Micrologix 1100 1400 controls a Powerflex 525 over ethernet

Sdílet
Vložit
  • čas přidán 30. 09. 2014
  • This video demenstrate how to control a Powerflex 525 over Ethernet using a micrologix 1100 PLC. It was requested as a 1400 but the only availible one i had was an 1100. I hope this video helps those who need it.
    Manual literature.rockwellautomation....

Komentáře • 145

  • @PLCAutomationTraining
    @PLCAutomationTraining  Před 9 lety +31

    Did this video help you out?

    • @plcprofessor
      @plcprofessor Před 7 lety

      Where can I find the PDF that has the instruction on memory locations used with the PF525 and the 1100? I have looked through the usual suspects. Thanks...

    • @plcprofessor
      @plcprofessor Před 7 lety

      my bad...as soon as I clicked on Reply, I noticed the link in the description of your video...again, my apologies.

    • @jimmymendoza8293
      @jimmymendoza8293 Před 6 lety

      Nice video, thanks a lot!

  • @javierhenriquez6043
    @javierhenriquez6043 Před 5 lety +2

    Sir... Is it even posible a better explanation than the one you did?
    You're completely awesome! Thanks for sharing knowledge with people out there! You've saved my back today... Thanks again for all your helpfull content

  • @ecdinc2759
    @ecdinc2759 Před 6 lety +1

    Great video! For anyone having issues writing but the PLC is reading the drive status correctly - Open the N11 file, view in binary, and set bits 0 and 2 = 1 of N11:0 (as used in this video for the first MSG command). Do this for each VFD connected in the first MSG (for message timeout read/write) and it may resolve the problem.

  • @thomascerwick2993
    @thomascerwick2993 Před 6 lety +3

    Excellent Video! Well made. Was able to setup 3- 525 drives for a program that needs to be done in week. Couldn't of got it done without your video. Thanks and keep on making them.

  • @shakersfadi
    @shakersfadi Před 9 lety

    That was a great and helpful, I had a problem getting data from Power monitor 1000 to my ML 1400, I watched it yesterday and finished the job today. Thank you so much. AAAAAAAAAAA

  • @parkour267
    @parkour267 Před rokem +1

    Great video. Saved me much pain and suffering to figure this out on my own haha.

  • @nelsonsbrian
    @nelsonsbrian Před 9 lety +1

    Not a lot of information around, thanks for the tutorial!

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 9 lety

      No problem let me know if there is anything else you guys may need a hand with

  • @djmoondragon7219
    @djmoondragon7219 Před 5 lety

    Thanks for the video is excellent question can you tell me what version of rslogix 500 are you using to program the powerflex

  • @diegof.ramirez1740
    @diegof.ramirez1740 Před 7 lety

    Great video! I really appreciated it... However, I got one question and what happen if I have 2 Drives? All I need to do is change IP adress (of course), controller internal adresses and still using same PowerFlex internal adresses like N42:3, N41:0 and N41:2, right? Thanks for your time and best regards from Colombia.

  • @charliekey2979
    @charliekey2979 Před 6 lety +1

    Great project tutorial, I really appreciate your work. I have learn a lot! It will be awesome if you could make one for ControLogix (RSLogix 5000) Two thumbs up!

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 6 lety

      the bedrock house thank you for the feedback please follow this link to the video you requested. czcams.com/video/t55UbbzwL9U/video.html

  • @JackCainicela1
    @JackCainicela1 Před 9 lety

    Good tutorial, thanks for the information.
    Greetings from Perú

  • @glennlorimer1618
    @glennlorimer1618 Před 6 lety

    this is how videos should be made this is absolute brilliant thanks

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 6 lety

      Glenn Lorimer thank you sir!

    • @glennlorimer1618
      @glennlorimer1618 Před 6 lety

      you're most welcome ive got it running like a dream but im struggling to find the data table address to get the inverter to run in reverse would you wizards be able to assist me?

  • @kennethabbott3856
    @kennethabbott3856 Před rokem +1

    This was immensely helpful. Thank you.

  • @dandwyer3919
    @dandwyer3919 Před 7 lety

    Thanks!!! Saved me a lot of time.

  • @NaserNorouzi
    @NaserNorouzi Před 6 lety

    really all your training videos are useful and thank you for that

  • @TheLRBrown
    @TheLRBrown Před 5 lety

    Excellent video. I would like to be able to send Powerflex fault codes to the Micrologix. Is there a way to do this?

  • @alexjanierosa4338
    @alexjanierosa4338 Před 5 lety

    Where can you find all the N files to read and write to other parameters for the powerflex 525.

  • @MrAdamk1981
    @MrAdamk1981 Před 9 lety

    Mate fantastic info there !

  • @jcerranom
    @jcerranom Před 4 měsíci

    Great video!!
    this it apply for powerflex40 as well?

  • @gustavocruz7450
    @gustavocruz7450 Před 6 lety

    Hi, great video, congrats! so, i need to control 6 pf525 through ethernet/ip with ML1400 and panelview 800, there any problem??
    How I assure that it works correctly?, being a non-deterministic control method (according to rockwell information)?
    Regards

  • @moseslakkam
    @moseslakkam Před 7 lety

    Thank you for the video , it help me in how to do, but please explain how do i message to third party HMI module by using modbus tcp, as the HMI has got this modbus serial com RS485.

  • @SirHayk
    @SirHayk Před 6 lety

    I already commented this video, great video. Question related to sofware: I use Micro Developer Edition to write Plc code. Do you know if Micro Starter Edition will be able to open/download that PLC code? I asked many people actually, they all say , should be able to open . But i need to know for sure, Thanks

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 6 lety

      Hayk Azizbekyan I'm not sure I need to look this up sorry for the late response

  • @MICOLOGIX
    @MICOLOGIX Před 4 lety

    somebody can help me, i'm trying to communicate with a powerflex 40 using 22 Comm-e, the manual say that are the same files to flex 40 but for some reason not works

  • @ryancoe5180
    @ryancoe5180 Před 9 lety +1

    Thank you for the video. It certainly saved me some time.

  • @Carlosab04
    @Carlosab04 Před 8 lety

    Do you know if you can control a 525 with a panelview plus compact 600. Its the same ethernet configuration?, could you do a video?

  • @Carlosab04
    @Carlosab04 Před 8 lety

    This is a really good video. Thanks for share.

  • @joew4202
    @joew4202 Před 3 lety

    Do you have to use CCW to use the Powerflex with the 1100/RSL500?

  • @glennlorimer1618
    @glennlorimer1618 Před 6 lety

    ive got it running like a dream thank you greatly but im struggling to find the data table address to get the inverter to run in reverse would you wizards be able to assist me?

  • @pipoy8
    @pipoy8 Před 8 lety

    i follow exactly the same in the video but i cannot able to trigger the pf 525, im using the 1400.

  • @gregdake7356
    @gregdake7356 Před 9 lety

    Is it best practice to trigger message instructions in Logix500 such as you are? I am not being critical, I am wondering as I've had many debates over the years on the proper way to trigger multiple messages.

    • @jeremymiller9165
      @jeremymiller9165 Před 9 lety +1

      I just go with what works I have found there are better ways to save processor scan times but in these tutorials I'm not worried about the scan time but your right. I'll bring that up later about scan times.

  • @SirHayk
    @SirHayk Před 7 lety

    Thanks a lot for the video. I have question: we're testing our own hardware with Compact Logix PLC . it ( Compact Logix ) sends message using MSG . Our hardware works OK . I need to test it with Mirco 1400, but dont have it . Is it possible to say for sure, that if it (our hardware ) works OK when COMPACT Logix send MSG , then it will will ok if Micro 1400 sends MSG? What i'm trying to ask if output frame (or package) is same for Compact and Micro 1400 when they use MSG insruction? Thanks

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 7 lety

      Hayk Azizbekyan yes it should work just fine, though you are using two different software's rslogix 500 and rslogix 5000

    • @SirHayk
      @SirHayk Před 7 lety

      Thanks a lot of your response . I have question, would really appreciate you can help. , I can't figure out what to to enter in RXI file. below is the link. It says Extended Routing information File. What I have to enter in that file.? Compact Logix doesn't' ask that information. And last question: is there anything i have to enter in Send Data / Recieve Data tabs ? Thanks again for your video and response
      drive.google.com/file/d/0B3mee-O6OwfBTGs2bGZyZkJRdk0/view?usp=sharing

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 6 lety

      sorry for the delay i have not used this one before you must have RS500 pro I was using rs500 standard so i didnt have the extra tags. I will have to check on this one

  • @thiefgold0913
    @thiefgold0913 Před 9 lety

    Great Video. Have you made any video's with programming a panelview with the same setup?

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 9 lety

      MIke Wilson I have a few and am working on more. there are 2 or 3 videos uploaded to this Channel. Do you have a specific one your looking for?

    • @thiefgold0913
      @thiefgold0913 Před 9 lety

      I'm looking for a panelview/micrologix that is setup to control a VFD through numeric display or arrow keys as your speed reference. But since I watched this video I feel I have more of a grasp of what has to happen, so thanks for informative video.

  • @goku7s
    @goku7s Před 7 lety

    Hey i am using a powerflex vfd 525 to control a motor and i am using micrologix 1400 PLC, i am using a scale block to scale the value which i am getting form the VFD so at zero speed i should be getting the input as zero which i am not getting instead i am getting a value of 12000.
    can you help me with this problem?

  • @Kalleweed
    @Kalleweed Před 9 lety +1

    The more I watch your videos the more i see things clearly

  • @dpdAL
    @dpdAL Před 8 lety

    Great Video, Keep up the good work!!! Can you make a video on how to connect ML1400 via ethernet with schneider electric's atv71 and how to give a speed reference from the output of a PID block.?

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 8 lety

      I'll see what I can come up with. I'm limited on getting some equipment for every situation so I'll research this and get back to you

  • @guangyaoli6218
    @guangyaoli6218 Před 7 měsíci +1

    Boss. When I met two internet cards in plc with different ip address. Which ip address I should set up in my computer to matching? Thank you very much

  • @davidrickert4925
    @davidrickert4925 Před 7 lety

    Good video...Can you read other parameters like Amp load or KW?

  • @gulamhussainshaikh9410

    How to read the other parameters of drive such as ampere ,volts etc

  • @plcprofessor
    @plcprofessor Před 7 lety

    Very good!!!

  • @aang9112
    @aang9112 Před 9 lety

    hey! one question. How do you connect the 1100 over the ethernet and the pf 525 in the same loop, i have a 1100 with only one port ethernet,and in your loop in rslinx appears the plc and the pf525, cheers!

  • @jorgeluisrodriguezaday8581

    Excelent video, thanks!

  • @dominikpi7778
    @dominikpi7778 Před rokem +1

    Great video! Thanks!

  • @ThiagoLima85
    @ThiagoLima85 Před 8 lety +1

    Hello!
    Can I control an Ethernet/ip drive connect to other 4 drives via DSI using micrologix processor? Do you have an example!? Thanks!!

  • @tnrw30
    @tnrw30 Před 9 lety +1

    Great thanks a lot !!

  • @franciscojavierrodriguez8747

    Excellent I Would like see more videos
    thanks

  • @Vijay__JV
    @Vijay__JV Před 8 lety

    Sir you are using 20 comm e or 22 comm e and how to do for micrologix 1500

  • @petedazer3381
    @petedazer3381 Před 2 lety +1

    Very helpful, thank you.

  • @peymanmehrdadian1015
    @peymanmehrdadian1015 Před 6 měsíci +1

    It is Great. I am appreciated. It is really helpful.

  • @jedisgarage4775
    @jedisgarage4775 Před 8 měsíci +1

    I did everything that you showed but if I change B3:0/1 to 1 nothing happens... No acceleration, no frequency shown on the display on the VFD. What could have go wrong?

    • @jedisgarage4775
      @jedisgarage4775 Před 7 měsíci +1

      Just managed to sort it out. I put PLC IP instead of inverter IP... duh... :D

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 6 měsíci +1

      Im Glad you were able to get this resolved its crazy I made this video so long ago I even forgot I made it!

    • @jedisgarage4775
      @jedisgarage4775 Před 6 měsíci

      @PLCAutomationTraining Examples like this are priceless for beginners like me. Thank you very much, pal!

  • @TheLRBrown
    @TheLRBrown Před 7 lety

    How would I signal the PLC if I have an Ethernet COMM loss....if my Ethernet cable is unplugged, the drive will fault but the PLC will not know it because all of my communication is through the Ethernet cable. Is there something that changes state in the PLC if it fails to communicate?

  • @martycholewa883
    @martycholewa883 Před 4 lety

    Can you give the EXACT Reference manual number where you found the Integer file numbers to send the Drive commands to the drive?

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 4 lety

      There is a link in the description that takes you to the pdf

    • @richardsibanda1
      @richardsibanda1 Před 4 lety

      Hit me up if you still in the woods managed to tweak this to use an slc5/05 and it worked like a charm

  • @TheLRBrown
    @TheLRBrown Před 7 lety

    In the video you refer to the documentation several times. You show two separate pages from a manual of some kind. Could you give me the reference number for that manual? I can't seem to find those pages in the manual that I have. Thanks.

  • @PLCAutomationTraining

    Yes I am going to restructure and add links to them. For now click on my channel and you should see them!

  • @jorgeluisbracamontesverdug1548

    Hello, Is possible change the acceleration/deceleration time with some N file?

  • @pipoy8
    @pipoy8 Před 8 lety

    Nice tutorial video

  • @22stupididiot
    @22stupididiot Před 7 lety

    Do you know if it is possible to read the motor current through a MicroLogix1400?

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 7 lety +3

      Nicholas Lloyd b003 [Output Current], value is in N12:1, divide by 100 to get the correct value

    • @22stupididiot
      @22stupididiot Před 7 lety +1

      Cheers, I also found you can do it through CIP Generic where in MSG you use:
      This controller
      Channel: 1 (Integral)
      Communication Command: CIP Generic
      Data Table Address (Receive): N#:#
      Size in Bytes (Receive): 2
      Target Device
      Extended Routing Infor File (RIX): RIX#:#
      Service: Generic Get Attribute Single
      Class (hex): 93 (for DPI Parameter List)
      Instance (dec): 3 (for Motor Current)
      Attribute (hex): 9

  • @anilkumarsuram4917
    @anilkumarsuram4917 Před 6 lety

    this is for only single drive, what is the data table address in target device for 2nd drive ?

  • @Tassadar0078
    @Tassadar0078 Před 6 lety

    HI. Can I Use a MicroLogix 1400 and PowerFlex 527? Is the same programming method?

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 6 lety

      Pablo Valle Flores great question, the 527 used motion instructions so I need to look it up I haven't tried this one yet.

    • @Tassadar0078
      @Tassadar0078 Před 6 lety

      PLC Automation Training thank you very much. I'll be waiting your answer, because I don't have a PowerFlex 527 to do a test...

  • @thiefgold0913
    @thiefgold0913 Před 8 lety

    I have a ML1100 and powerflex 40 drive and the 22com e card communicating with each other, I copied what you illustrated in rslogix 500 program but my project isn't working as illustrated.

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 8 lety

      that's because it's a pf40 and in the video we are using a pf 525. you will have to refer to the manual for the correction message settings.

    • @thiefgold0913
      @thiefgold0913 Před 8 lety

      I did read in the manual and the settings should be the same as you illustrated when setting up the msg instruction . 42:3, 41:0, and 41:2.

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 8 lety

      +MIke Wilson I'll check this out in the morning for you

    • @thiefgold0913
      @thiefgold0913 Před 8 lety

      Ok thanks.

    • @MICOLOGIX
      @MICOLOGIX Před 4 lety

      @@thiefgold0913 did you get it? I actually have the same problem, can you help me?

  • @sunilgiri7792
    @sunilgiri7792 Před 4 lety

    Sir, Can I get drive output current from Drive 525 to micrologix 1400.

  • @thomasguarnuccio4550
    @thomasguarnuccio4550 Před 4 lety

    Can I use this method with SLC 5/05 PROCESSOR?

  • @vanderleyandrade8711
    @vanderleyandrade8711 Před 9 lety

    How can i read output current from PowerFlex 525 using ML 1100?

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 9 lety

      CIP i sent you an email with the info you needed let me know how that works for you. PG 72 of the PDF on comms

    • @MrCashbroo
      @MrCashbroo Před 9 lety

      PLC Automation Training
      Could you please send me the same info? This video has been very helpful and I have tried the CIP setup in the 20-comm-e manual but keep getting error code 45 and no data

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 9 lety

      +chris ashbrooks yes I'll go back and look and send it to you

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 9 lety

      +chris ashbrooks send email to coldbluemountainapps@gmail.com

    • @kunalthorat4701
      @kunalthorat4701 Před 5 lety

      Please send me the link to read output current from 525 using micrologix.
      Mail id: kunalthorat30@gmail.com

  • @rodrigomedina9593
    @rodrigomedina9593 Před 9 lety +1

    It's a good video, it helped me a lot ... but I have a problem with writing data to the PF525 ... I can not write any command ... but I can read the status from the drive ... maybe my problem is in the drive configuration ...

  • @kunalthorat4701
    @kunalthorat4701 Před 5 lety

    How to read output current using ethernet for micrologix 1400

  • @RaulHerrera-nw9qr
    @RaulHerrera-nw9qr Před rokem

    how can tis be done on rs logix 5000 v13 ?

  • @hasalasen
    @hasalasen Před 7 lety

    Appreciate if you could share the .rss file.

  • @GeorgeRoman
    @GeorgeRoman Před 8 lety

    What happens if we have 2 or 3 drives more, Is it the same procedure?

    • @PLCAutomationTraining
      @PLCAutomationTraining  Před 8 lety

      Yes I always separate mine in new files

    • @GeorgeRoman
      @GeorgeRoman Před 8 lety

      +PLC Automation Training. thanks for your excellent video and reply. If I want to control two drives, I can use the same parameters to read and write the drive, or there are other parameters, or i can use the same parameters to control the speed, start, stop. etc.

  • @shaijuj2380
    @shaijuj2380 Před 4 lety

    Pdf file??

  • @mikewilson4622
    @mikewilson4622 Před 4 lety

    powerflex 40 doesnt work with this setup.

    • @MICOLOGIX
      @MICOLOGIX Před 4 lety

      did you get it? I actually have the same problem, can you help me?

  • @sunilgiri7792
    @sunilgiri7792 Před 4 lety

    Please sir Help me .............