How to install grounding according to standards. Carelessness can have fatal consequences

Sdílet
Vložit
  • čas přidán 3. 03. 2021
  • The grounding system or better known as grounding is a very important component in electrical installations, because grounding functions as protection when leakage current occurs in equipment, so that humans who touch the equipment will be safe from electric shock.
    In accordance with the requirements of PUIL (General Electrical Installation Regulations), the grounding resistance value must be less than or equal to 5 Ohms and anything above this value cannot be tolerated.
    In this video, we will learn how to install grounding and continue with the measurement process using an Earth Tester measuring tool.
    Hopefully this video is useful for creative friends who are learning about electrical systems. If you have questions or input, please write them in the comments column. Thank you for your support and support for the Siroedhie Kreasi channel...
    Come on, let's watch this video...let's go kemon
    #Grounding #PUIL #EarthTester #GroundingResistance #siroedhiekreasi

Komentáře • 853

  • @bejegriezman7326
    @bejegriezman7326 Před 2 lety

    Semangat om meski telat nonton vedeo ny tapi sangat bermanfaat ilmu ny buat saya

  • @noerhadi8797
    @noerhadi8797 Před 2 lety +5

    Sukses dan berkah selalu untuk bapak dan keluarga
    Karna sudah baik hati berbagi wawasannya

  • @fajartambunan3221
    @fajartambunan3221 Před 2 lety +4

    Ma Sha Allah Tabarakallah...
    Semoga Ilmu Yang Disebarkan Menjadi Sedekah Jariyah 😇😇

  • @abdussalamabdussalam1638

    banyak sekali ilmu di channel ini, terima kasih sudah berbagi. semoga abang sehat selalu

  • @dedigaly3352
    @dedigaly3352 Před rokem

    Ok maseh saya like mantap

  • @abimunandar5583
    @abimunandar5583 Před 2 lety +1

    Alhamdulillah.. Trimakasih pak info nya 🙏

  • @iwayanpujawan7267
    @iwayanpujawan7267 Před rokem

    Terus berbagi bang🙏 saya tertarik belajar tapi masih awam🙏

  • @onedeeProject
    @onedeeProject Před 3 lety

    Ikut nyimak boss selamat sukses

  • @shundhem_electrick
    @shundhem_electrick Před 2 lety +1

    Luar biasa, terimakasih ilmunya.

  • @majestyteknik7723
    @majestyteknik7723 Před 6 měsíci

    Pekerjaan yg perlu perhitungan matang.... 👍👍👍

  • @rudisamijo
    @rudisamijo Před 2 lety +1

    Terimakasih Ilmu nya bos, semoga menjadi amal jariah👍👍

  • @aangjunaidi5914
    @aangjunaidi5914 Před 2 lety

    ManTap ,jd pengen belajr kelistrikan dr nol...sukses bang

  • @rafifahaura4547
    @rafifahaura4547 Před 9 měsíci

    Alhamdulillah, semoga sukses dan dimudahkan urusannya

  • @user-fm2zf4nl9r
    @user-fm2zf4nl9r Před 4 měsíci

    Trmksh pak utk ilmunya.

  • @vitaldearaujo5171
    @vitaldearaujo5171 Před 6 měsíci

    mkasih banyak bang atas berbaginya ilmu

  • @anakpetani_7791
    @anakpetani_7791 Před 2 lety

    Terimakasih ilmunya sukses selalu

  • @didimaulanamahulauw3613

    Mantapp sukses n sehat² trus tim nya 🙏🏻

  • @rulgempargemilangsago963

    Mantap ..ilmunya ..boss

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety +1

      terima kasih boss...🙏 saya juga sedang belajar. mohon saran dan masukannya

  • @aryanuramdiansyah8247
    @aryanuramdiansyah8247 Před 2 lety

    Baru tau,terimakasih atas ilmunya pak.

  • @WillemLuntungan
    @WillemLuntungan Před 2 lety

    Mantap ground 👍👍

  • @lingkuppetarung6415
    @lingkuppetarung6415 Před 2 lety

    terimakasi tas ilmu yg di bagikan

  • @agushapiludin6415
    @agushapiludin6415 Před 11 měsíci

    Terus berkarya bang,semangat.... 💪

  • @listrikoke2885
    @listrikoke2885 Před 2 lety

    Terimakasih bg ilmu nya🙏🙏

  • @wantograb8108
    @wantograb8108 Před 2 lety +1

    cukup jelas

  • @AdeAprilockers
    @AdeAprilockers Před 2 lety

    Terima kasih pak.... Semoga jadi amal jariyah pak..🙏

  • @kembangtelonproduction9583

    Setelah lihat video ini saya berhasil buat sendiri dibwh 5 ohm. Sudah saya videokan juga, ternyata mudah. Terima kasih...

  • @adityabaladewa3966
    @adityabaladewa3966 Před 3 lety

    Nongol diberanda terlihat menarik. Auto subret pak.

  • @prismatech_ind
    @prismatech_ind Před 9 měsíci

    Terimakasih mantap ilmunya pak

  • @f.oetomo4573
    @f.oetomo4573 Před 2 lety

    Terima kasih infonya.

  • @rizalmaulana8632
    @rizalmaulana8632 Před 2 lety

    Mantap pak

  • @sukasuka728
    @sukasuka728 Před 2 lety

    Mantap ilmunya pak, saya subscribe 👍

  • @ereniyegah4766
    @ereniyegah4766 Před rokem

    terima kasih pak videonya

  • @depanbelakang5550
    @depanbelakang5550 Před 3 lety

    Mantap master

  • @TUTORIALLISTRIK303
    @TUTORIALLISTRIK303 Před 2 lety

    Keren Bossku salam kenal🙏

  • @herywaluyo1074
    @herywaluyo1074 Před rokem

    Mungkin yg dimaksut om dibawah itu ..untuk groung panel besar
    Memang lebih kecil nilai omh nya lebih bagus

  • @Achenx-bo7rs
    @Achenx-bo7rs Před 10 měsíci

    👍💪Terima kasih

  • @omahngareptebu
    @omahngareptebu Před 2 lety

    di bantu sama air uenak bosss. g perlu di pantek2 gitu😅

  • @manoeng
    @manoeng Před rokem

    Sangat Bermanfaat....Subscribe Dulu😁

  • @fajarfajar4188
    @fajarfajar4188 Před 3 lety

    Sangat membantu..
    Sy ingin pasang tp blm tau dgn siapa yg ahli

  • @syamsultvchannel8421
    @syamsultvchannel8421 Před rokem +1

    😁😁😁😁😁pakailah mesin hammerjack untuk masukkan earth chamber.nya agar tak payah pukul guna hammer. .cable harus min.8mm.jangan kecil.dan earth yg masuk dalam sekurang2nya 4x joint

  • @D_K
    @D_K Před 3 lety

    Selamat siang kak

  • @dirojo
    @dirojo Před 3 lety +1

    berkelas tutorial singkatnya om. thnks.

  • @ngatnomas8749
    @ngatnomas8749 Před rokem +1

    Ikut nyimak.. semoga ilmu yang bapak berikan bisa menjadi amal jariyah ya Pak..

    • @siroedhiekreasi
      @siroedhiekreasi  Před rokem

      Amin ...

    • @robotpenghancurjohe3325
      @robotpenghancurjohe3325 Před rokem

      @@siroedhiekreasi mas info rod yg ditanam kalo gak ada yang murni tembaga gimana sama kabelnya itu hitam tipe apa ya ?

    • @siroedhiekreasi
      @siroedhiekreasi  Před rokem

      @@robotpenghancurjohe3325 kabel yg hitam bisa pakai jenis kabel bc mas

    • @robotpenghancurjohe3325
      @robotpenghancurjohe3325 Před rokem

      @@siroedhiekreasi mas kalo road gak murni tembaga gimana ya, saya si yakin bisa, mohon kalo ada waktu di jelaskan mas, saya suka belajar

    • @siroedhiekreasi
      @siroedhiekreasi  Před rokem +1

      @@robotpenghancurjohe3325 bisa sih mas, tapi nilai resistansinya lumayan besar dan membutuhkan elektroda yg lumayan bnayak untuk mendapatkan nilai resistansi seperti yg dipersyaratkan oleh PUIL. disamping itu, kalau tidk menggunakan tembaga murni akan rawat berkarat

  • @gilanggm8413
    @gilanggm8413 Před 2 lety

    sangat bermanfaat ilmunya

  • @Bang_Din
    @Bang_Din Před 2 lety +1

    Saya pernah dapat grounding murni,dibawah 1ohm,pemiliknya sangat puas,saya yg kerja jg sangat senang melihatnya😁

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety +1

      wah...mantap nih. saya sendiri belum pernah dapat di bawah 1 ohm Pak

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety

      kalau boleh tau, berapa batang grounding rod yg digunakan Pak ? terima kasih

    • @adiadisupriyadi5045
      @adiadisupriyadi5045 Před rokem

      Chanek abang ngebahas soal praktek teknik grounding juga bang? Mau lihat dong saya!

  • @elektricalchannel9784
    @elektricalchannel9784 Před 2 lety

    Mantap

  • @iblesbosuok
    @iblesbosuok Před 2 lety

    Saya dulu pasang panel distribusi 11kVA fasa tunggal, ardenya bela-belain membor tanah sedalam 12 meter agar mencapai air tanah. Penghantar pakai BC-35 dimasukkan ke pipa kasing bor tanah mentok ke dasar.
    Itupun cuma dapat resistansi 1,6Ω.
    Salam genimili

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety

      sangat mantap tuh Pak, dapat 1,6 ohm. terima kasih sharingnya 🙏

  • @abdurrachmanabdurrachman2244

    Assallamu'alaikum..Saya sangat suka dengan deretan videonya, sangat tertata dan penuh pemahaman, teori dan praktenya sama. 🙏🙏🙏Maaf sebelumnya saya masih belajar dan mau menanyakan ke bapak, kapan bisa berbagi tentang video baru mengenai rangkain panel khusus HVAC beserta diagramnya terima kasih .Wassalamu'alaikum Wr. Wb.

    • @siroedhiekreasi
      @siroedhiekreasi  Před rokem

      Waalaikumussalam. terima kasih Pak, saya juga masih belajar. untuk rangakaian panel listrik 3 phase saya sudah buatkan tutorialnya. saya buat dalam 4 episode. bila berkenan bisa Bapak cek di playlist kelistrikan 🙏. ini salah satu contohnya czcams.com/video/XzMbywffLzM/video.html

    • @wawansetiono6529
      @wawansetiono6529 Před 7 měsíci

      ​@@siroedhiekreasiBang saya ngak punya alat earth tester. Apakah bahaya kalau tegangan tidak sesuai

    • @siroedhiekreasi
      @siroedhiekreasi  Před 7 měsíci

      @wawansetiono6529 bila nilai resistansi grounding ridak sesuai, akan sangat berbahaya saat terjadi gangguan arus bocor Pak. manusia yg menyentuh leralatan bisa kesetrum

    • @wawansetiono6529
      @wawansetiono6529 Před 7 měsíci +1

      @@siroedhiekreasi ok bang makasih🙏

    • @siroedhiekreasi
      @siroedhiekreasi  Před 7 měsíci

      @wawansetiono6529 sama sama bang

  • @IsaruddinIsar
    @IsaruddinIsar Před rokem

    Pak, bila berkenan tolong buatkan tutorial cara menurunkan nilai resistansi pentanahan bila nilainya lebih besar dari 5 ohm. terima kasih atas responnya

    • @siroedhiekreasi
      @siroedhiekreasi  Před rokem

      baik, terima kasih. insya Allah kita buatkan di lain waktu dan kesempatan 🙏

  • @farchanzulianto92
    @farchanzulianto92 Před 11 měsíci

    Waktu tanam groundingnya sambil dialiri air biar tanah lebih empuk kayaknya jadi mudah mukulnya

  • @budiawan1784
    @budiawan1784 Před rokem +2

    Terimakasih, sdh menyimak dan menyisakan beberapa pertanyaan:
    1. Rod memakai solid brass?
    2. Untuk daya 900-1.200, pakai Rod diameter berapa dan panjang minimal berapa?
    3. Setelah rod terkubur.... Apa yang harus dilakukan jika HASIL PENGUKURAN lebih besar dari 5 ohm?

    • @siroedhiekreasi
      @siroedhiekreasi  Před rokem +1

      jika lebih besar dari 5 ohm, bisa kita pasang elektroda berikutnya dihubung paralel, agar tahanannya menjadi lebih kecil. mengenai panjangnya relatif, tergantung dari karakter tanah, bisa menngunakan diameter 16 mm²

    • @budiawan1784
      @budiawan1784 Před rokem +1

      @@siroedhiekreasi terimakasih.
      Saya "pemakai" PLN pakai meteran lama (pakai dulu...bayar blakangan) daya 900, belum ada grounding dan mmg mau grounding; mumpung ada sdkt rejeki.

    • @siroedhiekreasi
      @siroedhiekreasi  Před rokem +1

      @@budiawan1784 baik Pak, grounding terkadang sering diabaikan. tapi masalah keselamatan adalah hal yg sangat perlu kita perhatikan. 🙏

  • @jameskaligis6976
    @jameskaligis6976 Před 2 lety

    Thanks

  • @fandiartitani9860
    @fandiartitani9860 Před 2 lety

    Bang saran biar lebih cepat pake humerr drill yang besar bang...

  • @darsilmane6934
    @darsilmane6934 Před rokem

    biasanya saya pasang coper roadnya. tanah di bor. gak di pukul make hammer.

  • @sahrawioc629
    @sahrawioc629 Před 2 lety +2

    Kenapa harus pakai yang panjang arde nya, apakah gak sebaiknya di paralel arde nya biar semakin kecil tahanan grounding nya

  • @hartonolubis1559
    @hartonolubis1559 Před 3 lety

    Mak.. Ngeri kali pak.. kebayang kalo tu palu lepas di tangan.. wkwkwkwkwkw...

  • @madegusti2402
    @madegusti2402 Před 2 lety

    Bekerja tanpa prosedur keselamatan kerja. Csra kerja yg sangat High risk

  • @budiwiro8487
    @budiwiro8487 Před 2 lety

    Maaf ,,,klo pembuatan grounding banyak caranya,,yg sy sarankan cari lokasi disekitar gedung yg tanahnya lembab lebih bagus yg ber air.Klo di area yg tandus /kering tanahnya keras ada bahan campuran yg digunakan spy tanahnya lembab dan lembek, maaf gak sy sebut bahannya.Utk mencapai nilai 0, sebetulnya mudah tp banyak yg gak ngerti caranya,,grounding petirpun sama,,nilai yg bagus dibawah 0, klo hanya sekedar syarat ada grounding gampang aja ,,,pake kabel BC 25,/16, jg bisa

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety

      Alhamdulillah...terima kasih sharing ilmu dan pengalamannya Pak. Sangat mencerahkan 🙏

    • @rahmatpkytimur4880
      @rahmatpkytimur4880 Před 2 lety

      Jadi gmna caranya mas utk dpt tahanan di bawah 5 ohm..bisa minta masukan nya
      Rencana nya saya mau pasang root 2 titik Kedalaman 8 meter pake bc 10 mm ..apakah ada cara yg lebih efektif 🙏

    • @manoeng
      @manoeng Před rokem

      @@rahmatpkytimur4880 Gunakan Bahan Semen Grounding...Bisa Bentonite atau Bahan Lainnya.

  • @zulkarnaintan8794
    @zulkarnaintan8794 Před 2 lety +1

    Jangan pakai Tang buat kencangin bautnya. Pakai kinci Ring

    • @muhammadsukma9199
      @muhammadsukma9199 Před rokem

      Kumci ring ga bisa masuk itu kalo lewat bawah enak nya pake kunci pas

  • @matyie609
    @matyie609 Před 7 měsíci

    Kalau kt malaysia pakai drill hammer saja.. xperlu letih pakai tukul😂

    • @siroedhiekreasi
      @siroedhiekreasi  Před 7 měsíci

      siap pak, kebetulan saya belum punya alatnya 😂

  • @gummi4977
    @gummi4977 Před 2 lety +5

    Terima kasih info nya, pak. Sangat menarik.
    Sekalian mau bertanya:
    1. Untuk di daerah perumahan yg lagi dibangun, dimana baiknya ground root tembaga nya dipasang? Karena rumah berdempetan, apa bisa ditaruh di bawah lantai rumah sebelum benar" di pasang keramik?
    2. Berapa biaya pemasangan atau jasa pemasangan grounding ini?
    3. kalau tidak punya alat ukur yg bapak pakai, baiknya dipasang berapa buah lagi tambahan batang tembaga nya pak buat antisipasi mencapai < 5 ohm ?

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety +3

      1. bisa Pak, atau kalau mau hemat dibuat satu ground root untuk dua rumah juga bisa.
      2. biaya pemasangan bervariasi Pak, mulai 2 s.d 3 jt. semakin kecil nilai resistansi, semakin mahal biayanya
      3. sebaiknya menggunakan alat ukur Pak, karena tanpa alat ukur kita tidak bisa mengetahui resistansi yg sebenarnya 🙏

    • @gummi4977
      @gummi4977 Před 2 lety

      @@siroedhiekreasi wah begitu ya, kira" yg ahli buat urusan grounding itu tukang apa ya pak namanya?

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety +1

      @@gummi4977 sebenarnya gak perlu yg benar² ahli Pak 🙏😀. pasang sendiri juga bisa, gampang banget caranya. lebih kurang caranya seperti yg ada dalam video ini. tapi sebaiknya diukur Pak 🙏

    • @gummi4977
      @gummi4977 Před 2 lety

      @@siroedhiekreasi Ndak punya mesin tes nya pak hehe
      Terima kasih banyak pak atas insight nya, semoga barokah 🙏

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety

      @@gummi4977 amin... 🙏

  • @capt.hasmangbinbatjo6825

    Pak mau tanya klau pasang grounding dari kwh pln ke tanah dan yang ke instalasi hanya 2 kabel saja netral dan phase.apakah itu aman.terima kasih by Hasmang

  • @glidikglidik2679
    @glidikglidik2679 Před 2 dny

    Apa tidak di bor dulu lebih dalam lebih bagus dan memakai bc 6 mm atau yg lebih besar🙏

  • @AlgojoBuzzer
    @AlgojoBuzzer Před 2 lety +2

    Kenapa rata² Meter an listrik PLN tidak menerapkan fungsi ground???
    Apakah mereka tidak mengikuti SOP

  • @user-wb5zp3xr2y
    @user-wb5zp3xr2y Před rokem

    😊

  • @denz9282
    @denz9282 Před 2 lety +1

    ijin bang bertanya mana lbh baik penggunaan stick rod (dalam cuma 3meter sprti abang diatas ) atau tombak splitzen dg kabel BC 50mm2 dg kedalmaan 6meter?

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety +2

      ada banyak model pentanahan Pak, intinya adalah nilai resistansi pentanahan harus memenuhi standar PUIL yaitu lebih kecil atau sama dengan 5 Ohm. Grounding yg paling baik adalah yang nilainya mendekati 0 ohm karena lebih cepat menyalurkan arus gangguan ke bumi. 🙏

  • @anhito
    @anhito Před 2 lety +4

    1. Sebaiknya Pakai kabel ground nya atau nyaf?
    2. Untuk pemasangan ground listrik 1 phase dan penangkal petir sebaiknya dipisah jarak nya berapa jauh

    • @keretanafaz1135
      @keretanafaz1135 Před rokem

      brapa min ukuran kabel NYAF ke grounding, pipa tembaga berapa ukuran ? dan kedalaman minimal brapa ?

  • @MadiMubarokah
    @MadiMubarokah Před 3 lety +2

    Masyaallah, sangat bermanfaat buat sy yang belum paham masalah Grounding. Sy mau bertanya pak, solusi untuk kami yg terkadang punya alat2 komputer yg rentan terhadap gangguan listrik karena tidak adanya grounding bagaimana ya? Seperti grounding sederhana begitu. Karena sy sering instalasi live streaming pakai laptop kemudian kami dapati seluruh perangkat kami teraliri listrik yang bagian besinya, pernah sy coba buat grounding sederhana dgn cara tanem paku 1 inci ke tanah dan di sambung ke ground stop kontak hasilnya tetap teraliri listrik tapi tidak separah tanpa grounding sederhana tersebut

    • @siroedhiekreasi
      @siroedhiekreasi  Před 3 lety +1

      kalau seperti itu kondisinya, kemungkinan nilai resistansi pentanahan nya masih tinggi Pak. Belum seperti yg dipersyaratkan oleh PUIL, yaitu lebih kecil atau sama dengan 5 Ohm. Solusi yg bisa saya tawarkan adalah elektroda pentanahannya harus ditambah, dan ditanam agak dalam, seperti yg terlihat dalam video, elektroda saya tanam dengan kedalaman lebih kurang 3 meter. Elektroda pentanhan biasa di sebut juga dwngan ground root bisa Bapak beli di toko perlengkapan listrik. Selamat mencoba, semoga berhasil ya Pak 🙏

    • @siroedhiekreasi
      @siroedhiekreasi  Před 3 lety

      paku 1 inchi belum memadai Pak, masih terlalu dangkal dan bahannya tidak terbuat dari tembaga. 🙏

    • @MadiMubarokah
      @MadiMubarokah Před 3 lety

      Begitu ya pak, terima kasih atas jawabannya pak. Untuk harganya berapa ya pak? Tembaga gorunding nya? Kemudian cara buat mengukur tingkat ohm selain pakai alat bapak yg ada di video itu apa ya kira2?

    • @siroedhiekreasi
      @siroedhiekreasi  Před 3 lety

      @@MadiMubarokah terima kasih kembali Pak, untuk harga memang lumayan mahal Pak, di daerah saya (aceh) harga per batang di kisaran 800 k. Untuk mengukur tahanan pentanahannya menggunakan earth tester, kalau gak punya alat ukur memang agak susah sedikit Pak. Tapi bisa kita gunakan cara manual seperti yg sudah Bapak lakukan, setelah elektroda terpasang dan dihubungkan ke sistem, bisa kita lakukan uji sentuh. Kalau tegangan sentuh masih terasa besar, berarti nilai resistansi pentanahannya masih belum memadai 🙏

    • @siroedhiekreasi
      @siroedhiekreasi  Před 3 lety +1

      kalau nilai resistansi pentanahannya masih besar (belum memenuhi persyaratan) bisa kita buat dengan metode paralel Pak. Dua buah elektroda atau lebih, kita tanam dalam hubungan paralel

  • @omahngareptebu
    @omahngareptebu Před 2 lety

    konek nya di bilitkan kawat nya bos, lalu di klem😂

  • @BPMChannel123
    @BPMChannel123 Před 10 měsíci

    Gak Fatal kok ....santai saja

  • @dkredy
    @dkredy Před 6 měsíci

    Terimakasih sharingnya, ingin bertanya:
    Apakah grounding tidak diperlukan bak control?
    Untuk kabel dr Rod ke MDP sebaiknya menggunakan kabel BC atau NYA?

    • @siroedhiekreasi
      @siroedhiekreasi  Před 5 měsíci

      bok control idealnya diperlukan pak, tapi tergantung sikon juga. biasanya menggunakan kabel bc pak tapi yg menjadi pedoman adalah diameter penghantarnya, semakin besar akan semakin baik

  • @jhoniirawan2172
    @jhoniirawan2172 Před 2 lety +5

    Oya pak satu lagi,,kebanyakan yg saya lihat dr instalasi listrik rumahan khususnya di pedesaan. Kebanyakan grounding gk terpakai,, jd groundingnya cuma sebatas dr tanah ke box sekring(artinya sia-sia) . Keluar dr box cuma kabel fasa dan netral,, karena kalau instalasi rumah setiap stop kontak harus pake ground membutuhkan dana lebih ketimbang cuma 2 kabel.Padahal grounding itu penting dan sesuai standar.

    • @daengbacho829
      @daengbacho829 Před 2 lety

      itu semua tergantung sipemilik rumah gan.. mau ngeluarin biaya tambahan untuk kabel grounding apa ngga?. kebanyakan ya mintanya mau yg murah..

    • @jhoniirawan2172
      @jhoniirawan2172 Před 2 lety +1

      @@daengbacho829 iya mas,, yg saya maksud di atas itu termasuk instalasi dirumah saya sendiri.Masalahnya ya mengirit biaya. Hehehe
      Tp kalau mengingat fungsi dr kabel grounding, sebenarnya penting sekali karena kita terhindar dr sengatan listrik jika ada arus bocor.

    • @jayaabadi9027
      @jayaabadi9027 Před 6 měsíci

      Itu pakek Kuningan asli ya ,biasanya besi dicat warna kuning emas kalau di tempatku di desa

  • @yogial-fa4289
    @yogial-fa4289 Před rokem

    Ada baiknya pakai helm bang , yg nonton agak khawatir 😅 palu takut lepas..waktu pukul ground Rod nya

  • @arielenofficial4684
    @arielenofficial4684 Před měsícem

    Kak mohon bantuan anti petir saya kabel groding anti pertinya digabung kabel grading di di goding ncb box listrik.saya egk kal.mohon bantunya saya binggung

  • @surinnida2183
    @surinnida2183 Před 2 lety +1

    kami buat menara dari siku besi utk penempatan spiker dan Di pasang penangkal petir sedang Kabel BC kan tanpa isolasi dan pemasangnya pakai clem yg nempel body kalo ada petir apa gak kena bodi siku .trm ksh. Sebelumya

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety

      untuk pemasangan grounding pada bagian konduktor terbuka seperti besi siku sebaiknya menggunakan penghantar berisolasi. Agar aman ketika terjadi sambaran petir

  • @diywoodworkingjourney5010

    Terima kasih atas videonya. . .
    Btw, boleh ngga sambungan tiang tembaganya di solder dengan timah solder?

    • @siroedhiekreasi
      @siroedhiekreasi  Před rokem +1

      kalau disolder dikhawatirkan lepas pak, sebaiknya dibaut atau bisa juga sistem las menggunakan serbuk misiu (konsepnya hampir sama seperti disolder)

    • @diywoodworkingjourney5010
      @diywoodworkingjourney5010 Před rokem

      @@siroedhiekreasi betul juga yah. . .kalau pake sistem las bubuk mesiu pasti materialnya menyatu dengan sempurna, saya pernah liat di video saat teknisi rel kereta api menggunakan sistem ini untuk menyambung rel kereta 🙏
      Makasih atas ilmunya, sangat berguna untuk saya. . .terima kasih edukasinya, sukses selalu 🙏

  • @dedekkurniadi672
    @dedekkurniadi672 Před 2 lety +1

    kalau untuk rumah minimalis (6 rumah) dengan tipe 5x8
    apakah bisa dan fungsi ny sama, kalau hanya 1 ground saja di tancapkan tembaga dan di pararel ke setiap rumah?

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety

      bisa Pak, pastikan nilai resistansinya di bawah 5 Ohm. Semakin mendekati 0 Ohm akan lebih baik lagi

  • @hartonolubis1559
    @hartonolubis1559 Před 3 lety

    Ajarin saya dong pak

  • @netasari5470
    @netasari5470 Před rokem +1

    Coba diukur pak, tegangan Phase to grounding brapa Volt?

  • @AxyStudio
    @AxyStudio Před 2 lety

    Mantap ilmu nya Pak, mohon bantuannya menjawab, kalau uda tanam batang elektroda di pekarangan rumah, terus pekarangan tersebut kebanjiran, setinggi mata kaki, dimana batang elektroda terendam air, apakah aman? karena kadang anak2 suka main air, apakah bisa nyeterum? Posisi listrik kwh meter semua nyala.

  • @user-gs3dt8bw5s
    @user-gs3dt8bw5s Před 8 měsíci

    Di ralat om ya, kebetulan saya org listrik, cumanmau menjelaskan om
    Kalo untuk instalasi rumah menurut aturan puil ya di bawah 5 ohm, akantetapi kalo untuk pemancar wajib 0,5 ohm malah kalo bisa di bawah 0,5 lebih bagus, dan ada cara nya dan teknik nya om biar bisa dapat ukuran nya sgtu, mohondi ralat kalo salah

  • @aribudiman3228
    @aribudiman3228 Před 2 lety

    ijin share ya min...

  • @edo_daniartha
    @edo_daniartha Před 5 měsíci

    Assalamualaikum Pak. Izin bertanya Sebulan lalu saya sudah ganti kabel instalasi rumah. pakai supreme 3 ×2.5 jalur utama dan 2x1.5 untuk Lampu. saya baru ingat kalau kabel grounding ke Tanah itu sdh lama bgd di putus. lalu sy coba cek lagi dibawah tembok rumah saya dan ada bekas tembaga dan sisa kabel sambungan groundingnya. pertanyaannya, apakah bisa sy sambungkan lagi ?, atau harus beli dan buat baru di tempat yg berbeda. saya lihat warna tembaganya sudah hitam sekali. 1 lagi jika sdh pasang grounding perlukah buat pasang ELCB /RCBO di box mcb. rumah sy masih 900 watt. Terima kasih sdh mau dijawab Pak. 🙏 Waalaikumsalam wr.wb

    • @siroedhiekreasi
      @siroedhiekreasi  Před 4 měsíci

      bisa pakai grounding yg lama saja pak, warna hitam wajar karna proses korosi. bisa diamplas dulu sebelum disambung kembali. ELCB/RCBO diperlukan sebagai proteksi pak

  • @ethonnuga2405
    @ethonnuga2405 Před 3 lety

    Maaf mas mau tanya untuk mengukur grounding apa harus sejajar dengan tembok atau boleh arah depan dari tembok rumah,,,

    • @siroedhiekreasi
      @siroedhiekreasi  Před 3 lety

      tidak mesti kawan, bebas aja. yang penting nilai resistansi pentanahannya sesuai dengan yg dipersyaratkan PUIL 🙏

  • @Nezukokmd
    @Nezukokmd Před rokem +2

    Pak apakah ada sumber referensi , apabila grounding petir tidak boleh menyatu dengan grounding instalasi ?

    • @ucupbintangtoedjoe4489
      @ucupbintangtoedjoe4489 Před rokem

      Mudahnya pahami apa itu gronding dulu insyaallah nanti pinter dengsn sendirinya

  • @user-hk3mp8fr3c
    @user-hk3mp8fr3c Před 3 měsíci

    untuk rumah yg besaran listriknya hanya 4 ampere..sebaiknya ukuran panjang stick grounding brp meter ? dan besar batang stick grounding brp milimeter ?... mhn jawabanya bg...
    trus untuk jarak tanam stick grounding yg dibolehkan sesuai aturan, bberap meter jauhnya dari KWH meteran (atau kotak yg divideo abg td)? ....hal ini sy tanyakan krn ingin mendapatkan tanah untuk tanam grounding yg lembab (misalnya pinggir parit)...mhn jawabanya bg....
    trus besar kabel yg BC/atau kabel yg abg pakek tsb brp milimeter minimalnya bg? (untuk besaran listrik rumahan 4 ampere)..mhn pencerahannya bg..

    • @siroedhiekreasi
      @siroedhiekreasi  Před 3 měsíci

      mengenai panjang stick relatif pak tergantung struktur tanahnya, mengenai diameter stick semakin besar semakin baik (yg saya gunakan dlm video ini 25 mm), dgn jarak stick ke box panel +- 4 meter. yg menjadi patokan adalah nilai resistansinya pak tidak boleh lebih dari 5 ohm

  • @deninav156
    @deninav156 Před 3 lety

    Ilmunya sangat membantu, InsyaAllah berkah Pak.
    Kalau tester pakai multimeter tekiro MS-DM1908, apakah bisa?

    • @siroedhiekreasi
      @siroedhiekreasi  Před 3 lety +1

      Amin... kalau untuk mengukur tahanan pentanahan tidak bisa menggunakan multimeter Pak 🙏. Alat ukurnya earth tester seperti yg saya gunakan dalam video ini 🙏

    • @deninav156
      @deninav156 Před 3 lety

      @@siroedhiekreasi berapa nilai tahanan grounding yang tepat khusus untuk mesin Cnc Pak?

    • @siroedhiekreasi
      @siroedhiekreasi  Před 3 lety +1

      @@deninav156 seperti yg saya sampaikan dalam video ini, nilai tahanan pentanahan sesuai standar PUIL adalah lebih kecil atau sama dengan 5 Ohm. Tapi kalau bicara ideal, nilai tahanan pentanahan yg paling kecil mendekati Nol Ohm yang lebih baik Pak 🙏

    • @siroedhiekreasi
      @siroedhiekreasi  Před 3 lety +1

      @@deninav156 di beberapa perusahaan, mensyaratkan nilai pentanahan harus 0,2 Ohm, tapi nilai tersebut perlu biaya yg lumayan mahal Pak 🙏

    • @wachanel1721
      @wachanel1721 Před 2 lety

      @@siroedhiekreasi biaya yg mahal maksudnya gimana pak. Apakah ada komponen tambahan?

  • @asepdadangsepriawansepriaw1789

    Trimakasih atas Tutorialnya Mas. Saya mau tanya : yang dipake untk ground itu apakah bisa besi ukuran 8 mm atau 12 mm ?. Dan kalo diberi lilitan kabel tembaga itu gimana ?. Ukuran resitensi Ground stadar itu brapa OM ?.

    • @siroedhiekreasi
      @siroedhiekreasi  Před 3 lety +1

      Terima kasih kembali. untuk ground rod tidak bisa menggunakan besi Pak 🙏. karena antara besi dan tembaga memiliki hambatan jeenis yg berbeda dan material besi kurang baik menghantarkan arus. Seperti yg saya sampaikan dalam video, nilai resistansi sesuai standar PUIL adalah lebih kecil atau sama dengan 5 Ohm. Semakin mendekati 0 ohm akan semakin baik

    • @regystacy4887
      @regystacy4887 Před 2 lety +1

      Bantu jawab pak, saya pernah tanam ground pake besi, waktu itu pake potongan besi D16, ujung nya dililit kabel. Jika tanahnya adalah bekas rawa yang ditimbun, maka untuk penanaman titik grounding yang baik, tanah timbunan harus dikupas dulu. kebetulan waktu itu di proyek, jadi timbunan tanah sekitar 3m dikupas, lalu besi tersebut ditanam dan diurug kembali. kabel pakai 16 mm2, dapat resistansi sekitar 0.5 Ohm - 1.5 Ohm. namun utk hal yang pasti, sebaiknya pakai copper rod.

    • @badartsani8841
      @badartsani8841 Před 2 lety

      Besi boleh juga dipakai sebagai grounding rod, asalkan disesuaikan ukurannya dan dilapis galvanis/sepuh tembaga. Sudah ada standar yg mengatur berbagai ukuran grounding rod menurut bahan materialnya. Klo besi lapis tembaga klo tidak salah minimal 15mm diameter.

  • @amirudincrane
    @amirudincrane Před 2 lety

    Mau Nanya Pak l,Pemasangan Ground Anti Petir di tanam dalam rumah Atau Diluar rumah grounding nya,Trus cara pemasangan nya apa sama Rumah 3 tingkat , Mohon Penjelasan nya ,🙏🙏🙏

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety

      dipasang di luar rumah Pak, carampemasangannya sama persis seperti yg ada dalam video. Dan nilai resistansi pentanahan semakin mendekati 0 ohm akan semakin baik

  • @aditya-5893
    @aditya-5893 Před 2 lety +1

    Untuk kabel grounding / penangkal petir....apakah bisa dimasukkan ke lubang pipa sumur air? Daripada pakai electroda..

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety

      tetap pakai elektroda Pak, karena material yg digunakan (tembaga) dengan diameter tertentu dan nilai resistani lebih kecil atau sama dengan 5 ohm akan sangat berperan menyalurkan arus gangguan.

  • @kangtoniwae1420
    @kangtoniwae1420 Před 2 lety

    Pakek bor lah bang.. Bawah siram air, kasian yg mukul 😁

  • @wachanel1721
    @wachanel1721 Před 2 lety

    Pak klw kabel yg dri grounroot nya itu apakah bsa langsung di sambungkan ke unit (alat medis) bukan ke panel listrik sprti di video. Dan satu lagi apa jenis kabel yg di gunakan? Dan berapa ukuran kabel yg disarakan? Terima kasih 🙏

  • @Taukahkamu92
    @Taukahkamu92 Před 2 lety +1

    Maaf bang mau tanya,,. Atap rumah sya baja ringan, untuk menghindari bahaya, apakah bisa saya psang kabel grounding dari atap baja ringan ke tongkat grounding..?
    Terima kasih

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety +1

      bisa Pak, dan pastikan resistansi pentanahan sesuai yg dipersyaratkan PUIL. Agar berfungsi ketika ada gangguan 🙏

  • @triplea363
    @triplea363 Před 2 lety

    Tancepkan Pakai jack hammer mas,

  • @budionobudi8647
    @budionobudi8647 Před 2 lety +1

    Pak mau Tanya apakah boleh kabel grounding Di tanam satu persatu dibawah stop kontak satu persatu, Dan apa resikonya terimakasih..

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety +1

      boleh Pak, karena ada banyak model/ tipe pentanahan. Tapi yang perlu diperhatikan adalh nilai resistansi pentanahannya, apakah sesuai standar atau tidak. Karena kalau hanya sekedar kita pasang grounding dan tidak diukur, tidak ada jaminan apakah sistem groundingnya efektif atau tidak. 🙏

  • @abdidalem7251
    @abdidalem7251 Před rokem

    Apa gk lebih fektif di bor saja ..kayak bikin sumur bor..😅

  • @fajrulsyamsi5010
    @fajrulsyamsi5010 Před 2 lety +1

    Maaf bertanya jarak rod yg ditanam antara rod buat grounding dan rod buat arrester berapa meter ya

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety

      mengenai jarak pemasangan rod relatif sifatnya Pak, tergantung dari karakteristik tanah. bisa kita pasang dengan jarak 2 s.d 3 meter. intinya masing² rod harus tersambung dengan baik, dan nilai resistansi pentanahan harus sesuai standar PUIL yaitu lebih kecil atau sama dengan 5 Ohm. Semakin kecil mendakti 0 ohm akan semakin baik 🙏

  • @mochamadridwan5998
    @mochamadridwan5998 Před 2 lety +1

    untuk mencapai nilai 0 ohm apakah bisa? apakah batang rod dari bahan tembaga murni gak karatan ditanam dibawah tanah? usia batang rodnya berapa tahun ? berapa banyak biaya yg dikeluarkan untuk dapat menghasilkan resistansi 0 ohm?

    • @siroedhiekreasi
      @siroedhiekreasi  Před 2 lety

      idealnya tahanan 0 ohm bisa dicapai, tapi pada kenyataannya memang sulit Pak. PUIL juga mensyaratkan dikisaran 0 sampai 5 Ohm. Rod yg ditanam tidak berkarat ( beda dengan besi) dan bisa digunakan selamanya, tapi tentunya harus ada pemeliharaan. Kalau resistansi berubah di atas toleransi, maka harus dilakukan penyesuiaan kembali.

  • @freddypurnomo8722
    @freddypurnomo8722 Před rokem

    bang jika buat generator 1000w apakah perlu gensetnya di lengkapi rod grounding ?
    apa ada saran di beri rod ground berapa meter minimal terpendek ?

    • @siroedhiekreasi
      @siroedhiekreasi  Před rokem

      perlu bang, mengenai kedalaman rodnya relatif bang. yg paling penting resistansinya harus sesuai. maks 5 ohm, semakin mendekati 0 ohm semakin baik