2020 NEC - Kitchen Outlet Rules

Sdílet
Vložit
  • čas přidán 22. 07. 2024
  • It's not uncommon to fail a final inspection on a newly built home due to some issue with electrical outlets in the kitchen. Here's a few points from the 2020 NEC that all builders should be familiar with.

Komentáře • 157

  • @fortheearth
    @fortheearth Před měsícem

    Great information and beautifully presented. Thank you.

  • @icevariable9600
    @icevariable9600 Před 2 lety +3

    I'd like to see a video on all the outlets in the kitchen & laundry room, including the refrigerator, microwave, dishwasher/disposal, dedicated, which need to be GFCI protected and which is preferred, either 15A or 20A based on dedicated circuit or not. I know that both are allowed in the kitchen, but in the field we're putting in 15A outlets in the kitchen, unless it's a dedicated circuit, then it's a 20A outlet. Thanks for your video.

  • @anthonyhitchings1051
    @anthonyhitchings1051 Před 4 měsíci

    My toaster is plugged into the adjacent wall outlet (table height) at one end of the breakfast/dinner table. Actually, I have two receptacles at that location, on different circuits. When we remodeled the kitchen-dining area we made it NEC compliant.

  • @Calistogakid2u
    @Calistogakid2u Před 2 lety

    Is there a minimum counter depth (not width) that gives any exception to the spacing requirements? Renovation work has a pilaster that the counter notches around resulting in a counter section of about 33" in width by 14" in depth. It also happens to be at one end of the counter. Where do I start measuring? Thanks.

  • @gregorall9779
    @gregorall9779 Před 2 lety +3

    How does this apply with the cooktop directly behind you, would you simply restart the 2-4 rule from the opposite corner?

  • @martingonzalez529
    @martingonzalez529 Před 3 lety +1

    Well explained,thank you 👍👍👍👍

  • @JS-mx3he
    @JS-mx3he Před 10 měsíci

    What about the range oven is that included in the 4ft rule

  • @ronaldoleksy8264
    @ronaldoleksy8264 Před 3 lety +10

    20 amp combo breaker with Arc fault

  • @robertochavez8196
    @robertochavez8196 Před 3 lety

    Great explanation!!!

  • @robertandnancytrowsdale126
    @robertandnancytrowsdale126 Před měsícem

    Where do we find there angled outlets with led lighting?

  • @jolyonwelsh9834
    @jolyonwelsh9834 Před 3 lety

    Most blenders have 6' cords on them. Vitamix blenders have them.

  • @salty7346
    @salty7346 Před 2 lety +1

    My old house is about 3 outlets shy then. And my wife is wanting them NOW😳

  • @robertochavez8196
    @robertochavez8196 Před 3 lety +7

    Please upload more videos about codes! Thanks for sharing!!!

  • @billybilodeau1991
    @billybilodeau1991 Před 3 lety +20

    The code really says you must have outlets spaced so that at not point along the horizontal surface can you get further then 24” from an outlet. Which means if you have an outlet 30” from the end of a countertop, you don’t meet code. Also you must have an outlet where a countertop is 12” or larger. So if you have a small countertop between a cooktop and a double oven and its 11” wide you aren’t required to have one there.
    Oddly enough I’m about to install those flip up outlets for the first time and initially it was suggested to use a tower type. Never heard of them before now I’m bumping into them everywhere lol. Good basic video.

    • @SuperVstech
      @SuperVstech Před 3 lety +1

      This is incorrect.
      Any countertop over 12” must have a receptacle OUTLET, and 24” from edge is the maximum, but you can have UP TO 48” space between the receptacle OUTLETS

    • @billybilodeau1991
      @billybilodeau1991 Před 3 lety +3

      If you have them spaced at 48” can you get further then 24” from a receptacle?

    • @austinluepkes5484
      @austinluepkes5484 Před 3 lety +1

      @@SuperVstech I don’t see how what you said differs from what he said, no space can be 24” from an outlet. Just as no space along a wall in bedrooms, living areas, etc can be 6’ from an outlet.

    • @austinluepkes5484
      @austinluepkes5484 Před 3 lety

      @@billybilodeau1991 do you know if I can have my kitchen ceiling light and fan on the same circuit as my kitchen counter top outlets?

    • @billybilodeau1991
      @billybilodeau1991 Před 3 lety +1

      I don’t see why not but I wouldn’t only because its a waste of wire and 12gauge is harder to deal with. Older homes might have something like that because of how they were wired.

  • @MB-xq3ol
    @MB-xq3ol Před 10 měsíci

    What about 2 feet from the sink code

  • @thesauce807
    @thesauce807 Před 4 lety +3

    good stuff Sir!!

  • @davidkiser4758
    @davidkiser4758 Před 3 lety +6

    Don't you need a receptacle within 24 inches of a sink (both sides if sink is in middle of counter)?

    • @timwilson3150
      @timwilson3150 Před 3 lety +3

      No closer than 6” to the edge of the sink and no further than 24” from edge of sink.

  • @kylestorts3428
    @kylestorts3428 Před 2 lety +1

    Hey does anyone know where I can find code references for receptacles in a commercial kitchen or school kitchens? Or do the dwelling unit codes on receptacles apply to commercial kitchens as well?

  • @jeffstaunton1416
    @jeffstaunton1416 Před 3 lety +6

    This is very helpful! Maybe a video or some info about installing outlets in the gap above kitchen cabinets for light strips? If NEC compliant..

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety +5

      Strip receptacles are allowed to run along the bottom of the wall cabinets as long as they don’t exceed the maximum height allowed. When this is done it does make for a clean looking backsplash.

    • @SuperVstech
      @SuperVstech Před 3 lety +1

      @@HomesBuiltRight keep in mind, the receptacles, and receptacle outlets are different... a strip of receptacles less than 24” above a countertop would only count as a SINGLE receptacle outlet... no matter how many receptacles are in the strip.

    • @adamgagnon9506
      @adamgagnon9506 Před 2 lety

      Hard wire them and run spilt tubing and strap it

    • @melissag2219
      @melissag2219 Před rokem

      I would love to find documentation supporting this to show my builder.

  • @georgenarso3148
    @georgenarso3148 Před 3 lety +1

    My customer wants an power outlet inside a cabinet for sole purpose of pluging in an 1800 watt Fryer oven, is it acceptable to have an outlet like that inside the cabinet?

    • @SuperVstech
      @SuperVstech Před 3 lety

      Sure.
      It will NOT reduce the required countertop outlets though.

  • @brentrathgeber8629
    @brentrathgeber8629 Před 2 lety +1

    Can 'Pop ups' be installed in the underside of a cabinet and pop down? We will be getting granite countertops and backsplash and don't want do ruin the look of receptacles, thanks.

    • @HomesBuiltRight
      @HomesBuiltRight  Před 2 lety

      I would check with your local building official. In the end - it’s their decision that counts.

  • @hippo-potamus
    @hippo-potamus Před 2 lety

    Do the outlets on the same circuit have to be side by side continuous with each other? Or can you have 2 circuits 4 oulet duplex staggered. So instead of breaker 1 duplex outlets a and b, breaker 2 outlets c and d. Instead can you put it breaker 1 powers duplex outlets a and c, breaker 2 outlets b and d. ??

    • @andrewsalazar98
      @andrewsalazar98 Před rokem

      Minimum two circuits and so long as both circuits have GFCI protection and AFCI protection, stagger them however you’d like.

  • @kevinyork4757
    @kevinyork4757 Před 3 lety

    What about the rules for outlets on either side of the stove? Isn't there a minimum/maximum distance? I am getting ready to tile and one is 16" away, and the other is 15" away. I can only move the 15" to 16" but it is getting very close to the fridge. Comments?

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety +2

      They can go right up to a slide in range (just not behind it). You start measuring from the edge of the countertop at the range and then cannot exceed 24”. If yours are 15” and 16” from that edge you are OK.

  • @WardCo
    @WardCo Před 3 lety +1

    Does the 2020 NEC also require AFCI on outlets within 6 feet of the sink? (Potentially including dishwasher and disposal?)

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety +1

      Arc fault protection for receptacles in kitchens and laundry areas was actually added in the 2014 NEC. You’ll usually see combination AFCI/GFCI breakers for these areas.

    • @mikedabney3855
      @mikedabney3855 Před 3 lety

      @@HomesBuiltRight l m.j moo moo pub
      boo

    • @patrickkelley3408
      @patrickkelley3408 Před 3 lety

      @@HomesBuiltRight but it was in 2017

  • @Lonniejd
    @Lonniejd Před rokem

    I’m working on a remodel, I’d like to have undercabinet outlets. My question is, do the GFI‘s have to be installed inside the upper cabinets or can they be relocated someplace else. The issue is having the homeowner having to cut into very expensive upper custom cabinets and having to look at GFI reset circuits in their beautiful custom cabinets.

  • @davehancock7305
    @davehancock7305 Před 11 měsíci

    I've read that the same kitchen counter circuits may also power a refrigerator, a gas range, a clock, and even outlets in the dining room. Instead of serving only the counter area. Is this correct?

    • @dannyboycharter7698
      @dannyboycharter7698 Před 2 měsíci

      yes....but, what if the refrigerator manufacturers want their products on a separate circuit. Can the building inspector tell you to invalidate their product. Code says you can run more circuits, just the minimum is two 20 amp circuits. Say your ref takes 7 amps and your microwave takes 15amps. (just run another circuit for the ref and you cure these problems.)

  • @MrKen59
    @MrKen59 Před 2 lety

    What about accommodating microwave hoods? My kitchen is from 80s and while we have two circuits, there is a separate 20a for the refrigerator. I’m installing a microwave hood and wonder if the refrigerator/microwave can share same circuit. I’d love to see how this is all described in code. The total combined peak load is 2kw (1100+900). Thanks and great video. Nice and tight, clear to understand.

    • @HomesBuiltRight
      @HomesBuiltRight  Před 2 lety

      Thanks Ken. I defer all specific questions like this to your local Building Official or local electricians due to variable codes and ordinances. Thanks for watching.

    • @MrKen59
      @MrKen59 Před 2 lety +2

      @@HomesBuiltRight lol good answer.

    • @electricaf365
      @electricaf365 Před 2 lety

      @@MrKen59 they can share a circuit

    • @daby8399
      @daby8399 Před 2 lety

      @@electricaf365 no they cannot microwaves are too powerful and they should have their own dedicated circuit

  • @robertheard8853
    @robertheard8853 Před 2 lety

    what is the minimum distance from a sink on the backsplash can a CFGI outlet be installed

  • @heroknaderi
    @heroknaderi Před 3 lety +2

    Good to know

  • @OthmanAlikhan
    @OthmanAlikhan Před 2 lety

    Thanks for the video =)

  • @downtownPatna
    @downtownPatna Před 3 lety

    What about the outlet feeding the microwave? That's got to be above 20 inches higher than the countertop.

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety +2

      That one is not servicing the countertop. 20” rule applies only to those.

  • @robertfunicello2676
    @robertfunicello2676 Před 3 lety +28

    You failed to mention the circuits must be 20 amp. Otherwise,good presentation

    • @jolyonwelsh9834
      @jolyonwelsh9834 Před 3 lety +3

      In the 2020 code they also require arc fault circuit interrupter protection.

    • @jesusortiz6842
      @jesusortiz6842 Před 2 lety +1

      @@jolyonwelsh9834 I think if you use the gfci, you don’t need to install arc fault breaker

    • @zb9795
      @zb9795 Před 2 lety +2

      @@jesusortiz6842 GFCI does not protect against arc fault.

    • @electricaf365
      @electricaf365 Před 2 lety

      @@jesusortiz6842 you thought wrong

  • @prishalaguduva3517
    @prishalaguduva3517 Před 3 lety +2

    Thanks for the video. Can the GFCI outlets be placed under the cabinet (instead of backsplash wall). Do the codes allow it?

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety +4

      Yes. The face of the lower cabinet is doable under certain conditions. You would follow similar rules like the ones for islands. You could also choose the pop up style of outlets as well.

  • @daby8399
    @daby8399 Před 2 lety

    So there are three GFCI outlets in my kitchen, you're not supposed to use microwaves in GFCI a lot of appliances cannot handle the GFCI.
    I can't even use my appliances in my rental. I just moved in here and the GFCI can't even handle my microwave they don't have any dedicated outlets/ circuits

  • @Zest4life890
    @Zest4life890 Před 2 lety

    We have a new build with no gfci in our primary sink area, not up to code

  • @gregnelson7506
    @gregnelson7506 Před rokem

    Is that microwave plugged in two feet above the counter top?

    • @HomesBuiltRight
      @HomesBuiltRight  Před rokem

      Microwave outlet is in a cabinet above the unit. (This outlet does not serve the countertop)

  • @lancewolf2451
    @lancewolf2451 Před 2 lety +1

    Do all kitchen outlets need to 20 amp type?

  • @mikeriebe4240
    @mikeriebe4240 Před 2 lety

    What if there is a sink between the outlets?

    • @HomesBuiltRight
      @HomesBuiltRight  Před 2 lety

      Then you start measuring from the edge of the sink in each direction.

  • @Kubotajoesfarm
    @Kubotajoesfarm Před 3 lety

    Can knob and tube be made safer by installing afci breakers on the knob and tube circuits? Or is it best to shell out thousands to rewire.

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety

      I’m not an electrician. Best to contact a local professional and ask them this question.

    • @waterbug1135
      @waterbug1135 Před 3 lety

      I had a house with knob & tube and an electrician told me there's no need to replace it. That was his opinion for what that's worth. The insulation on that wire was very degraded, but still in place. If left undisturbed I assume it would be fine. I replaced it when I did a remodel though.

    • @mkidd8806
      @mkidd8806 Před 3 lety

      @@waterbug1135 just remember if you have existing knob & tube wiring that wiring CAN NOT be covered with any insulation etc, bottom line it must be exposed for air exposure including running down walls.

    • @davenag957
      @davenag957 Před 3 lety

      Shell out the thousands to replace it. It is extremely dangerous!!! Mice have probably chewed all the insulation off, the splices made over the 100 plus years that it's been in service are probably faulty. When that stuff was installed, the only load was lighting and maybe a receptacle in each room. Burning alive in a fire is a very bad way to die. I've been wiring for 40 years and I've seen a lot a bad stuff. Take my advice or buy a lot of good life insurance!

    • @salfitimina2376
      @salfitimina2376 Před 2 lety +1

      @@davenag957 OK, knob and tube is NOT "extremely dangerous ". It's just about common sense. If it's damaged or needs repairs then replace it ( just like anything else) . If you have a small basic house , few lights and a few outlets, it's not worth changing it to romex. Leave as is.
      On other hand, if you plan on installing insulation, remember knob and tube must be run in free air. If you plan on upgrading your service panel, remember almost every circuit needs to be AFCI protected ( usually with afci circuit Breakers). Problem is that knob and tube was installed with shared neutrals ( multi branch circuits ) . I only seen one manufacturer so far that actually makes an AFCI breaker for multi branch wiring. Also, I've heard about a couple home insurance companies refusing to renew existing policies unless the knob and tube was replaced

  • @Makinja
    @Makinja Před 2 lety

    Should the refrigerator be on a dedicated circuit and should the microwave also, be on its own circuit or included on one of the 2 circuits addressed in the video? Thanks

    • @HomesBuiltRight
      @HomesBuiltRight  Před 2 lety +2

      Electricians and code officials may have varying opinions. Technically, no. An over the range microwave does not require a separate circuit but most will supply one since the make and model of the unit can vary and there are code limits on the amount of power that little thing can draw. Fridge is similar. It can be on a shared circuit but really shouldn’t be based on the size of modern refrigerators.

  • @chrisf9607
    @chrisf9607 Před 3 lety

    2:49 where in the code book dose it say maximum 4 foot on center or mention 4 foot 2 foot im not trying to be a rude guy i realy am asking

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety

      In the 2018 IRC it’s in E3901.4.1 and the 2020 NEC has wording in 210.52(C). Hope that helps.

    • @chrisf9607
      @chrisf9607 Před 3 lety +1

      @@HomesBuiltRight thanks for the reply after reading 210.52c1 repetedly the detaill is recepticles shall be installed so that no point along the WALL LINE is more than 24" horisontaly from a recepticle. i so thought that ment recepticals every 2 feet infact ive done at least a hundred of peicework apartment kitchens like that but now i understand where the 4' came from even though i dont see 4' in the code book its because in the middle of the 4' is the 2' spot of WALL LINE between recepticals is still 2' from a receptical i think they should realy put the number 4 and 2 in the code book but thanks for the reply again i needed that clarified.

  • @phishertube
    @phishertube Před 2 lety

    Sink?

  • @MrRickoscar
    @MrRickoscar Před 2 lety

    Thats part of it ,,, how close to a sink can a outlet be?????

    • @HomesBuiltRight
      @HomesBuiltRight  Před 2 lety

      In line with the edge. (That’s why they need GFCI protection)

  • @chrisandrews7102
    @chrisandrews7102 Před 8 měsíci

    My refrigerator outlet was inside cabinet

  • @pragnesh02ee313
    @pragnesh02ee313 Před 3 lety +1

    Pop up outlet is allowed on kitchen floor?

  • @21gonza21
    @21gonza21 Před 3 lety +2

    You said 2 foot 4 foot, so no more than 4 feet, but what does 2 foot has to do?

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety +2

      Let’s say you have a toaster with a 24” cord. Anywhere you put that toaster on the countertop it should be able to plug in within a 24” span. (The 2’ rule). Therefore, outlets cannot be more than 48” apart along countertops. (Does that make sense?)

    • @21gonza21
      @21gonza21 Před 3 lety

      Dave Yelovich yess thank you! So does the 4 feet distance end where the sink goes? If so what would be the closest you can put an outlet to the sink?

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety

      Can go right up to the sink. Within 2’ of the edge of that sink you would need an outlet. (I know you wouldn’t put a toaster on the edge of your sink but that’s how the code reads).

  • @AndresPerez-tc5pr
    @AndresPerez-tc5pr Před rokem

    good video

  • @wesroberts7514
    @wesroberts7514 Před rokem

    Distance from end of counter

  • @Not2daysatan
    @Not2daysatan Před rokem

    What about under cabinets outlets?

    • @HomesBuiltRight
      @HomesBuiltRight  Před rokem +1

      Yes, under cabinet strips or individual receptacles are OK as long as they are not more than 20” above the countertop and the spacing rules are still adhered to.

    • @Not2daysatan
      @Not2daysatan Před rokem

      @@HomesBuiltRight thank you for the quick reply 😊

  • @majid_us
    @majid_us Před 3 lety

    Hello Dave, I am building a tiny house and it has a two foot wide countertop and the countertop has no backsplash (because of window). Can I place an outlet on the front of cabinet (where the sliding drawer is located in your video) just below the countertop level ? I also have open space on the side of the kitchen cabinet. Is it okay to place an outlet on the side of the cabinet? This will be similar to having an outlet on the face of the cabinet (just below the countertop level) except it will be on the side of the cabinet. Thanks so much in advance for any reply...

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety

      Sounds like you have an application similar to island rules - when they are all placed on sides. Check your local codes for tiny homes. They may be dealt with differently than houses in the IRC or NEC.

  • @Platerpus7
    @Platerpus7 Před rokem

    What happens if the gas range is 48 inches? Isn’t it impossible to get an outlet to be less than 4 feet apart?

    • @HomesBuiltRight
      @HomesBuiltRight  Před rokem

      The spacing rules apply to the workable countertops. You don’t count the range space.

    • @Platerpus7
      @Platerpus7 Před rokem

      @@HomesBuiltRight so the 4 feet would reset?

    • @HomesBuiltRight
      @HomesBuiltRight  Před rokem +1

      @@Platerpus7 yes. There would need to be an outlet to the left and right of the range - within 24” of the edge next to the range.

    • @Platerpus7
      @Platerpus7 Před rokem

      @@HomesBuiltRightI had a window in the way so couldn’t do it. Nobody is inspecting my house.

  • @dougbourdo2589
    @dougbourdo2589 Před 2 lety +4

    When I built my retirement home I frustrated my Electrician by doubling the number of outlets, Dimmable light switches and exterior outlets & motion sensor & decorative lights. (my wife's) ideas. Outlets every 4 ft. in the garage as well.

  • @Government-agencie
    @Government-agencie Před 3 lety +1

    I’m in a electrical class right now and he asked me how many circuits are required in a kitchen can you plz respond fast

    • @santinoconte4181
      @santinoconte4181 Před 3 lety

      2 at least

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety +5

      Thank you Santino. I just saw this. Good answer. That’s an open ended trick question though. Yes, 2 circuits for receptacles. But to be a “kitchen” by definition it’ll need some appliances. Each one has its own circuit. Range! Fridge? Disposal? Dishwasher? Trick question.....

    • @santinoconte4181
      @santinoconte4181 Před 3 lety

      Dave Yelovich very true. I’m an apprentice and have learnt a lot from your channel.

    • @timothybrady1174
      @timothybrady1174 Před 3 lety +1

      @@HomesBuiltRight what's the code for how many outlets on 1 circuit?

    • @mkidd8806
      @mkidd8806 Před 3 lety

      @@santinoconte4181 you should be asking your instructor during classroom studies. Next ask your journeyman your assigned to work under.

  • @jesuspadron7232
    @jesuspadron7232 Před 4 lety

    Have you had a situation where you have counter tops! But in other parts of the house like a game room or hall or even the utility to my knowledge this kitchen rule only apply in the kitchen! (Talking about the 2 feet 4 feet outlets) can you help me out thank you!

    • @jonbri4383
      @jonbri4383 Před 3 lety

      @T-RopE Have some respect...and He was not asking you Dude...

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety +1

      Countertop receptacle outlet rules as described in section 210.52(C) apply to kitchens, pantries, breakfast rooms, dining rooms and similar areas. That 2’ rule applies. If you had cabinetry with countertops in a game room or library (or other types of rooms not mentioned in the first sentence) the rules would be per section 210.52(A). In a nutshell, for “other countertop” areas those countertops are included as “wall space.”

  • @georgeryan9139
    @georgeryan9139 Před 3 lety

    Distence from sink and closest outlet.

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety

      Technically, there can be an outlet right on the edge of the sink - but not more than 24” from that edge.

    • @georgeryan9139
      @georgeryan9139 Před 3 lety +1

      @@HomesBuiltRight yah, though I wouldn’t like splashing water on the outlet. Maybe 23” would be better for my house. Never lived in a house the had one close to the sink. The code these days has so much in it, but one or two seem to get missed.

  • @patrickx2420
    @patrickx2420 Před 3 lety +1

    You cannot exceed 4 feet between outlets? Why? Why can't they be 5 feet apart???

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety +1

      Countertop outlets: If, let’s say, you place a toaster with a 24” cord between 2 outlets on a countertop, it should be able to plug in to the left or right. Code says maximum spacing for countertop outlets is 48”.

    • @dperreno
      @dperreno Před 3 lety +1

      Simple answer: because the code says so.

    • @davenag957
      @davenag957 Před 3 lety

      Because appliance cords are only 2', they don't want extension cords used for appliances. Extension cords cause fires. It's the same in other residential rooms, no more than 6' to any receptacle, with many details regarding short walls and fixed glass panels. All lamps come with a 6' cord, and again, no extension cords required when the electrician follows the code.

    • @electricaf365
      @electricaf365 Před 2 lety

      Wall spacing codes

  • @lanejohnson8552
    @lanejohnson8552 Před 3 lety

    I live in Massachusetts not sure if the rules differ but does every outlet have to be GFCI protected or is it just the first plug or outlet in the circuit?

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety +1

      If done at the outlet, yes, the first in line would work. However, many circuits are GFCI protected.

  • @Lughnerson
    @Lughnerson Před 8 měsíci

    No way in a kitchen with all the liquids, crumbs, and greasy fumes would I put outlets below the counter top.

  • @oddopops1327
    @oddopops1327 Před 4 měsíci +1

    👍👍😉

  • @arjumandvillagecooking

    Nice video🌹👏⚘❤❤❤

  • @martinbeirne7621
    @martinbeirne7621 Před 3 lety +4

    They are supposed to be arc fault breakers as well. You are better having combination breakers. It’s best leaving this to licensed electricians

    • @electricaf365
      @electricaf365 Před 2 lety

      They are actually called dual function breakers.

  • @djmystery7235
    @djmystery7235 Před 3 lety

    I just wanna know why my kitchen has a friggin coaxial outlet.

    • @kevinyork4757
      @kevinyork4757 Před 3 lety

      So you can have cable tv in your kitchen...

    • @djmystery7235
      @djmystery7235 Před 3 lety

      @@kevinyork4757 who wants that?

    • @kevinyork4757
      @kevinyork4757 Před 3 lety +1

      @@djmystery7235 Lots of people would put mini TV's under the cabinet so they can watch the news or soaps while cooking.

    • @Californians_go_home
      @Californians_go_home Před 7 měsíci

      Gen z’r ?

  • @bee4pcgoldrule592
    @bee4pcgoldrule592 Před 3 lety

    18" from edge of sink

    • @HomesBuiltRight
      @HomesBuiltRight  Před 3 lety

      A receptacle can be right next to the sink or up to 24” away from the edge of the sink. 18” is in that range.

  • @jdeschampselectrician
    @jdeschampselectrician Před 3 lety +1

    Gfci × afci...on kitchen
    Should be dual funtion breaker
    Or
    Gfci receptacle +afci breaker
    More easy to get dual funtion breaker
    And regular receptacles...
    Which will be protected from
    Panel with the dual funtion breaker

  • @nhankhuu5643
    @nhankhuu5643 Před 2 lety

    Island my dude

  • @johnwhite2576
    @johnwhite2576 Před 2 lety

    didn't comment on islands !

  • @do-py1fn
    @do-py1fn Před 2 lety

    Talk only? You have to do something

    • @eberthpineda3224
      @eberthpineda3224 Před 2 lety

      Outlets and lights can go on the same circuit?

    • @wellcraft2136
      @wellcraft2136 Před 2 lety

      @@eberthpineda3224 The Kitchen, Breakfast, Dining, Pantry branch circuits for receptacles are not permitted to have any other outlets connected to those circuits, including lighting outlets and or receptacles in other rooms.