Emergency service call on WIC not cooling

Sdílet
Vložit
  • čas přidán 11. 09. 2024

Komentáře • 12

  • @chanceh2405
    @chanceh2405 Před měsícem

    This video helped me a lot. The step by step was super helpful- thanks for the insight!

  • @bagtube
    @bagtube Před měsícem +1

    So that makes me your 1st Subscriber to Post! 😎 Looking forward to watching more of your content.

  • @marcoferreira226
    @marcoferreira226 Před měsícem +1

    nice work, good vid and step by step

  • @markcotter2355
    @markcotter2355 Před měsícem +1

    nice job, she was dirty.

  • @alejandrozometa1951
    @alejandrozometa1951 Před měsícem +2

    Just sub love any refrigeration videos

  • @WswRefrigeration
    @WswRefrigeration Před měsícem

    That coil will ice up again in no time with that thermostat. Should be capillary style sensing return air at one of the fan grilles

    • @RealWorldHVACR
      @RealWorldHVACR  Před měsícem

      Has not iced up sense 2 weeks later but appreciate the input!

  • @ErickHernandez93
    @ErickHernandez93 Před měsícem +2

    Unit looks like it can take a bit more of charge
    3 subcool & 40 superheat
    Evaporator superheat at least at 8-12°f
    Compressor superheat at least at 20-25°f
    Subcool you can get it to 8-12°f

    • @RealWorldHVACR
      @RealWorldHVACR  Před měsícem +3

      @erickhernandez93 cannot charge by sub cooling with a system with receiver. With a full sight glass and receiver filled to 80% she is charged. More superheat at condensing unit is due to about a 55 FT line set that runs in attic almost entire length. Appreciate the comment!

    • @ErickHernandez93
      @ErickHernandez93 Před měsícem +1

      @@RealWorldHVACR mentioned as i saw pressures based on box temperature still above 40’s but that’s good man