

  • @jamesfitzsimmons381
    @jamesfitzsimmons381 Před rokem +3

    Great repairing. Never liked those compresser Spade connectors. Didn’t trust them. I connected them the same way

    • @joehead1294
      @joehead1294 Před rokem +1

      Open barrel or B crimp. I like to solder them on after mashing down the tabs. Just a little dab for peace of mind.

  • @search_eternal
    @search_eternal Před rokem +3

    You should try some Wago connectors. That's all I use now.

    • @leviweltin1163
      @leviweltin1163 Před rokem +2

      Where do you get them from other than online?

  • @jeanlawson9133
    @jeanlawson9133 Před 5 měsíci

    It very interesting 🤔.....

  • @pauldusa
    @pauldusa Před rokem +2

    You didn’t do a cap test

  • @beethoven2JAMES
    @beethoven2JAMES Před rokem

    Where's the bloopers Curtis..🤔🤣

  • @tedhicks5431
    @tedhicks5431 Před rokem +2

    That was good one have you ever tried the Zebra stat may help sometimes

    • @HVACGUY
      @HVACGUY  Před rokem +1

      Not sure I know what that is

    • @tedhicks5431
      @tedhicks5431 Před rokem +1

      @@HVACGUY if knew how I'd send you a picture of it got from ccd ur may have ig

  • @larryehrlich57
    @larryehrlich57 Před rokem +3

    Maybe you should wear those thin rubber gloves all the time. I would rather have a spider on my rubber gloves than my bear hand....whether the spider bites or not.

  • @BWIL2515
    @BWIL2515 Před rokem

    So the homeowner is a electrician or a son or a friend never fails

  • @user-fq9og7lr9b
    @user-fq9og7lr9b Před měsícem

    How do you get your customers to be honest in a situation when there’s a power surge or an electrical short.
    Frequently get customers that aren’t truthful about what happens thinking it’s gonna save them money and it makes it much harder to quickly diagnose all the problems with their system, how do you get your customers to tell you the straightforward truth?

  • @robertairey3095
    @robertairey3095 Před rokem +2

    Sooooo how does a job like that go when it comes to billing, I mean do you send a separate invoice to the "electrician" as well? hahaahaha

    • @bobboscarato1313
      @bobboscarato1313 Před rokem +3

      They sue the "honor" system or the "golden rule"! lol

  • @karellodewijks4971
    @karellodewijks4971 Před rokem +2

    👍👍😊😊

  • @user-ur7rv1ei9x
    @user-ur7rv1ei9x Před rokem +1

    Who makes that tool bag? And where did you get it? Thanks for the videos.

  • @kens.3729
    @kens.3729 Před rokem +4

    If Electrician used his Tools and Lack of Experience inside the Outside AC Unit, he needs to Stick to Electric Work and leave the HVAC to a Qualified Technician. 🤪👎

  • @joeysennett4215
    @joeysennett4215 Před rokem +2

    What do you call these types of units. I live in Illinois where I'm used to the split systems where the air handler is indoor with the evaporator and the condenser is outside.

    • @bobboscarato1313
      @bobboscarato1313 Před rokem +3

      The evaporator inside next to the furnace or air handler. Condenser is outside!

    • @HVACGUY
      @HVACGUY  Před rokem +4

      Package Unit

  • @joedavidzuniga1993
    @joedavidzuniga1993 Před rokem

    🎉🎉😊

  • @brandongraser2939
    @brandongraser2939 Před rokem

    now we all know electrician would not do that as you said a handyman would or the homeowner so it was one of those too.

  • @ronroberts7566
    @ronroberts7566 Před rokem +2

    when you go to collect for payment, do you give them the burnt wires, transformer? I did in the day to help them see what failed and prove or justify cost of visit. what’s your policy on replaced parts

    • @HVACGUY
      @HVACGUY  Před rokem +1

      If there is a need for something like that I’ll leave the parts, but usually they get thrown away.

    • @bobboscarato1313
      @bobboscarato1313 Před rokem +2

      In NY we had a policy that when repairing electronics we had to save all the bad parts! Ms. Myerson was the boss lady!

  • @jeffkablock3229
    @jeffkablock3229 Před rokem

    you know that 3/8 discharge line gets hot and will over time short out so try not to put it there !