Earth fault loop impedance testing - ZS

Sdílet
Vložit
  • čas přidán 24. 05. 2023
  • Yo!
    In this video i run trhough the full process of earth fault loop impeadance testing and about of the theory behind the ZS test.
    If you enjoy electrical content please subscribe to the channel and checkout my links below 👇
    M Y W E B S I T E ⚡
    residualcurrent.com/
    M Y L O A D O U T 🛠️
    residualcurrent.com/pages/loa...
    B I G B O O T S D I S C O U N T 🥾
    bigboots.co.uk/?ref=4s3760y77o - Use code RESIDUAL
    U N I L I T E D I S C O U N T 🔦
    unilite.co.uk/?ref=RESIDUAL - Use code RESIDUAL
    J O I N T H E C H A N N E L 🤝
    / @residualelectrical
    I N S T A G R A M 📷
    / residualcurrent
    T I K T O K ♪
    vm.tiktok.com/ZM86U2jjG/
    The works carried out in the video and the opinions shared are my own, and not representative of the associates and companies in the video.
    This content is purely for entertainment purposes and is in no way a "how to", tutorial or educational video.
    Please consult an electrician when dealing with any electrical installations.
    #electricianlife #electrical #electricalengineering
  • Věda a technologie

Komentáře • 28

  • @staypufttechtank
    @staypufttechtank Před rokem

    Thanks for run through - nice video, well explained!

  • @pinchermartyn3959
    @pinchermartyn3959 Před 9 měsíci

    Excellent run through of what it is. Thanks

  • @corymac
    @corymac Před rokem

    Great video as always Mike 👍🏼

  • @thomassparling5956
    @thomassparling5956 Před rokem

    Brilliant 👏 thanks 👌🏻

  • @gordonkerr6740
    @gordonkerr6740 Před 5 měsíci

    Thank you. That was very well presented. Well done you. Infact first class.

  • @miezankacou3455
    @miezankacou3455 Před rokem

    I really appreciate

  • @electrician247
    @electrician247 Před rokem

    The most important test 🙌❤

  • @kyledixon3464
    @kyledixon3464 Před 11 měsíci

    Very good videos

  • @TheHomeent
    @TheHomeent Před rokem

    Great content as usual.
    Keeping things simple, thinking about a teaching career when you're too old to be on the tools?
    Honestly if you lost any one then they need to go back to class. Best info for me was the quick summary on the fact different testers call it different things but the basics of hi and low (trip and no trip) and that most require 3 wire test on low.

  • @looking9175
    @looking9175 Před rokem +2

    I think with your tester doesn't have to be a 3 lead test for low. Easier to use 2 lead low. Just change setting with F1 button.

  • @Oufg103f
    @Oufg103f Před 6 měsíci

    Can I test Zs on a lighting circuit with led fitting which lit up? Cheers

  • @electricalservicesmaroc

    Pro ❤❤🎉🎉

  • @sajeevipiumika4033
    @sajeevipiumika4033 Před 2 měsíci

    Is this for TT system?

  • @ELECTRICLIFE4U
    @ELECTRICLIFE4U Před rokem

    👍👍👍👍👍

  • @PHealey1981
    @PHealey1981 Před rokem

    What’s the motor whirring in the background?

    • @PHealey1981
      @PHealey1981 Před rokem

      Sorry for going off the point, little Schneider VFD’s in that panel or softstarts?

    • @PHealey1981
      @PHealey1981 Před rokem

      @@residualelectrical noo, don’t apologise.
      Loop testing description whilst in a panel is my jam mate. 😆😆😆👏🏻👏🏻👏🏻👏🏻👏🏻👏🏻

  • @gino2465
    @gino2465 Před rokem

    No volume

    • @gino2465
      @gino2465 Před rokem

      @@residualelectrical appoligies it was connected to my car . Dah

  • @three-phase562
    @three-phase562 Před rokem +1

    Sorry, but stating that impedance and resistance are the same isn't the best approach in my opinion.
    Impedance is resistance to AC current and the resistance value is purely the DC component. From your distribution board out along the final circuit which is just a cable, then yes, the impedance and resistance will be the same as the cable has no reactive component to it. That is why it is just measured with a resistance meter.
    However, as you go back into the DNO supply from the distribution board and come to the transformer secondary winding, that does have both a resistive and a reactive element and the two added together will give the impedance. It therefore, must be measured with an AC Test Current.
    If you measured the the DC resistance of the earth loop, you would get a lower value than if you measured the impedance value. The impedance value is more reflective of the actual fault current, where as the DC loop measurement would give a higher fault current, that the system would not be able to supply in reality.

    • @TheHomeent
      @TheHomeent Před rokem

      If it wasn't "basically" the same how could you add R1 and r2 to Ze.
      Yes Z is a measurement of resistance at a given frequency, but a straight run of copper should have negligible difference between Z and R, now a motor winding or an indicator coil or anything that produces a reasonable magnetic field then Z is greatly affected in relation to R.

  • @eddtheduck
    @eddtheduck Před 11 měsíci

    Why would be listen to you when you’ve only ever installed 1 earth rod?

  • @tombarrett1487
    @tombarrett1487 Před rokem

    1st view!