FX Training Group
FX Training Group
  • 72
  • 59 471
Using System Mode to help TAB
Use this point in CCT to be able to override multiple VAV flows at once.
zhlédnutí: 121

Video

Pressure dependent VAV using side loops in CCT
zhlédnutí 149Před 2 měsíci
This video shows how to program a pressure-dependent VAV controller using side loops in JCI CCT.
JCI CCT State Table
zhlédnutí 148Před 2 měsíci
In this video, I try to explain the state table in CCT
Discharge air pressure setpoint reset in CCT
zhlédnutí 276Před 2 měsíci
This video shows how to create a discharge air pressure setpoint reset in JCI CCT.
How to transfer your JCI CCT license to a new computer.
zhlédnutí 182Před 2 měsíci
This video will show you how to transfer your original CCT license to a new computer.
JCI Water Cooled Chiller Program, Does it Work?
zhlédnutí 305Před 3 měsíci
This video shows you what to fix in the standard CCT program for the condenser water system.
How to add Schedule to JCI controllers
zhlédnutí 194Před 4 měsíci
This video shows how to create a schedule in CCT to load into a JCI controller.
JCI Pressure Dependent VAV
zhlédnutí 322Před 5 měsíci
How to program a pressure dependent VAV in CCT.
Creating VVT program with JCI CCT
zhlédnutí 488Před 6 měsíci
Here is an easy way to create a VVT system program with JCI in CCT.
Honeywell web launcher
zhlédnutí 1,6KPřed 6 měsíci
How to install and use web launcher if you don't have a Niagara workbench.
How to fix JCI MAP Gateway Fault
zhlédnutí 256Před 8 měsíci
This video shows how to fix the MAP Gateway went it goes into fault as soon as you try to sign into it.
What a VAV is and how it works
zhlédnutí 137Před 8 měsíci
This video explains what a VAV, FPB, or terminal unit is and how it works.
Honeywell Spyder 7 Optimizer VAV Template
zhlédnutí 1,3KPřed 8 měsíci
Using the Honeywell template makes programing the new Spyder 7 VAV so easy.
Using weather service in Niagara
zhlédnutí 547Před 9 měsíci
This shows how to add the weather service and what you can do with the weather service in Niagara.
JCI SNC Part 2 the Fix
zhlédnutí 239Před 9 měsíci
JCI SNC Part 2 the Fix
Why I hate SNC controllers Part 1
zhlédnutí 267Před 9 měsíci
Why I hate SNC controllers Part 1
F4 DLK0350 JCI Display Everyone needs one of these.
zhlédnutí 465Před 10 měsíci
F4 DLK0350 JCI Display Everyone needs one of these.
Part 2 Honeywell TR50 and some Event Programing in the Optimizer
zhlédnutí 306Před 10 měsíci
Part 2 Honeywell TR50 and some Event Programing in the Optimizer
Honeywell TR50 wall sensor brought in as a BACnet device.
zhlédnutí 257Před 11 měsíci
Honeywell TR50 wall sensor brought in as a BACnet device.
Belimo Duct Sensor vs ACI/ Honeywell vs JCI Which duct sensor do you like?
zhlédnutí 226Před rokem
Belimo Duct Sensor vs ACI/ Honeywell vs JCI Which duct sensor do you like?
Honeywell Optimizer controller
zhlédnutí 1,6KPřed rokem
Honeywell Optimizer controller
How to turn the new CWCVT into a BTCVT to use in CCT
zhlédnutí 984Před rokem
How to turn the new CWCVT into a BTCVT to use in CCT
The New Johnson Controls CWCVT is out.
zhlédnutí 1,1KPřed rokem
The New Johnson Controls CWCVT is out.
Vykon Vec-10(Edge 10) controller overview.
zhlédnutí 313Před rokem
Vykon Vec-10(Edge 10) controller overview.
How to get into a JCI branch controller with FX CCT
zhlédnutí 529Před rokem
How to get into a JCI branch controller with FX CCT
JCI CCT Troubleshooting
zhlédnutí 476Před rokem
JCI CCT Troubleshooting
LeadLag pumps with monthly rotate
zhlédnutí 156Před rokem
LeadLag pumps with monthly rotate
Home made Multizone RTU programing
zhlédnutí 102Před rokem
Home made Multizone RTU programing
Backing up JCI controller programing
zhlédnutí 194Před rokem
Backing up JCI controller programing
Re-binding Graphics when replacing controllers
zhlédnutí 701Před rokem
Re-binding Graphics when replacing controllers

Komentáře

  • @hvactech77
    @hvactech77 Před 22 dny

    Is there a way to do a temporary occupied for cleaning people to push a button on this thermostat?

  • @vengatesanpakkirisamy7257

    Excellence of teaching

  • @reggiek3186
    @reggiek3186 Před 27 dny

    Thanks

  • @jorgehumbertohernandez4060

    Es un buen tip sensei

  • @Shutyourjibbs
    @Shutyourjibbs Před měsícem

    You mentioned these slides are from a class you teach. Do you still teach the class, and if so can I get more information? Thanks.

  • @TheCrowder3
    @TheCrowder3 Před 2 měsíci

    Great video!

  • @Drak7282
    @Drak7282 Před 2 měsíci

    My xml won’t convert to a module file, any tips?

  • @Tormod-by4ku
    @Tormod-by4ku Před 2 měsíci

    We had a crash at main server for the BAS, will it be possible to find the old lisences somewhere or can it be provided from JCI. This is just perfect for us. We are not getting CCT up and running at the replacement computer.

  • @twobarb
    @twobarb Před 2 měsíci

    Why not use the G36 DAP reset module that already exists?

    • @stevenhurst1631
      @stevenhurst1631 Před 2 měsíci

      Because that program uses a span block and does not meet the sequence requirements

  • @rightconditions2789
    @rightconditions2789 Před 3 měsíci

    Where did you buy it?

  • @vikram5777
    @vikram5777 Před 3 měsíci

    How can I get the CCT & SCT Software? Can you provide me the application?

    • @stevenhurst1631
      @stevenhurst1631 Před 3 měsíci

      You will need to reach out to your local JCI BAS distributor in your area.

  • @salvadorluperon9002
    @salvadorluperon9002 Před 3 měsíci

    Muy

  • @MohdIrfan-mt6ir
    @MohdIrfan-mt6ir Před 3 měsíci

    Hi i have issue on uploading the program. My controller in the default state.

  • @woodysgeekchannel2204
    @woodysgeekchannel2204 Před 4 měsíci

    Awesome videos! Keep up the good work. Much appreciated

  • @andyandy4459
    @andyandy4459 Před 4 měsíci

    We just had a training seminar on this line, my supervisor is really excited about it. Sounds good, we'll see how it performs in the wild

  • @PhilXC_
    @PhilXC_ Před 4 měsíci

    Can I used the latest windows software or it has to be Windows 10? I'm asking because I'm buying a computer specifically for CCT Training. Appreciate the videos.

    • @stevenhurst1631
      @stevenhurst1631 Před 4 měsíci

      The newest version of CCT (16) supports windows 11

  • @ericaragon6801
    @ericaragon6801 Před 4 měsíci

    How does the controller know the real time? Is that based on your computers local time once you download?

    • @stevenhurst1631
      @stevenhurst1631 Před 4 měsíci

      Yes, and I have tested it being powered off for two weeks and when I apply power back to it, the trends report the correct time without hooking it up to a computer

  • @a12gos
    @a12gos Před 5 měsíci

    All other modules will be useless. Id rather make a custom program for this application. Also id use PID and Preproc for the control.

  • @buxt25
    @buxt25 Před 5 měsíci

    Thanks for the video! Where do you get the template download?

    • @stevenhurst1631
      @stevenhurst1631 Před 5 měsíci

      If you are a signed up Honeywell customer, you can find it on the Honeywell Buildings Forum if not you will need to ask your controls distributor for it.

  • @godzilladestroyscities1757
    @godzilladestroyscities1757 Před 5 měsíci

    I work for JCI and they have never offered me training like this. This is great.

  • @skyheatingair
    @skyheatingair Před 5 měsíci

    Above & beyond , Thank you so much for the Great Video 👍

  • @skyheatingair
    @skyheatingair Před 6 měsíci

    best teacher ever , thank you

  • @erikla_zcar4060
    @erikla_zcar4060 Před 6 měsíci

    nobody likes JCI 😂

  • @erikla_zcar4060
    @erikla_zcar4060 Před 6 měsíci

    videos a life saver!!!

  • @jeffyoung7987
    @jeffyoung7987 Před 6 měsíci

    Hate to break it to ya, but all of that is already there even without web launcher...

  • @skyheatingair
    @skyheatingair Před 6 měsíci

    love your Video Thank you , HAPPY NEW YEAR 🎉

  • @muhdfaris9497
    @muhdfaris9497 Před 8 měsíci

    How about other country like Malaysia / indonesia?

  • @GTStuning-
    @GTStuning- Před 8 měsíci

    Is bypass when someone does an operator override on an output?

  • @Interventor-xn5bs
    @Interventor-xn5bs Před 8 měsíci

    I did not see any programming language....

  • @stevenhurst1631
    @stevenhurst1631 Před 8 měsíci

    No this is a free service, at least here in the United States because most of the weather providers are government funded.

  • @davetroy294
    @davetroy294 Před 8 měsíci

    Do you need to pay to connect to the weather services that’s in the pallet as a subscription

  • @user-magnatik
    @user-magnatik Před 9 měsíci

    круто молодец. удачи. покажи готовые решения на этом контроллере.

  • @abdullahsavas9
    @abdullahsavas9 Před 9 měsíci

    You make everybody go go sleep, shame on you, drunk man

  • @twobarb
    @twobarb Před 9 měsíci

    I never can understand the hatred for the SNC I use the heck out of them as I can get way more bang for my buck them an CGM plus an expansion module and a display. From what I've seen 99% of the problems people complain about are PICNIC errors. Had a long talk with JCI at CBC23 and found out the next release of SCT will have a classic mode that will allow you to upload directly from CCT the way you can with an NCE.The NCE was basically an NAE with a controller slapped on the FC bus and housed in the same package, unfortunately when they designed the SNC they made it one unit and it kind made a mess of things.

  • @MohdIrfan-mt6ir
    @MohdIrfan-mt6ir Před 9 měsíci

    Hi Great video there on SNC controllers, im using the same model SNC25151... i already manage to import the CAF file on SCT but when i download the caf file into the SNC the downloading process stuck at 25%.. Do came across the same issue as mine?

    • @stevenhurst1631
      @stevenhurst1631 Před 9 měsíci

      Unfortunately yes, I can usually get it to work 1 out of every 20 times are so. Make sure your firewall is off and disable all other Ethernet ports that you are not using for the download like the wifi, this usually helps. If it keeps failing restart the whole computer then try syncing first.

    • @MohdIrfan-mt6ir
      @MohdIrfan-mt6ir Před 9 měsíci

      Thank you so much for the advise. Will try it out and update here.

  • @MohdIrfan-mt6ir
    @MohdIrfan-mt6ir Před 9 měsíci

    Hi great video man! Can you share with me how do i download the caf file to the SNC via SCT? Do i need to create controller template first? Really need help on this.

    • @stevenhurst1631
      @stevenhurst1631 Před 9 měsíci

      I really hate SNC controllers but here is how it should be done czcams.com/video/vdTGSdF1SmU/video.html but as you see in the video I get nothing but problems out of those controllers.

  • @mylesxd562
    @mylesxd562 Před 10 měsíci

    Thank you this worked!

  • @finretard69
    @finretard69 Před 10 měsíci

    Question: when I connected my 2nd wifi N card/dongle to my laptop I can connect to CCT and use it fine. I connected my laptop wifi card to a know good Wi-Fi signal to connect to the Internet(so I can use team viewer) at the same time but I don't have Internet access now.(and won't until I disconnect from the map wifi) Is there something special I would need to set up as well to be on both networks at the same time?

  • @Buggerhey
    @Buggerhey Před 10 měsíci

    Can you flash the cwcvt with WLED? 😀

  • @yayaquilts5846
    @yayaquilts5846 Před 10 měsíci

    Question about the hardware. I’ve successfully upgraded the caf file to replace an FEC2611 with a CGM9090 and downloaded the controller. The UIs aren’t reading (DA-T sensor) at all. Jumpers are all set to default. Am I missing a step?

    • @stevenhurst1631
      @stevenhurst1631 Před 10 měsíci

      First step is to check the wiring, second step look at what type of sensor it is and make sure it is programed for that type of sensor, in configure mode right click on the DA-T input and modify signal to what ever type sensor it is. Make sure you are not using firmware 8 which is 10.4 this is a known bug for that firmware. If all that doesn't work move the DA-T to a new input and see if it works, you could just have a controller with a bad input.

    • @yayaquilts5846
      @yayaquilts5846 Před 10 měsíci

      @@stevenhurst1631 You’re my hero! Upgraded to 10.5 and downloaded and it worked like magic. Thank you!

  • @PaulCKay
    @PaulCKay Před 11 měsíci

    These just got installed in my apartment building. They have the minimum temperature set to 72.5 degrees and it's just way too hot for the climate I'm in. Do you know if there's a way to unlock/bypass this limiter and set it to a lower temp? It would be a huge help

    • @stevenhurst1631
      @stevenhurst1631 Před 10 měsíci

      unfortunately you would either need a MAP Gateway and or the software to make that kind of change, you can't do it by the stat, but if you invest in a small reading lamp and point in near the stat ( not too close that it could catch on fire) you might be able to trick it to make it colder.

  • @arjunno
    @arjunno Před 11 měsíci

    How to add occupancy schedules

  • @jlimg5215
    @jlimg5215 Před 11 měsíci

    i would like to purchase this software with the license who i need to contact?

  • @garymatthews6309
    @garymatthews6309 Před rokem

    How do i login to the platform under myhost?

  • @garymatthews6309
    @garymatthews6309 Před rokem

    How do I log into the platform under the host ?? What is the user pass?

    • @stevenhurst1631
      @stevenhurst1631 Před rokem

      on your workbench or supervisor it will be the windows user name and password, if it is a Jace, it is whatever the user set it at.

  • @GomSeiUS99
    @GomSeiUS99 Před rokem

    Mapas

  • @TheQuelle
    @TheQuelle Před rokem

    Thank you

  • @skyheatingair
    @skyheatingair Před rokem

    Great video , great teachers, wealth of knowledge , God Gift to Humanity. THANK YOU .

  • @skyheatingair
    @skyheatingair Před rokem

    Hi , I'm one of your subscibeder , I'm working on PCG2611 controller currently had RTU program running on it , I would like to to replace the program to central heating/ Boiler , I'm able to discover the controller thru map getaway or old Bluetooth , I can read and write to it I can downloads the same program to it and check mark the main and the Boot if I want too ,, the RTU program on pcg2611 main 6.2 Boot 6.2 ,,,my ruining software CCT 15.0 release mode 10.2 firmware 6.2, so far so good But when I build boiler program and try to push it / downloads to the device ,,thru the commission summery its sees the PCG2611 when I hit next it will (CTT) start thinking then massage popup says ( please select a different device or different connection point to access this devices ) only when I try to changed the program but if I want to keep the same program and add to it such sensor or logic the downloads to it back will take it ?? would you pls advice me and let me know why , as usual I appreciate all your help .THANK YOU . Abe

    • @stevenhurst1631
      @stevenhurst1631 Před rokem

      Sounds like you have some other issue going on. Check out this video to see if any of these solutions to common problems fixes your issue. czcams.com/video/9_6jeDpoIu0/video.html

    • @skyheatingair
      @skyheatingair Před rokem

      @@stevenhurst1631 Thank you so much Steven, your Great video link help me allots and solve all the problem's I'm facing ,,, Much appreciate ,,😀

  • @ninjatrader4976
    @ninjatrader4976 Před rokem

    If you have a customer that still has relations with JCI they can purchase a license for you. Tell them to get you TL-BUNDLEMS-0. My local JCI won't sell it to me since Im a threat to business. Little do they know there are ways around it.