How to adjust the Transient Delay of your Affordable Diesel Generator

Sdílet
Vložit
  • čas přidán 6. 06. 2012
  • This video instructs you how to adjust the Transient Delay of your Affordable Diesel Generator. This may be necessary in the event that your generator is shutting down due to over/under frequency or over/under voltage alarm because of the startup of a large load such as air conditioning units, compressors, or large refrigeration units.
    For more information visit www.AffordableGenerator.com
  • Jak na to + styl

Komentáře • 75

  • @ridamuftah2500
    @ridamuftah2500 Před 2 lety +2

    This video very useful for me, I used this function with heavy staring current load, thanks alot Engineer

  • @prime91st99
    @prime91st99 Před 9 lety +1

    Thanks for this man give me more knowledge about dse panel..affordable diesel thanks a lot

  • @duncanvogel6991
    @duncanvogel6991 Před dnem

    Hi Mark just wanna find out how to set fuel priming and engine cool down time on the controller

  • @jmwaku1865
    @jmwaku1865 Před 4 lety

    The video helps me to find a solution of over voltage... Thank you !

    • @damarihenrik7285
      @damarihenrik7285 Před 2 lety

      You all prolly dont give a shit but does someone know of a tool to get back into an Instagram account?
      I was stupid lost my password. I appreciate any help you can give me.

    • @theodoredarian7889
      @theodoredarian7889 Před 2 lety

      @Damari Henrik instablaster :)

    • @damarihenrik7285
      @damarihenrik7285 Před 2 lety

      @Theodore Darian i really appreciate your reply. I found the site thru google and Im in the hacking process now.
      Looks like it's gonna take a while so I will get back to you later when my account password hopefully is recovered.

    • @damarihenrik7285
      @damarihenrik7285 Před 2 lety

      @Theodore Darian it worked and I actually got access to my account again. I'm so happy:D
      Thank you so much you saved my ass !

    • @theodoredarian7889
      @theodoredarian7889 Před 2 lety

      @Damari Henrik happy to help :D

  • @dldchannel1316
    @dldchannel1316 Před 3 měsíci

    Already did but why the setting keeps coming back to its original after switching off the key switch. Thanks for your reply

  • @user-xj4eb8sh6b
    @user-xj4eb8sh6b Před 6 měsíci

    I have a case where there is a chiller connected using star-delta and the GenSet trips, do you think it will help ?

  • @zelekeayalewbaychekn4260
    @zelekeayalewbaychekn4260 Před 2 lety +1

    hello hello my dear i have 100kva perkiness generator
    when i tray to start after starting
    the generator stops
    and
    on the display
    over frequency
    how can i adjest it

  • @TheAnd1982
    @TheAnd1982 Před 4 lety +2

    Hi sir.. please give me some advice about my generator. It always automatically shut down and it says "generator locked out".

  • @sundayalaiya9602
    @sundayalaiya9602 Před 3 lety +1

    Hi, if my generator does not have ignition key to switch on before I proceed to transit delay, is it possible for me to still carry out the transit delay?

  • @kelebogilemeje4138
    @kelebogilemeje4138 Před 2 lety +1

    Why do you suggest max of 0.7 ,what if it is set at 2.2, what would happen to the generators?

  • @ahmadrasooli7666
    @ahmadrasooli7666 Před 4 lety

    Hi, bro, I have two generators with using ATI automatic transfer switch system my DG,s are running will but when 12 hours of one DG is completed it gives the signal the other DG set get a start but the previous one does not get stops what is the reason when I bring down the main circuit breaker of DG after some time The DG which will be turned off will get off

  • @lalitarora1522
    @lalitarora1522 Před 3 lety

    How to resolve negative phase sequence problem and dg not stop during on this condition.

  • @jimmyayohan8019
    @jimmyayohan8019 Před 4 lety

    Sir what is problem my genset cummins 4bt3.9-g2 the engine high running acceleration is rough and shaking after 1 minute ,and don't start in automatic but he start in manual starting

  • @ameirrashid2285
    @ameirrashid2285 Před 3 lety +2

    What is couse of generator under frequency?

  • @Tanha_8817
    @Tanha_8817 Před 3 měsíci

    How to reduce or increase the running meter of the generator

  • @omolarafaith8504
    @omolarafaith8504 Před 3 lety

    Please what can cause crank down on deep sea 4510 version

  • @spiritualviking8094
    @spiritualviking8094 Před 15 dny

    Trying to find out how to remove the low water level alarm but im failing. Any help? The water level is okay and everything runs as it should but the alarm wont go away

  • @mohamedsiyam7447
    @mohamedsiyam7447 Před 5 lety +2

    Sir!
    How to update generator controller
    Please answer to me

  • @calluula
    @calluula Před 5 lety +1

    I have probelm my generator started and few second off massage ECM and picture engine

  • @monicamoreno9354
    @monicamoreno9354 Před 4 lety

    Hello because it throws me a memory corruption message after resetting the module when doing the service and it does not turn on

  • @heartofthetraitorAMINE

    Thanks

  • @josephotokunorsackey3895

    How do one trace earth fault on a generator set

  • @quyetho3417
    @quyetho3417 Před 4 lety

    Instruction to install smartgen screens?

  • @atkingapu7040
    @atkingapu7040 Před 9 měsíci

    how to fix under and over voltages in cumins control DSE 8610 KII

  • @user-qp5md3bh2v
    @user-qp5md3bh2v Před 8 měsíci

    Hello. how to turn on the ignition without starting the engine ? DSE 7320

  • @553castrojhay
    @553castrojhay Před rokem

    Hi sir my deepsea controller is DSE7310 volvo penta engine 500kva if I start up my generator 10 to 20 second monitor showing ecu amber .and generator under voltage.please give me advise

  • @philipaddae3628
    @philipaddae3628 Před 2 měsíci

    My generator is over frequency what should I do

  • @abdullahhamadeh
    @abdullahhamadeh Před rokem

    Hello, i have a problem with my kubota generator, when the generator shuts down ,it will not cut the power, it makes the electricity feather or turns on and off while shutting down, i need help on how to fix that

  • @mafioso530
    @mafioso530 Před 6 lety +1

    Is there anything else I can do to to get this generator yo start. We did this already and didn't work. The generator doesn't have anything hooked up to it and it says under voltage

    • @TheMemphiscash
      @TheMemphiscash Před 5 lety

      Saul sanchez check your voltage regulator

    • @mitchimal
      @mitchimal Před 5 lety

      If t's a large load motor, use a VFD on the motor so initial load is much lower

  • @DorahQuaicoe
    @DorahQuaicoe Před 4 měsíci

    Dg generator shutdown when I put new AVR on it what causes that

  • @jimeejeason1576
    @jimeejeason1576 Před 3 lety +1

    Dear sir
    how to reset under frequency shutdown power please explane me because my power generator auto shoutdown and in desplay soing under frequency shoutdowna

    • @ismailali7318
      @ismailali7318 Před 3 lety

      I have this problem under frequency so why did you solve it

  • @mbkim6215
    @mbkim6215 Před 5 lety

    Nice

  • @nishad9048
    @nishad9048 Před 2 lety

    I connect 30kw 3 phase motor to 100kw generator but when it ON getting under voltage alarm let me know y

  • @rajudakshinamurthy3797

    I have one dout genratater running but stopped when coming alarm low coolent oil level oil is full on the tank i given flot switch short is ganerater runing

  • @bonifacengunjiri8028
    @bonifacengunjiri8028 Před 3 lety

    Hi . I have a generator rated at 110 kva. When I connect it to a 30kw compressor the generator stops running and register under frequency error. What could be the problem?

    • @vinhly4344
      @vinhly4344 Před rokem

      when i made load testing 110% for my generator 750kVA (pri), it was stop and appear under frequency, cooling water was too hot and blow out at that time,

    • @jamieauriedward9554
      @jamieauriedward9554 Před rokem

      It's possible because of the huge added load, which cause the voltage to Dip and in turn causing the Genset to register a lower frequency check and re-adjust your transient delay.
      Or it might be your governor which can't keep up with the load demand

  • @pradhapskr5715
    @pradhapskr5715 Před 3 lety

    Can anyone say how can we adjust voltage or rpm in this device through setting

    • @jamieauriedward9554
      @jamieauriedward9554 Před rokem

      Voltage, RPM & Frequency are proportional they can be adjusted through the AVR and the engine speed governor

  • @asgharafridi3300
    @asgharafridi3300 Před 3 lety

    Sir here one problem generator
    Alarm
    Gun Under frequency
    Shutdown

  • @ronneldormido2549
    @ronneldormido2549 Před 4 lety

    Hi sir how to fix deep sea electronics 710 the alarm indacte the picture of turtle what is the meaning of these thankyou

  • @edgarboleche9457
    @edgarboleche9457 Před 4 lety +1

    Sir I have problem with my generator 750kva it start but after a seconds it will off and and the monitor displayed voltage cannot be reached,sir what is the main reason in that problem.

    • @charlieangkor8649
      @charlieangkor8649 Před 4 lety

      the main reason is that the generator is overly complicated.

  • @aliaziz7842
    @aliaziz7842 Před 2 lety

    What reason appear code (stoping) on screen generating 7320

  • @aliahmedaltrhone2066
    @aliahmedaltrhone2066 Před rokem

    So what's the ECU warning ⚠️? please

  • @RajaKumar-bd1tt
    @RajaKumar-bd1tt Před 3 lety

    Perkines generator code spn 110
    Please tell me problem how to sustion

  • @singhpreet241
    @singhpreet241 Před 10 měsíci

    Can anyone tell me genrator is stoped after 9 secs saying generater at rest how to fix it it says saftey on delay

  • @user-tc5xy9hn4g
    @user-tc5xy9hn4g Před 2 lety

    At my DSE 6110 running time always 0 h 0 m please help

  • @arhamrao5527
    @arhamrao5527 Před 3 lety

    When i start diesel engin generator after 3 to 4 days it becomea air lock. Whats problem

  • @mansooraziz1236
    @mansooraziz1236 Před rokem

    How increase display light

  • @wildeagle3736
    @wildeagle3736 Před 2 lety

    If you set up this genset,no more password?

  • @albertboye7057
    @albertboye7057 Před 3 lety

    People I wanted to ask if your generator starts alright,but the power did not shoot to where you need to used it,what might be the course?

  • @calluula
    @calluula Před 3 lety

    I have problem my generator shut down and message gen under frequency shud down our generator iveco generator 400 kva

  • @orlandopizarro5113
    @orlandopizarro5113 Před 8 lety

    i need key edit des7310

  • @ilkhombakhtiyorov3043
    @ilkhombakhtiyorov3043 Před 9 měsíci

    I need pin edit DSE 6120

  • @sharifuddin5200
    @sharifuddin5200 Před 4 lety +1

    Need bangla tutorial

  • @fendibaene5398
    @fendibaene5398 Před 2 lety

    Apa penyakit mensi controller tidak bisa hidup bisa di sentarte Tdk hidup tolong di jelaskan bahasa indonensia

  • @muhmmadtariq
    @muhmmadtariq Před 2 lety +1

    Sir Gen over votag gen shtdown

  • @charlieangkor8649
    @charlieangkor8649 Před 4 lety

    so there are unlabeled symbols for electric transmision pylon, a factory and a sinewave. Which of those means the power grid, the generator and the load? I think the person designing the panel was incompetent and should be fired.

  • @kienha9791
    @kienha9791 Před 2 lety

    CovidImages need to be invested more than half19

  • @DieselGeneratortraining

    Thanks #powerlearningchannel

  • @mdrana-kp3kt
    @mdrana-kp3kt Před rokem

    Nice