Goodman Gas Furnace natural gas leak repair

Sdílet
Vložit

Komentáře • 112

  • @andrzejhajder6405
    @andrzejhajder6405 Před 5 měsíci +3

    That's a good mechanic. Checking everything. That is 90+ . Temperature shuld be about 92*F . Not 300 *F . Even on 80% should be no more than 200. Good finde.👍

  • @blang2101
    @blang2101 Před 5 měsíci +2

    Always a joy to watch your videos! I spent 51 years in the trade and you make my day!

  • @gtpforever
    @gtpforever Před 5 měsíci +2

    I had a goodman unit getting extremely hot similar to this and the heat exchanger looked good with camera as far as i could reach and the flames didn't dance at all but turned out that the heat exchanger had a hole in it blowing massive heat right at the secondary.
    Never seen any signs until it was pulled out.

  • @JohnSmith-ug5ci
    @JohnSmith-ug5ci Před 5 měsíci +1

    I am glad that you will give them all the options. I always have a problem when a tech only says "you need a new unit" when there is other options.

  • @mattliebenau9083
    @mattliebenau9083 Před 5 měsíci +5

    The Trane screws probably doubled the value of that old Goodman! 😂😅

  • @craigbraswell4269
    @craigbraswell4269 Před 5 měsíci +2

    I will say, if you install mini-splits, nylog blue is your best friend. It's manufacturer recommended, it works and I've never had a flare leak when nylog is applied correctly. Say what you will, but nylog is the shiz! I wouldn't say it's necessary on low pressure, consistent temperature gas lines, but high pressure, hi temp fluctuating flare joints, YES!

  • @Ted_E_Bear
    @Ted_E_Bear Před 5 měsíci +4

    Cowboy, you have put out another awesome video ! Thanks for sharing

  • @search_eternal
    @search_eternal Před 5 měsíci +4

    I know the guy you're talking about. He puts dope on everything. LOL

    • @chatrkat
      @chatrkat Před 5 měsíci

      It’s good enough for this neighborhood mama. 😁 I watch several, I really like Ted.

  • @robalexander7348
    @robalexander7348 Před 5 měsíci +1

    Well done Ted, another one up and running safely... No heat required in NSW Au today its 12.20 and already 30c (86F ) 👍 Au

  • @eapentmani3384
    @eapentmani3384 Před 5 měsíci

    Every weeks upload troubleshooting videos your explain ways are good and understandable nice job

  • @mr.r9505
    @mr.r9505 Před 5 měsíci

    Great job Ted I totally agree with you 100%

  • @mtu-engineer3220
    @mtu-engineer3220 Před 5 měsíci +3

    Start with inspection of air filter, then break out the manometer.
    Also check gas pressure to make sure it is not overfiring. Clock the meter.

  • @danobrien3109
    @danobrien3109 Před 5 měsíci +6

    You need to set the gas valve pressure on all new gas valve replacements just as you do with new furnace installs. Manufactures no longer seem to care about quality. In the old days ( I’ve been doing HVAC since 76) it was very uncommon for gas valves to be over firing on new furnaces and replacement valves. At our age Theodore it’s always nice to not have to kneel down to work on stuff. Be well👍👍🇨🇦

  • @joeydiferdinando4441
    @joeydiferdinando4441 Před 5 měsíci +1

    Ted, was down your neck of the woods- Honea Path, this past week- pretty sure I passed your place going back to the GSP airport- I thought to myself, I just passed old Ted’s place- legend!

    • @TedCookHVAC
      @TedCookHVAC  Před 5 měsíci +1

      Should have stopped !!

    • @joeydiferdinando4441
      @joeydiferdinando4441 Před 5 měsíci

      I’ll be heading down to the plants a few times over the next couple months- I’d enjoy stopping over. I’ll be sure to give you a heads up.
      I enjoy Honea Path- nice and quiet - I can check Sparky’s Tacos off my list- Next, on the list is the Little Biscuit Barn- The plant boys got a kick out of the old PA yankee pap ordering sweet tea.

  • @gambitmac
    @gambitmac Před 5 měsíci

    3 weeks wait for a new video is too long. Love the content.

  • @williamserver4332
    @williamserver4332 Před 5 měsíci +1

    Id check filter, temp rise then gas pressure. It is definately running too hot. Great video as always

  • @throttlebottle5906
    @throttlebottle5906 Před 5 měsíci +1

    I've been putting pipe dope on majority of flare and union "threads" for around 20 years. my reason is mainly for anti-seize purposes, where they tend to get condensation or water spray from leaks or service work and can rust very hard into place. I use a vibration/locking type sealant though, don't want them to come loose and leak.
    the flex connector hoses don't need anything for anti-seize, because of stainless, brass or other coated metals not rusting. although the anti-vibration locking is nice, for some scenarios.

  • @jonnyaasen1018
    @jonnyaasen1018 Před 5 měsíci +1

    Time to calm down and relax after watching those da-gum chiefs win another Super Bowl. Thanks for the comfort Ted

  • @bryansimon4072
    @bryansimon4072 Před 5 měsíci

    With information given, looks like the right call.

  • @throttlebottle5906
    @throttlebottle5906 Před 5 měsíci

    gas smell that nobody can find. my first thought is "ignition failure", until it locks out and auto-resets or customers power cycle, causing more ignition failures. since every ignition failure dumps diluted unburnt gas out the flue pipe, it's often smelled fairly strong, add in drafty older home or leaking heat exchangers and you get tom foolery the gas company cannot find, not that they're great at finding leaks anyway! been there done that. lol
    **edit** well, it banging off the high limit endlessly, with flue exhaust directly in front of an crawlspace vent will do it! that was some real genius install work back then! 🙄😬

  • @kg4muc
    @kg4muc Před 5 měsíci

    Good job !! That things headed to a meltdown. I’m with you it needs to vacate the premises

  • @user-cb3um9yc6x
    @user-cb3um9yc6x Před 5 měsíci +2

    we ran in to close to same issue with Tempstar counterflow 90plus in garage over heating. eating up Camstats.
    Found someone cut loose return in attic. white blow in insulation clogged secondary heat exchanger.

  • @garypoplin4599
    @garypoplin4599 Před 2 měsíci

    11:07 - Because of the hex, I would expect it was meant for using to tighten the valve. Where else can you put a wrench to tighten it? The only thing I could see doing different here is using a flat jaw adjustable wrench (what my dad called a “Crescent” wrench).

  • @mtu-engineer3220
    @mtu-engineer3220 Před 5 měsíci

    I use thread compound on unions in damp and outdoor locations to keep the threads from seizing. I never put any on the actual seating face, it can squeaze out and leak.

  • @user-cb3um9yc6x
    @user-cb3um9yc6x Před 5 měsíci +1

    My vote would have also protect wire going through cabinet. from 4th generation family plumbing / hvac contractor. Nice crawl space

  • @rayvoorhies7180
    @rayvoorhies7180 Před 5 měsíci +1

    Did you consider condemning the unit? It's concerning that its getting too hot. But the high limit is doing its job to prevent a fire. Maybe they can get by another six weeks until Spring. Save money for a new furnace before next winter.

  • @LmTeamWaxOffroad
    @LmTeamWaxOffroad Před 5 měsíci +1

    I have had the same situation with gas smell that was hard to diagnose. Cone to find out, the crossovers on the inshot burner’s were dirty. Not lighting all the burners intermittently and filling the area with gas.

    • @throttlebottle5906
      @throttlebottle5906 Před 5 měsíci

      yeah, that happens, as well as spiders and bugs clogging the orifices, burner tubes and even partially plugging heat exchangers(stink bugs love filling them up!)

  • @CommercialGasEngineerVideos
    @CommercialGasEngineerVideos Před 5 měsíci

    That's a good repair right there

  • @raymondjacobs8429
    @raymondjacobs8429 Před 5 měsíci +2

    @ 11:17 Ted, like you said shouldn't be with a pipe wrench, But, I hand screw a nipple into it, for some structure, maybe it's just that it looks like it would help. Also having a Monkey wrench Helps.

    • @rmac2592
      @rmac2592 Před 5 měsíci

      As steamfitter apprentices, we were taught to always put a nipple in there. But like Ted, as one becomes more experienced, judgment calls are made. That valve looked extra beefy so I agree with Ted.

  • @Android_Warrior
    @Android_Warrior Před 5 měsíci

    @15:58, YOU ARE RIGHT UNCLE TED!!, a flare doesn't need pipe dope!!!!!

  • @hvactechwanttobe1499
    @hvactechwanttobe1499 Před 5 měsíci

    Ted good job on replacing the gas valve
    I probably replaced valve and the control board same time if I am you not sure what it is at fault it could be ether or both

  • @sknight0391
    @sknight0391 Před 5 měsíci +3

    23:30 Jimmy Protectors 😎👍

  • @watermanone7567
    @watermanone7567 Před 5 měsíci +2

    Did you check the air filter and the blower wheel for debris? Also what is the difference between the return and outlet of the unit? That was a really good video. Thanks

  • @apollorobb
    @apollorobb Před 5 měsíci

    I know who the guy was he was replacing a AO smith commercial water heater . Yeah i thought the Pipe dope on a taper seal fitting was a little goofy but you are correct the only thing you MAY need is lubrication and it should be between the flare nut and the copper to reduce friction when tightening and stop gauling .Another issue i see is they have that exhaust right in front of the Basement fress air vent thats bad news . Have you ever thought of doing combustion analasys i do it to every unit youd be surprised how many installs have way high CO2 and Nox that isnt very efficient .

  • @RayRay-nb7tn
    @RayRay-nb7tn Před 5 měsíci

    Those old Goodman furnaces don't need to be that hot on the exhaust housing maybe warm to the touch but not so you can't touch it. I see them melt before but due to the motor burn up. IMO its clogged. I like hanging my units on strut, 1/2" plywood with a metal drain pan the whole length and width of platform with rod. Never had a problem of vibration from the unit. I've even used metal high hats to sit the unit on in the pan. Depending on application. I see why they hung that unit is cuz of the flood line on the house and surrounding area. Wonder if ya can cut open the vavle to see what caused it, maybe the coil. Good call on replacement of gas vavle.

  • @waltradcliffe4482
    @waltradcliffe4482 Před 5 měsíci

    I had the same problem with my rental house she said she smelled gas when she came home after being away for a few hours, I guess she was desensitized when home for a while and not worried about it I told her it wasn’t something to ignore and to call the gas co. turned out the gas valve was leaking by after it shout off, I wouldn’t have ever found that with the soapy bubbles!

  • @richardboggs260
    @richardboggs260 Před 5 měsíci +1

    Hey Ted did you get your drive way all repaired and paved after the water pipe broke??

  • @craigbraswell4269
    @craigbraswell4269 Před 5 měsíci

    I've come across a few stuck valves in my time. They may hang open slightly on one try, they might work fine a dozen other times. Scary situation for the homeowners for sure.

  • @yz250a
    @yz250a Před 5 měsíci

    Secondary heat exchanger is probably choked by lint, hair or dust. Oops, ya beat me tuit.

  • @curtwuollet2912
    @curtwuollet2912 Před 5 měsíci +1

    Torque on that valve might be why the last one stuck with that big diaphragm. I'd check the manifold pressure.

  • @jimoakley3436
    @jimoakley3436 Před 5 měsíci +2

    She's a leaker mama!

  • @eastcoastwatch672
    @eastcoastwatch672 Před 5 měsíci +1

    Yup, I’ve seen that guy dope up a compression fitting, he claims it lubricants the joint. 😅

  • @JohnNininger-hg9im
    @JohnNininger-hg9im Před 5 měsíci

    I have had that problem on old cheeks back in the day and a few carriers it has always been for me someone replaced the draft inducer and did not put the restrictor (bushing) I guess you would call it on the draft inducer

  • @jazbell7
    @jazbell7 Před 5 měsíci

    A furnace that old and that hot with hard to replace parts is a prime candidate for a (fatal) heat exchanger leak. Best to replace...

  • @ozhoo
    @ozhoo Před 5 měsíci +2

    Have you ever seen the relay on the control board cause this problem?

  • @tomraines7398
    @tomraines7398 Před 5 měsíci +1

    Kudos on finding the overly hot cold header and the resulting shut down on high limit, that said, I'm not sure why the unit "needs to go" nor why it is not worth at least attempting to clean. I agree that the induction blower was old and might be difficult to source but that's a guess at this point. The burners seemed to be burning well as is evidenced by the unaffected flame when the blower came on. Too often I feel like the HVAC industry has a "needs to go" mentality that gives customers the opinion that upselling is all they're about. Just my opinion, for what it's worth, and an admitted advocate for the customer.

    • @TedCookHVAC
      @TedCookHVAC  Před 5 měsíci +3

      Not worth spending 1200 to 1500 to repair when 4800 gets a new one with 10 years Wtty.

    • @tomraines7398
      @tomraines7398 Před 5 měsíci

      fair enough. Woo hoo Chiefs!!@@TedCookHVAC

  • @terryrobertson8382
    @terryrobertson8382 Před 5 měsíci

    I am a Licensed Aircraft Mechanic and don't know enough about home HVAC to criticise any of your work. I would, however, hire you to work on my system any time.

  • @ronkurey5981
    @ronkurey5981 Před 5 měsíci

    All the supply registers open…in my experience, the secondary heat exchanger is clogged….one can still get the inducer motor assembly

  • @gmcxm211
    @gmcxm211 Před 5 měsíci

    It looks like there are two problems, bad high limit switch and airflow issue across the heat exchanger. Like you said the chamber area should never get that high. If the air flow across the heat exchanger is restricted, that would open the high temp switch prior to meeting the call on the thermostat, would it not? If limit switch is operating normally, this furnace would be experiencing premature shutdowns.

  • @barryriem3216
    @barryriem3216 Před 5 měsíci

    Seems like I can hear the gas flex line whistling the instant the gas valve opens.

  • @petersteffen9228
    @petersteffen9228 Před 5 měsíci

    It could be relace, when it's that old. I bet next problem will be the heat exchanger leaks.

  • @hotboiorlando
    @hotboiorlando Před 5 měsíci

    That furnace getting that hot seems a little on safe to me lol

  • @eddiereichel9354
    @eddiereichel9354 Před 5 měsíci

    My mom got a new house 4 years ago. Its a modular. It came with a miller furnace. 2 summers ago the contactor on the AC shorted out and blew the fuse. Last week she calls me and has no heat. I went over and fuse was blown again. It blew soon as gas valve opened. I pulled the wires off and fuse didnt blow anymore. My question is could there something underlying that keeps shorting outputs out or is it just they dont make things like they used to?

  • @chatrkat
    @chatrkat Před 5 měsíci

    Nice stand up crawl for a change. I can’t believe that high temperature plastic can stand those extremes without distorting. She gotta go!

  • @barryriem3216
    @barryriem3216 Před 5 měsíci

    GMT line of Goodman. (GMNT) I worked on a lot of those.

  • @daveoswald5375
    @daveoswald5375 Před 5 měsíci +1

    Hi Ted. When you changed the valve, did you verify manifold pressure or clock the gas meter to ensure the furnace was not over fired. Checking the condensing heat exchanger, filter and ac coil is also a must.😊

    • @TedCookHVAC
      @TedCookHVAC  Před 5 měsíci +1

      I did set gas pressure but video is too long as it is.

    • @daveoswald5375
      @daveoswald5375 Před 5 měsíci

      @TedCookHVAC Good to know... you not watching the superbowl?

  • @scott2582
    @scott2582 Před 5 měsíci

    Doing a meter test on the gas meter, [ Turning off all gas appliances , shutting valves on piloted appliances ] and moving the 1/2 foot hand to 6 oclock, marking it, and watching it for 5 /10 minutes , if it moves , you have a gas leak.

  • @bills6946
    @bills6946 Před 5 měsíci

    Did you leave your manometer home today? I ALWAYS check the gas out when I replace a valve. Most are set about 4” so they work on anything

  • @kevincampbell7276
    @kevincampbell7276 Před 5 měsíci

    A while back on one of my service calls I found a leak on the valve around knob when I press down for pilot it stopped leaking once I let off it started again just my experience not knocking yours

  • @chadwilson2879
    @chadwilson2879 Před 5 měsíci

    Id be willing to bet that the secondary HX is plugged. Find that quite often on the old Bryant/Carrier 90+ furnaces. The top of the furnace will get so hot that you cant hardly touch it

    • @AdamCraig-ir6yl
      @AdamCraig-ir6yl Před 5 měsíci

      Clogged internally or externally? I've always wondered if internally it could cause high limit

  • @numchux2
    @numchux2 Před 5 měsíci

    I just had one similar, the gas was leaking both at the meter union and from the crawl...it sucking into the return ductwork in the crawl through and cracks it could find and blowing out the supply and into the house. How the gas company "Didn't find anything" really makes me wonder. I found it easily.

  • @user-hv9gk5tc8z
    @user-hv9gk5tc8z Před 5 měsíci

    Any flood update? Hopefully those trucks are back on the road…

  • @EverythingHVACR
    @EverythingHVACR Před 5 měsíci +1

    Run what you brung 😅

  • @barryriem3216
    @barryriem3216 Před 5 měsíci

    Is that a 3/8 In OD gas flex line? Looks like 22 In long. Natural gas 60K BTU input. Looks small from my armchair.

  • @eddiekilby
    @eddiekilby Před 5 měsíci

    I think you called it right shes past it.

  • @joeshearer1247
    @joeshearer1247 Před 5 měsíci

    If you had just put some dope on that flex connector it would have fixed all those issues at the end

  • @keysautorepair6038
    @keysautorepair6038 Před 5 měsíci

    With something like this I would have replaced the whole thing wouldn’t want to be liable for someones death in case it happened again.

  • @drband8181
    @drband8181 Před 5 měsíci

    Is that furnace safe as it is?

  • @mfreisem7
    @mfreisem7 Před 5 měsíci

    Set new valve gas pressure?

  • @chrisjnoe2020
    @chrisjnoe2020 Před 5 měsíci

    Can that flu terminate that close to crawl space vent?

  • @sknight0391
    @sknight0391 Před 5 měsíci +6

    Temp. Rise: 40-300° 😮

    • @j.j.6050
      @j.j.6050 Před 5 měsíci

      That just doesn't seem safe.

  • @skatesuter5396
    @skatesuter5396 Před 5 měsíci

    Some thing fell out of the manifold pipe when you removed the gas valve. 9:30 Appox. It may have been a video fault or shadow, but some thing appeared to fall out of the pipe.

    • @skatesuter5396
      @skatesuter5396 Před 5 měsíci

      It may have been light reflection off of the black pipe. Sorry

  • @nomusicrc
    @nomusicrc Před 5 měsíci

    All the safety equipment we have on a furnace but nothing to tell us that the gas valve stuck
    open
    So what did they say about replacing the furnace

  • @craigbraswell4269
    @craigbraswell4269 Před 5 měsíci

    They call that a "cold header" and it's anything but cold! That ain't right!

  • @549BR
    @549BR Před 5 měsíci

    Good to hear the soft spoken Carolinian once again; if it's fixable, Ted's the guy that can do it.

  • @FixthisCD
    @FixthisCD Před 5 měsíci

    clean it up, run for another 10 years

  • @freebird7328
    @freebird7328 Před 5 měsíci

    tiny little gas line

  • @Eddy63
    @Eddy63 Před 5 měsíci +1

    I can attest that you didn't use a wheel puller one time in the removal of that gas valve ... Thx

  • @baratono
    @baratono Před 5 měsíci

    Looks like it was set up to be able to be plugged into a portable generator.

  • @search_eternal
    @search_eternal Před 5 měsíci

    Having the furnace flue pipe right next to a crawl space vent has to be a code violation?

  • @dmiestercommkitchentech3043
    @dmiestercommkitchentech3043 Před 5 měsíci

    Where is the fresh air coming from it only has a single vent pipe; I have a feeling it is not installed correctly because it needs a fresh air intake along with the exhaust vent pipe I'd be willing to bet the fresh air inlet is blocked causing a vacuum instead a air flow circuit.

  • @chuckq54
    @chuckq54 Před 5 měsíci +1

    Replacement time 🤷‍♂️

  • @MariosACandRefrigeration
    @MariosACandRefrigeration Před 5 měsíci

    checking static pressure could tell you what is wrong,2 cents.Tag out.

  • @bruceshepherd6217
    @bruceshepherd6217 Před 5 měsíci

    You don't set the gas prusher

  • @prettycureforever7102
    @prettycureforever7102 Před 5 měsíci

    When you’re a gas company and you won’t do anything to fix . What is the point in having gas companies if they won’t do much beyond ?

    • @AdamCraig-ir6yl
      @AdamCraig-ir6yl Před 5 měsíci

      Well they don't work on furnaces so they would have to know how to check the valve etc.....that's my guess

  • @SignorNessuno65
    @SignorNessuno65 Před 5 měsíci

    I still don't understand the doors put on with screws.

  • @wilcleno1866
    @wilcleno1866 Před 5 měsíci

    1st.

  • @ryanjackson0x
    @ryanjackson0x Před 5 měsíci

    Anti-DIY? Someone's got to do it themself though.

    • @j.j.6050
      @j.j.6050 Před 5 měsíci

      Go ahead. Then call Ted.

  • @larrycrain5650
    @larrycrain5650 Před 5 měsíci

    Cannot believe you did not try to sell them a new unit, you always try to sell a new unit. Was it because they are fellow church members.

    • @TedCookHVAC
      @TedCookHVAC  Před 5 měsíci +1

      I did quote a new furnace

    • @j.j.6050
      @j.j.6050 Před 5 měsíci

      Any number of things could be ready to fail on such an old piece of equipment. The tech fixes what he/she was called out for, and the next day something else fails that the tech gets blamed for. Tech becomes married to the thing, so it's not worth it.

  • @sonicfuker
    @sonicfuker Před 5 měsíci

    What happened? No leak test? Temp out of the vents? Verification of limit switch? Is there air flow? I'm lost on this one.

  • @robertvosburgh7540
    @robertvosburgh7540 Před 5 měsíci

    Being up here in Spartanburg. May I ask for your honest opinion? I have a horizontal furnace with a slab coil. You prefer not to hang the furnace. I have a limited crawlspace I thought hanging would be better. But since you don't like hanging. What's your preferred method?