Cooling Load | hand calculation example | HVAC 13

Sdílet
Vložit
  • čas přidán 29. 12. 2021
  • Step by step calculation of cooling load using the cooling load temperature difference known as CLTD method.
    The calculation is done for an office building.

Komentáře • 51

  • @Dexter-v2j
    @Dexter-v2j Před 7 dny

    Thanks for sharing your knowledge. It was well discussed and easy to understand. Can you please share the CLTDs for different latitudes? Thank you.

  • @khaihuelieu5065
    @khaihuelieu5065 Před 2 lety +2

    Thank you for content, it helps my career path a lot

  • @suheladesilva2933
    @suheladesilva2933 Před 3 měsíci +1

    Thank you very much for this video.

  • @reasmeingor1962
    @reasmeingor1962 Před 2 lety +1

    Hi sir, thanks for your video.
    I have a question, regarding the factor of LED light, how many factors for it?

  • @abdelnasiryosifabdelaziz3193

    Hello sir, this video was very helpful so I have a question, why the heat load through the floor was not calculated?
    the same question for the heat load through partitions between zoon 5 and the other adjacent zoons .

  • @beardedpinoy8645
    @beardedpinoy8645 Před rokem +2

    good calculation, brother. helps alot.

  • @soisaidtomydoctor3285
    @soisaidtomydoctor3285 Před 2 lety +1

    Keep up the good work 👏

    • @AMJEngineering
      @AMJEngineering  Před 2 lety +1

      Thanks for valuable feedback. Every share helps me keep going👍🌹

  • @kylemanson3011
    @kylemanson3011 Před rokem

    what would you do if your wall doesnt match one of the given wall types?

  • @jordanwclancy
    @jordanwclancy Před 2 lety +1

    Thank you so much for this video. Could you please send me the ASHRAE table referenced at 10:14? Thank you!

  • @paysalTV
    @paysalTV Před 19 dny

    Thanks for the vids. However, where and how did you get the CLTD correction for latitude and months?

  • @joabjim
    @joabjim Před rokem

    I have the 1997 ASHRAE Fundamentals Handbook, for Laredo Area, Table 1A is on page 26.18, and Table 1B is on page 26.19. Is there an error?. Thanks

  • @ochiengfaustineododa8409
    @ochiengfaustineododa8409 Před 10 měsíci

    Hey @AMJ,,, can I get a listing of the Tables??
    The ones not in ASHRAE Handbook

  • @EngrRuuveinzei
    @EngrRuuveinzei Před 9 měsíci +1

    Hi, I hope you can read this. But how did you get a 21deg F from given 11.8 Deg C. Because if you are going to convert 11.8deg C it should be 53.24deg F.

  • @agungsantosa6020
    @agungsantosa6020 Před rokem

    How can I get CLTD value for 75mm sandwich Panel material -2 Deg Latitudes. I can't find it in the existing tables.

  • @pshtiwanabdulmajeed6731

    thnk you for excelant work simply how do i get all table pleas

  • @kartiniganesha6741
    @kartiniganesha6741 Před rokem

    Hello, your videos are very helpful. I have a question, instead of using the temperature of radiation from the sun, is it possible to apply the temperature from the fire if there is fire ?

  • @FusssionMusik
    @FusssionMusik Před 11 měsíci

    I'm still trying to figure out how is 225/1000 x 5 = 2 at 16:37 I'm definitely not getting that answer. Is this an error?
    Also where did the 3.4 btu/hr/watt come from at 18:08?

  • @faviscore2200
    @faviscore2200 Před rokem

    How can I get the ASHRAE value for UK

  • @iniatiniat3822
    @iniatiniat3822 Před 2 lety +2

    Also take us through hvac ductwork design procedures

  • @yeunghubert
    @yeunghubert Před 2 lety +2

    Hi sir. May I know that how to get the Q(total) value at 18:29 table?

  • @jorgeisaacvarelagamboa2633
    @jorgeisaacvarelagamboa2633 Před 3 měsíci

    What do I do if my wall code number in table 11 is not in the table 33A?

  • @naumanfarooq6737
    @naumanfarooq6737 Před 2 lety +2

    Kindly Can you provide all tables for 36 degree

  • @arun4846
    @arun4846 Před 2 lety +1

    👍

  • @SiberianFenek
    @SiberianFenek Před 2 lety

    Hi, thanks for the video.
    I have a question, for the roof, if we look at the R value, the higher it gets, the associated number in table 30 goes up wish means higher Cltd values.
    Whats bugs me, is the fact that with more insulation, we have more cooling load to deal with, but it seems counter intuitive. I would expect better insulation to mean less cooling.
    Am i missing something ?

    • @AMJEngineering
      @AMJEngineering  Před 2 lety

      please let me know the video timing you are referring to.

    • @SiberianFenek
      @SiberianFenek Před 2 lety

      @@AMJEngineering i was refering to 8:09 with Roof no. In table 30 and R values in table 31.
      Additionaly, what does mass location mean ? And are the R values in table 31 for the complete roof composition, because even 5.3 seems low for a northern country. If i have an R = 6.5 whats do i pick in table 31 ?

  • @abbadubenzwin5157
    @abbadubenzwin5157 Před rokem

    The computed automatic cooling system complex for big or large buildings by placing temperature sensors everywhere.. This is what calls for the possibility of studying air engineering circuits

  • @husammalquzahy
    @husammalquzahy Před rokem

    Thanks for the video... It's was great for me.. Could you please send me the tables?

  • @MohitGoklani
    @MohitGoklani Před 4 měsíci

    At timestep 18:54 ; from where this space load comes?

  • @JohnFekoloid
    @JohnFekoloid Před rokem

    8:42 Please where did you get this table from? Cannot find it in ASHRAE 1997 handbook

  • @aldrenbungay632
    @aldrenbungay632 Před rokem +1

    just want to clarify where did you get the 0.2 U-value for the wall..Thanks

    • @AMJEngineering
      @AMJEngineering  Před rokem

      This should be given for any type of wall.

    • @joao_cavalcanti
      @joao_cavalcanti Před rokem

      I am in doubt too. Type C3 >> R = 0,125 m2 k / W. It was suggested 0,88 m2 k / W (0,2 Btu / h ft2 °F. Maybe C13 (150mm High Density Concrete R=0,88 m2 K / W) could fix the numbers.

    • @rithysorm8692
      @rithysorm8692 Před 3 měsíci

      How to convert it​@@joao_cavalcanti

  • @rupomroy98
    @rupomroy98 Před rokem

    can you provide me the ashrae 1997 fundamental book?

  • @hassanqadeer725
    @hassanqadeer725 Před 2 lety +1

    correction
    11.48> Degree centigrade multiply by 1.8 and add 32 to get Fahrenheit

    • @AMJEngineering
      @AMJEngineering  Před 2 lety

      Yes you are right and thanks for your comment. I mentioned that I made this mistake in previous comments

  • @mohammadahasan9444
    @mohammadahasan9444 Před 4 měsíci +1

    Where you get u value from?

  • @mohammadahasan9444
    @mohammadahasan9444 Před 5 měsíci

    How to convert : w/m^2k to btu/hr-ft^2 -°f?

  • @luisaguilar124
    @luisaguilar124 Před 10 měsíci

    How can I calculate correctly U factor?
    Its just that Ashrae has a lot of tables for U values and I'm confused

    • @AMJEngineering
      @AMJEngineering  Před 10 měsíci

      Depends on wall and roof types. Choose the nearest ashrea composition

  • @JoseMelierSingson
    @JoseMelierSingson Před 9 měsíci

    Good day po, can i have a copy of solar cooling load for 8deg north latitude..ty

  • @faisalalabdulkarem5731

    please send me the book if passible