Hello i have a question I also use smart load on my deye 6kw inverter I put my conditions for 50% 55% for the battery and the 1000w for PV For the on condition it is doing alright (when pv is higher than 1000w and lithium battery it kicks on) but for the off condition it only kicks on when the battery is below 50% and ignores the PV condition Can you explain that to me please
It swithes On when both parameters are met. It switches off when 1 parameter is not met >1min. It swithes back on after the battery has charged & both are met again. Your geyser's kW should preferably be lower than the PV setting, or you will cycle your battery a lot!
Excellent setup on your geysers...
Hello i have a question
I also use smart load on my deye 6kw inverter
I put my conditions for 50% 55% for the battery and the 1000w for PV
For the on condition it is doing alright (when pv is higher than 1000w and lithium battery it kicks on) but for the off condition it only kicks on when the battery is below 50% and ignores the PV condition
Can you explain that to me please
It swithes On when both parameters are met.
It switches off when 1 parameter is not met >1min.
It swithes back on after the battery has charged & both are met again.
Your geyser's kW should preferably be lower than the PV setting, or you will cycle your battery a lot!