LOOSE WIRES CAUSE FIRES 🔥 - A TORQUE SCREWDRIVER WON'T HELP!

Sdílet
Vložit
  • čas přidán 27. 08. 2024

Komentáře • 79

  • @TheCraig031272
    @TheCraig031272 Před 2 lety +23

    proper visual inspection & then a good tug test of terminated ends always makes sense

  • @dennisphoenix1
    @dennisphoenix1 Před 2 lety +13

    Bring back the old brown wylex consumer unit . 2 screws for every connection, lives neutrals and tails . No flimsy caged terminals. Also put ferrules onto meter tails , this would stop the splaying of the individual strands . Hager supplied tail ferrules with their consumer units years ago . They were clearly ahead of their time

  • @_______DR_______
    @_______DR_______ Před 2 lety +10

    With tails I always flatten a bit with pliers, terminate, and wiggle/re-tighten a couple of times. And another one: when doing a board is tighten as you go, but always to a full check of every terminal top left to bottom right before the lid goes on.
    I will admit until recently I haven't been a big user of the torque screwdriver, and even now I find it a bit funny that the importance of torque values (which i do not doubt are important) is stressed for distribution boards/consumer units, but its fine to use your own judgment for almost everything else. I've seen just as many cooked terminals in electric shower units and their isolation switches as I have in any switchgear enclosure.
    I also have to wonder, do all DNOs and suppliers insist on using torque drivers when they put their plastic cutout and meter on the bit of cheap chipboard that goes under our nice non-combustible/torqued up consumer unit? 😂

  • @chrisardern4594
    @chrisardern4594 Před 2 lety +14

    Maybe if the manufacturers started to use terminal screws that dont strip before you get to the torque setting might help.

    • @tommymack3210
      @tommymack3210 Před 2 lety

      Most breakers use PZ/SL 2 slot.
      And there exists PZ/SL 2 screwdriver.

    • @chrisardern4594
      @chrisardern4594 Před 2 lety +3

      @@tommymack3210 can't argue with that but I still stand on what I say about the very soft screws used by manufacturers.

    • @MS-Patriot2
      @MS-Patriot2 Před 2 lety

      @@tommymack3210 can you recommend one that is narrow enough to fit deep slots on some RCBOs please?

    • @jonanders76
      @jonanders76 Před 2 lety +1

      Totally agree. The poor manufacture of even expensive equipment is appalling now days and it seems to be getting worse. Why aren't all the screw heads, on all boards and accessories deep terminals with hex heads, as per most DNO equipment? Just seems a no brainer to me.

    • @ef7480
      @ef7480 Před rokem

      @@jonanders76 - maybe they do not buy into the 'over engineering' of 'potential fires' in consumer units....

  • @j.f5212
    @j.f5212 Před 2 lety +11

    Use an isolator with round holes specifically for meter tails. Henley blocks also have round holes.
    Most DNO'S and suppliers now use the Proteus double screw round hole iso.

    • @dennisphoenix1
      @dennisphoenix1 Před 2 lety +1

      It would be easy enough for the consumer unit manufacturers to make the incoming side of the main switch with round terminals , even if they keep the cage design .

    • @jonanders76
      @jonanders76 Před 2 lety +2

      @@dennisphoenix1 Or better still, the manufactures stop this race to the bottom with extremely shallow cage clamp terminals (expecting the installer to somehow overcome their poor design) and use round tunnel terminals, with double screws for the main switch & larger OCPDs & accessories. And the main one, for christ sake get rid of these useless plus/minus screw heads, which are always made of the softest metals known to man, and use hex heads like the DNO equipment.

    • @AndrewStrydomBRP
      @AndrewStrydomBRP Před 2 lety +3

      ​@@jonanders76 I'd hope they switch to torx as it is superior to Hex since it has more surface area for the driver to catch on, that's why wera made "Hex plus" to try and solve the issue of screws rounding out.

  • @johnmilla358
    @johnmilla358 Před 2 lety +3

    Experience is key. Efixx is a reminder. Common sense is a requirement. Nice video

  • @markkennard861
    @markkennard861 Před 2 lety +7

    Focus on the terminal hole size. The conductor should be twisted (for stranded conductors)and folded so as to fill the hole with as much copper as practical. Visually examine every termination as you go and then check every terminal again when finished. If you making bad connections it might be time to give it up..

  • @PraxZimmerman
    @PraxZimmerman Před 2 lety +3

    Cross-threaded bolts. See it a lot on screw-in battery terminals. Bolt gets stuck, but you got the right torque on it, so everything must be fine right? But the cable is totally loose.

  • @edhunter84
    @edhunter84 Před 2 lety +1

    As a meter engineer, I lean towards flattening out the cable strands except when its really fine multi strand as it tends to get cut by the terminal screws.
    I cleat the consumer unit tails to the board after de-energising but before removing them from either the meter outlet or isolator. Always try and swap any single screw/clamp terminal isolator for double screw. I have a method of doing a final check for tightness before sealing up and everything gets a little tug test.
    Had cutouts where the DNO haven’t tightened anything.

  • @oal2928
    @oal2928 Před rokem +1

    Professionals don’t use torque because they want to, it’s because if something goes wrong they can blame the manufacturer. It’s about responsibility transfer, from the user to the manufacturer.

  • @andysims4906
    @andysims4906 Před rokem +1

    In the old days it was rare to have problems with the old Wylex consumer units where every live and neutral terminal had 2 screws.
    Lots of the old wylex had wooden backs. Guess what we were told we couldn’t use them as the wood was combustible and we had to use plastic consumer units . What a joke the plastic ones were 20 times more combustible

  • @Poorlybobsdad
    @Poorlybobsdad Před 2 lety +1

    When in any fuse box, I routinely go left to right, top to bottom to check terminal tightness. There’s usually some loose.

  • @posei3960
    @posei3960 Před 2 lety +2

    So,why are the ferrules on cable called "bootlaces ferrules" and the ferrules on Bootlaces are called Aiglets? Just curious

  • @JorgeAMG187
    @JorgeAMG187 Před 2 lety +2

    Absolutely schocking that you guys over there still use Screws on anything.. sockets,switches,light fitting,terminals in 2022.

  • @muzikman2008
    @muzikman2008 Před 2 lety +6

    I always said from when torque settings were introduced to regs, it's a nonsense, because you can tighten a screw up to a certain torque, wiggle it, it will come looser, tighten it again, wiggle it, it will again come loose, copper is a malleable metal, and no amount of torque will make it 100% secure, but not moving the conductors will stabilise that movement and reduce its looseness in a terminal. I think cage terminals should also be circular to accept circular conductors.. Not square!.. Seems like mcbs/rcbos are designed solely for flat bus bar. The Conductor end clamp should be round or semi circular. Seems an easy fix to me but hey ho..

  • @davidclark3603
    @davidclark3603 Před rokem

    We have all come across the over tightened screw in a socket where one side of the screw slot has broken off! Or, one wire has acted a a fuse and blown off in a fault leaving an open ring! Over tightening a screw isn't doing anyone any favours. It's nearly as bad as under tightening! Good video again!

  • @darylsavage119
    @darylsavage119 Před 2 lety +2

    It's 2022, wheres wago RCBOs? Saves any messing about with torque screwdrivers, and if manufacturers are smart about it, it'll stop DIY DAVE putting a 3rd 2.5mm into a 32a

  • @raychambers3646
    @raychambers3646 Před 2 lety +4

    There are two types of tight
    1tight .
    2stupid tight .

  • @G1ZQCArtwork
    @G1ZQCArtwork Před 11 měsíci

    Henley blocks and old Wilex boxes their twin screws, can't beat them.
    55 years in the business, (now retired) never owned a torque screwdriver, there simply is no substitute for a good feel and common sense.
    Physics exams state, measure twice. Carpenters measure twice cut once. These values are not taught today.
    Youngsters today will rely too much on that click, and not really have the experience of the correct feel.

  • @gavkit
    @gavkit Před 2 lety

    Awesome guys nice to see information like this making it out to a wider arena

  • @nocode1603
    @nocode1603 Před 2 lety

    I always find once you have put away your ends in the mcbs or main switch I always try leve my connections abt 15mins or so & more often than not you will get a good quarter turn on your connections that tip was passed on to me by an older experienced guy at the time & for me it's just a final wee nip up 👍

  • @jameshorspool5054
    @jameshorspool5054 Před 2 lety +1

    I agree with the extendable flip mirror to check ✔ ✅ 👌 😉 got myself one, I must say fantastic work, thankyou for your amazing and informative videos 📹.

  • @andrewdale5473
    @andrewdale5473 Před 2 lety +3

    How much contact do wago connectors make with the cable compared to screw terminals?

    • @HenryLoenwind
      @HenryLoenwind Před 2 lety +2

      You have to do something really weird for WAGOs to not have near perfect contact. That's the advantage of springs over screws---they automatically re-tighten themselves.

    • @JasperJanssen
      @JasperJanssen Před 2 lety +2

      The springs actually make very little contact, but it’s not degraded by movement (it gets better, if anything) and that makes it Enough for their rating.

    • @HenryLoenwind
      @HenryLoenwind Před 2 lety +2

      @@JasperJanssen The springs are just there to push the conductor against the busbar, they are not required to conduct themselves.

  • @KendalMike
    @KendalMike Před 2 lety +1

    This is another reason why 100 amp DP isolators should be mandatory. Any new CU change should include a 100 amp DP isolator. Any subsequent meter change will not disturb the tails within the CU. Any meter change where there is no isolator should be forced to also install an isolator and check inside the CU main isolator for tightness.
    New CU or new meter, whoever's there first should install an isolator. Sadly, there's a lack of joined up thinking in the industry and too much passing the buck.
    Mike.

  • @BYENZER
    @BYENZER Před 2 lety +2

    Stranded wire? FERRULE IT! What?? I SAID: "STRANDED WIRE? Put a BLOODY FERRULE on it!!! PERIOD.

  • @tanveerkhan9221
    @tanveerkhan9221 Před 2 lety +1

    Boot lace ferrules should be used on all screw down terminals

  • @samplumbe3288
    @samplumbe3288 Před 2 lety

    In my experience as a competent DIYer and site manager, the worst places for potential fire and burn out in sockets etc that I have seen is with electric shower supplies. Found 3 now. Damn lucky that each time the fire never spread but the fittings were badly damaged. Always hard to tell how tight or not they might have been after it has all melted. One consistent thing I have found though is they were all damp with corroded wires still evident with plenty of green corrosion on the copper. Found it a couple of times in other sockets as well but more of a tripping issue than fires. So a big issue in the millions of old homes with solid masonry walls and no DPCs I guess.

    • @TheFool2cool
      @TheFool2cool Před 2 lety +3

      I think the "corrosion" is actually evidence of long term thermal damage, I've seen it on quite a few things that have been hot for a long period.

    • @petermichaelgreen
      @petermichaelgreen Před 2 lety +3

      The good thing with traditional UK electrical accessories and patress boxes is they tend to be made of thermosetting resins like Urea-Formaldehyde which are pretty good at retaining their integrity under exposure to excessive heat. So a loose connection on a shower circuit does severe damage to the accessory but the problem generally remains contained within the accessory and it's box.
      Plastic din rail enclosures (used for consumer units before the "metal consumer units" rule came in) OTOH tend to be made of thermoplastics like ABS which are much worse at retaining their integrity in overheating scenarios (though much better from an impact resistance point of view).

    • @samplumbe3288
      @samplumbe3288 Před 2 lety

      @@TheFool2cool good point. In the cases I have found the masonry has been damp which is why I have assumed dampness/moisture as the issue. Sometimes I have had to make the call to get the sparky to replace the in wall back boxes with surface mounted ones. I had to do the same for BT master sockets in my own house as 3 of them fried themselves before I realised the problem. Once surface mounted it was fine.

  • @infinitybeyond6357
    @infinitybeyond6357 Před 2 lety +2

    why aren't all stranded wire termination be crimped?

    • @efixx
      @efixx  Před 2 lety

      would be good to see - but it doesn't happen in the domestic setting

  • @BerkeleyTowers
    @BerkeleyTowers Před 2 lety +3

    Busbar misalignment..... Love the Crabtree Starbreaker for it's plugin, impossible to screw up, arrangement.....
    IEEE Entrance Exam;
    1. Which of the following is likely to cause a catastrophic house fire?
    a. The DIY rats nest, which is technically sound, and has tight connections.
    b. The neatest, most expensive job in the world, where no care has been paid to correctly tightening connections.

    • @efixx
      @efixx  Před 2 lety +2

      Wise words Paul! - tidy doesn't always mean the best.

  • @trespire
    @trespire Před rokem

    Visual inspection every time, a good light and "dentist" mirror.

  • @normanboyes4983
    @normanboyes4983 Před 2 lety +1

    Crimped ferrules on all stranded should be in the British Standard. Whatever tools you may use, remember it is a bad workman who blames his tools.

  • @timboha8191
    @timboha8191 Před rokem

    Tight is tight, a trained hand can feel the limit of the screw.

    • @efixx
      @efixx  Před rokem

      Worth watching 👇🏻
      You'll be Shocked By How Much Torque Changes Electrical Resistance
      czcams.com/video/EB-Zh89nHnk/video.html

  • @timballam3675
    @timballam3675 Před 2 lety

    Seen many a burnt out contactor screw terminal.....

  • @DeviloftheHelll
    @DeviloftheHelll Před 2 lety +1

    thats a properly thightened connection right there :D throw away those torque screw drivers and they wont bite you in the ass later. m12 bolt on a 300mm2 lug was tightened with torque wrench set to 80nm i was able to move the lug and we ended up using a regular wrench and tightened till it was held in place, no issues years later, as for the rating on the terminals that is a joke it will come loose within a year mostly, we can argue about it thats why maintance is important, but if you tighten it by hand good it wont come lose, if the breaker breaks when thightened all the way its a crappy construction.

  • @joopterwijn
    @joopterwijn Před rokem

    Just a question, with stranded wiring should you not default use a crimp sleeve? And a remark about torque, if find it often rather difficult to find the specs specifically on older stuff.

  • @rondo122
    @rondo122 Před 2 lety

    excellent videos chaps!

  • @Buzzer
    @Buzzer Před 2 lety +5

    I'm being taught atm. I've been taught to always tighten terminals give the cables a good pull to check. Then once everything is finish go around for a final check as by then the copper strands should of settled in place. None of the sparkies that teach me have used a torque screwdriver or think they're worth it so long as you got half a brain and don't under torque.

    • @gggggppppp
      @gggggppppp Před 2 lety +4

      Worked in the game 16 years and never used a torque screwdriver it’s a utube sparky thing. I think I seen one bloke use one once. These lads are sponsored to sell tools

    • @Easydread
      @Easydread Před 2 lety +1

      Technology move on & the torque screw driver is not the cure for all problems. I've been in the game for 30 yrs and never used one. I think like most things the price of these are way to expensive plus it needs calibration after 12 months £££ I would be sticking to my screwdriver and to date I have not had to make a claim on my public liability 🤑

    • @ef7480
      @ef7480 Před rokem +1

      @@gggggppppp - 'Well your honour, I didn't think that the manufacturer's instructions would ever come back and bite me on the arse. Didn't realise how the legal system worked... '

  • @boblewis5558
    @boblewis5558 Před 2 lety +1

    More grist to the mill for my favourite gripes:
    1. IRRESPECTIVE of the cable type ALWAYS use the right sized ferrule. Even solid core cables benefit due to the extra crush resistance. Ideally for screw terminals use a quad crimper and set the ferrule flat side up when screwing down and use a hex crimper when fitting into cage clamps.
    2. Fires inside CU's would RARELY if EVER happen if a proper temp sensor of below 85° were fitted and triggering - a contactor (resettable type that consumes zero power in normal use (nc contacts) opens on a fault and will not reset except manually. No high temp ... NO fire!
    In the worst case even causing rcd or rcbo tripping to isolate when a temp fault occurs.
    3. WHY are busbars fitted below not above the breakers where they should be? Yes I know UK breakers suck with stupid flying neutrals instead of proper double pole RCBOs and standard breakers too . Top in bottom out SHOULD be the norm not what we have now. MUCH easier to check for a single cable connection in the bottom rather than the mainly hidden busbar under insulation. At the top the busbar connections can EASILY be seen!

  • @andybakr
    @andybakr Před 2 lety

    Spot on guys, 👍

  • @MrDONPJ
    @MrDONPJ Před 2 lety

    Crimping leg terminal solutions

  • @gordonshumway9675
    @gordonshumway9675 Před 2 lety +1

    Should low voltage (12-24V) terminals also be torqued down? Is it considered good practice or overkill?

    • @efixx
      @efixx  Před 2 lety +6

      Low voltage is higher risk - higher currents and I2R losses! - we've seen LED strip installs cause fires!

    • @gordonshumway9675
      @gordonshumway9675 Před 2 lety

      @@efixx Thanks for the response. Thankfully I don't deal with high current stuff, but you never know when you are going to start. Gonna start saving for a Wiha.

    • @deang5622
      @deang5622 Před 2 lety

      Voltage does not cause heat. It's current that does. Are you a qualified electrician?

    • @ef7480
      @ef7480 Před rokem

      Extra low voltage...

  • @colinpenfold2971
    @colinpenfold2971 Před 2 lety

    The problem with reliance on torque screwdrivers, IMHO, is it depends on the medium being tightened. Copper is ductile, and I think we need to encourage a common sense tug test mentality. I have experience in aviation maintenance, torque loading is normal 'steel to steel' I am not so sure with this 'copper to brass' obsession.

  • @secozbay
    @secozbay Před 2 lety

    Thanks

  • @t.k.tronix0815
    @t.k.tronix0815 Před 2 lety

    does anyone know the Estation Smart from Innogy and the house connection box ... 2 brass crimped cables under a U-clamp ... I saw so much bad things done by Superstar Electricians

  • @tarassu
    @tarassu Před 2 lety

    So much whine around strands twisting out. You guys there in UK. Have you heard anything about ferrules? Absolute fail if not installed on fine stranded wires here....

    • @efixx
      @efixx  Před 2 lety +1

      Ferrules on class 2 conductors is a grey area.
      see discussion in the video - czcams.com/video/Ia13o1I6DkM/video.html

  • @HenryLoenwind
    @HenryLoenwind Před 2 lety

    Unguarded clamp terminals should be banned. There's no reason to use them over guarded ones, other than the manufacturer saving 1/10 penny worth of material...

  • @Dave_Audits
    @Dave_Audits Před 2 lety +2

    Torx screwdriver, waste of time and dangerous. Just use a screwdriver, give the cable a little wiggle while you tighten up the cable and you will always know you got it properly 😎

  • @justme5384
    @justme5384 Před 2 lety

    I still fit plastic consumer units. Cheaper than metallic

  • @UberAlphaSirus
    @UberAlphaSirus Před 2 lety

    My mate has a calibrated nipple. exactly 1mt from his finger tips.

    • @stevethomas5849
      @stevethomas5849 Před 2 lety

      I believe we are all blessed with this accurate measurement. A flook of nature .

  • @seandempsey7351
    @seandempsey7351 Před 2 lety

    So I am right after all 🤣 use torque screwdriver is a complete waste of time, as as you have just proved with the main switch demonstration, I have said before for if you put a single conductor in the terminal then double the over the ends as it gives the screws a bigger area to clamp down on . Gaz that’s what you tort your Lerner’s for 19 years and it is how you and I were tort .
    Fantastic video guy’s as always
    👍❤️👍👍👍👍

  • @andrewthomas405
    @andrewthomas405 Před rokem

    Torques don’t have the FEEL that a competent electrician has