Komentáře •

  • @Simply2sureOdds
    @Simply2sureOdds Před 11 měsíci +2

    Very educative 😊. Thank you for your simplified explanations.

  • @Black74c
    @Black74c Před 8 měsíci +2

    Informative....Why are the mains supply cables for solar and Grid connected at the down terminals of the earth leakage . Kindly explain

  • @batjiyasanthos5526
    @batjiyasanthos5526 Před 7 měsíci +1

    Simple and informative. Thank you 👍

  • @giftmofolo9487
    @giftmofolo9487 Před 7 měsíci +1

    Me and my class we are proud of you sir we have made it❤

    • @obloni_Electrical
      @obloni_Electrical Před 7 měsíci

      Wow! That's great to hear. From which country please?

  • @mulandomulilambonge9124
    @mulandomulilambonge9124 Před 4 měsíci +1

    Very good demonstration.

  • @mostafaawad9407
    @mostafaawad9407 Před 11 měsíci +1

    Thank you for the good explanation, look forward for the new video ❤️

  • @danielteyehuago1633
    @danielteyehuago1633 Před 8 měsíci +1

    Well done, but having a rough sketch of the diagram and adjusting the camera angle will have been of a great help to us.

  • @solomonkipsi3762
    @solomonkipsi3762 Před 6 měsíci +1

    Great explanation 💗

  • @isausmanaudu6351
    @isausmanaudu6351 Před 16 dny

    Very well explanation but sir for the NC you said to solar coil you didn't mention which terminal thank you

  • @kayitamoses8580
    @kayitamoses8580 Před 3 měsíci +1

    I am going to apply the very same controls for a 3-phase circuit

  • @romeosecretaria6968
    @romeosecretaria6968 Před 4 měsíci +2

    Its a nice demonstration and explanation. But for lighting load only, it can be done by using relays which are cheaper and lesser power consumption on magnetic coils.

    • @obloni_Electrical
      @obloni_Electrical Před 4 měsíci +1

      Thanks Romeo. I only used the lamps to represent the load in the wiring. It doesn't mean it is only meant for lighting load. Thanks 👍

    • @romeosecretaria6968
      @romeosecretaria6968 Před 4 měsíci +3

      But i still like your discussion. But next time, kindly use materials relative to the load you are demonstrating. Or mention the load that the circuitry capability to carry on.thanks

    • @obloni_Electrical
      @obloni_Electrical Před 4 měsíci +1

      Well noted thanks. @@romeosecretaria6968

  • @multiskilledelectrician1
    @multiskilledelectrician1 Před měsícem

    Thank you for sharing. Is the device placed on Grid contactor timer or what?

  • @dylanthomasprowse880
    @dylanthomasprowse880 Před 4 měsíci +1

    excellent video, very good

  • @luckychidi9777
    @luckychidi9777 Před 5 měsíci +1

    very impressive and educative, pls what about a connection when relay in involved in this kind of connection
    pls i would love to balance this

  • @user-xn6jm4pb1h
    @user-xn6jm4pb1h Před 9 měsíci +1

    Great! keep it up bro.

  • @danielteyehuago1633
    @danielteyehuago1633 Před 6 měsíci +1

    This video I rate it 🌟🌟🌟🌟🌟

  • @Kodjoedem
    @Kodjoedem Před 2 měsíci

    If you want to add a 3rd power source say gen. If the solar power runs out, does it mean you wire the contactor of the generator as secondary to the solar where you place an aux NC contactor and run the live through it before it goes to A1/2?

    • @obloni_Electrical
      @obloni_Electrical Před 2 měsíci

      That will require a very different arrangement. I will show it in a subsequent video. Thanks

  • @royakalah181
    @royakalah181 Před 3 měsíci +1

    Very clear explanation - you didnt mention function of the MCB

    • @obloni_Electrical
      @obloni_Electrical Před 3 měsíci

      Don't worry dear, everything you need to know about that is here use this link: czcams.com/video/EDl-Vapdm5M/video.html

  • @gowthampavanaskar1889
    @gowthampavanaskar1889 Před 24 dny

    On this example are you using two different power supplies or uaing the same power supply split into solar and grid?

    • @obloni_Electrical
      @obloni_Electrical Před 24 dny

      I used two different phases. L1 and L2, to represent Grid and Solar respectively.

  • @thousiffg7393
    @thousiffg7393 Před 6 měsíci +1

    Can we do it with two pole contactor

  • @carl78052
    @carl78052 Před 4 dny +1

    Whats the use of single pole breaker?

    • @obloni_Electrical
      @obloni_Electrical Před 4 dny

      @@carl78052
      czcams.com/video/EDl-Vapdm5M/video.htmlsi=03__xTgOIxxf-snv
      Please use the link above for thorough explanation to your question. Thanks

  • @danielteyehuago1633
    @danielteyehuago1633 Před 8 měsíci

    Please this is a good tutorial, can you redo it with detailed diagram and good camera angle. Thanks

  • @manudesmond1680
    @manudesmond1680 Před 11 měsíci +1

    Pls sir, what if I am using generator instead of solar panel, can I go by the same principle. Thank you.

    • @travismailsa1
      @travismailsa1 Před 10 měsíci

      I think you can, but you will have a power dip if you do not have an inverter before you either manually start your generator or for the ATS to start the generator.
      Normally with generators a solenoid based changeover switch is used.

    • @manudesmond1680
      @manudesmond1680 Před 10 měsíci

      @@travismailsa1
      Pls I don't get it well, can you please give me further explanation. Thank you 💕

  • @MosesChanda-eh2of
    @MosesChanda-eh2of Před 2 měsíci

    Please help me how to wire a hammer mill with a 24 HP circuit

    • @obloni_Electrical
      @obloni_Electrical Před 2 měsíci

      Please kindly come clearer on how you want me to help you. For 24Hp you may have to use Star delta starter. You can watch this video for more explanation on the star delta wiring.
      czcams.com/video/zIJ66ZRrJQo/video.htmlsi=if2DogaCzdMtn-du

    • @MosesChanda-eh2of
      @MosesChanda-eh2of Před 2 měsíci

      @@obloni_Electrical yes using star delta

    • @MosesChanda-eh2of
      @MosesChanda-eh2of Před 2 měsíci

      I mean the whole circuit inclusive using stop and start buttons and timers together with loverload relay. It would mean a lot to me thank you

  • @Black74c
    @Black74c Před 9 měsíci

    What happens in an event of a faulty contactor ?

    • @obloni_Electrical
      @obloni_Electrical Před 9 měsíci +2

      As a result of bad Coil, the contactor Will not close.
      As a result of a bad contact, the contactor Will close but there will not be out put power.

  • @VemuriRakeshRakesh
    @VemuriRakeshRakesh Před 5 měsíci +2

    Looking good . Please provide drawing as connections are not understanding

  • @biggiekasimba2972
    @biggiekasimba2972 Před 11 měsíci +1

    Hundreds

  • @danielteyehuago1633
    @danielteyehuago1633 Před 6 měsíci +1

    This video has weight. I am back again

  • @jessew6757
    @jessew6757 Před měsícem

    Do you have a schematic for this sir ?

  • @KariIru-li8xu
    @KariIru-li8xu Před 10 měsíci +1

    Please need a wiring diagram. Ta

  • @antoniorodriguezperico
    @antoniorodriguezperico Před 11 měsíci +1

    Diagram please! Thank you

    • @obloni_Electrical
      @obloni_Electrical Před 11 měsíci

      Noted . I will try to include diagrams in the subsequent videos. Thanks

  • @thousiffg7393
    @thousiffg7393 Před 6 měsíci +1

    Can we do this without rcb

    • @obloni_Electrical
      @obloni_Electrical Před 6 měsíci +1

      Oh yes!

    • @thousiffg7393
      @thousiffg7393 Před 6 měsíci

      I done without rcb but my inverter burnt

    • @obloni_Electrical
      @obloni_Electrical Před 6 měsíci +1

      @@thousiffg7393
      Oh no! Something was probably not done right.
      But please, did you test the changeover setup before hooking it up?

    • @danielteyehuago1633
      @danielteyehuago1633 Před 6 měsíci

      ​@@thousiffg7393Please which auxiliary contact did you use. Because the auxiliary contact used on the grid contactor was NC

    • @user-lg3mq3sh2i
      @user-lg3mq3sh2i Před měsícem

      Noticed that the breaker is not switched on or off in the circuit

  • @user-lg3mq3sh2i
    @user-lg3mq3sh2i Před měsícem

    The breaker is not switched on or off why ,😮 did anyone notice

    • @obloni_Electrical
      @obloni_Electrical Před měsícem

      Yes, that mcb was intentionally placed there to let you that anytime you are wiring RCDs there must also be an mcb. The other one is an RCBO so it can work alone. Please watch these videos to be guided.
      czcams.com/video/s1dP9xth6KY/video.htmlsi=s4bGxpv_Sp5JRL9k
      czcams.com/video/EDl-Vapdm5M/video.htmlsi=6TQYZgWn4wIjeKSJ
      czcams.com/video/yAxkPvMb-7E/video.htmlsi=i2-O9lOykfwibT3d
      czcams.com/video/MhdUZ7wOEPw/video.htmlsi=ikg-wRbN3EzbrjIy
      czcams.com/video/HeRdarYcoIQ/video.htmlsi=eY4wRP2fNCmADMMn

  • @Ibrahimsaheed-bn2ph
    @Ibrahimsaheed-bn2ph Před 11 měsíci

    Very well explained but I have a question to ask sir,My question is that what's the work of the single mcb beside the double pole RCB of Solar grid ? Where does the output of that mcb connected to ? Secondly why the input for Solar and Grid are not the same T1&T2 I mean colour and Terminal interchange, Lastly can you please drop your WhatsApp number for more experience and have access to your status.Thank you sir

    • @obloni_Electrical
      @obloni_Electrical Před 11 měsíci +1

      1. please watch these videos
      czcams.com/video/EDl-Vapdm5M/video.html
      czcams.com/video/yAxkPvMb-7E/video.html to clearly understand why I used the single-pole mcb with the RCCB.
      2. connecting the Live & Neutral cables of the grid and solar to different terminals T1 & T2 doesn't matter. What matters is the connection at the output side of the contactor (L1 & L2), to ensure that the
      Live and Neutral from the grid aligns correctly with the Live and Neutral from the Solar supply.
      3. WhatsApp +233242809918
      main channel: czcams.com/channels/WnOYQv9Jxsv6Ax9tip9OnA.html

    • @iambenqazy
      @iambenqazy Před 11 měsíci +1

      Thank you for the thorough explanation. Great video by the way 💯. Can you please share the layout diagram for this particular setup. I really like the mechanical interlock you did. Thanks in advance.

  • @manudesmond1680
    @manudesmond1680 Před 11 měsíci

    Pls sir, what if I am using generator instead of solar panel, can I go by the same principle. Thank you.