How to reset error code U4 (VRV4)

Sdílet
Vložit
  • čas přidán 27. 08. 2024
  • Brand : Daikin VRV4
    model : FXMQ63PVE(indoor)/RXQ8AYM(outdoor)
    error code : U4-01
    Error code U4
    System Comunication Fault.
    This is a communication issue between the indoor and outdoor unit's.
    This fault can be caused by the outdoor unit being powered down or a BS Box or fan coil
    also bring powered down.
    When any of these things happens it cause confusion in the communication protocol and stop everything communicating correctly. Please check and restore power to any equipment if this is the cause.
    1)check all indoor unit power supply
    2)check outdoor unit power supply.
    3)On back if any switch trip and reset outdoor unit
    4)If any indoor and outdoor part's incoming is okay, please check the pc board or communication wire
    5)If pc board or communication wire is faulty, please replace it.
    #Daikin #VRV4 #bonmj

Komentáře • 68

  • @IvanToman
    @IvanToman Před rokem +1

    Same here on 20+ years old Daikin inverter. Power cycle of the whole equipment "fixed" the error. Weird... but thanks for the idea :)

  • @welcometomydreamworld6812

    Thnxx for information

  • @expertair8641
    @expertair8641 Před 3 lety +2

    Good work sir

    • @BonMj
      @BonMj  Před 3 lety +1

      Thanks

    • @expertair8641
      @expertair8641 Před 3 lety +1

      @@BonMjsir Daikin VRV 4 single outdoor one compressor faulty please e

    • @BonMj
      @BonMj  Před 3 lety

      @@expertair8641 the only way is replace compressor.

    • @expertair8641
      @expertair8641 Před 3 lety +1

      @@BonMj AC all brand work sir

    • @expertair8641
      @expertair8641 Před 3 lety +1

      You

  • @nilorcruzimjr1738
    @nilorcruzimjr1738 Před 7 měsíci +1

    verry good job

  • @scottyd035ntknow
    @scottyd035ntknow Před 2 lety +3

    This just happened to me. The unit is mounted pretty high up on the house so I just killed power completely. Waited 120 seconds and made sure all the breakers were set before hitting the main so everything came on in sync. AC back. Hopefully was just a glitch from a bad breaker we had last week.

  • @sonuradheshyam8771
    @sonuradheshyam8771 Před 3 lety +1

    Nice information

  • @jiezhang730
    @jiezhang730 Před rokem +1

    Hi, my Daikin R407C has U4 code. Can you please give me some idea how to rest it? Thank you

  • @robertperez2296
    @robertperez2296 Před 2 lety +1

    Bon I have a VRV4 that gets the U4-01 errors 2-3 times week. When we cycle off the unit it works for a couple day and then the error comes back. What are your thoughts?

    • @BonMj
      @BonMj  Před 2 lety +2

      Check indoor unit got link to smoke detector or fire alarm.
      May the alarm cause error U4.
      By my experience,the kitchen smoke detector intermittent short circuit cause aircon erreo U4.

  • @sewashton1048
    @sewashton1048 Před rokem +1

    请问一下,我的daikin 也是出现U4,是需要联络daikin 的technician还是其他technician也行呢?

    • @BonMj
      @BonMj  Před rokem

      有经验的都可以,如果你担心就直接联络Daikin

  • @muthuarun8341
    @muthuarun8341 Před 3 lety +1

    Hello sir..., thanks you for sharing your knowledge sir.what is the minimum thermistor value sir.pls replay sir.,

    • @BonMj
      @BonMj  Před 3 lety

      Daikin is 16k ohms by ambient temperature around 30c

    • @muthuarun8341
      @muthuarun8341 Před 3 lety +1

      @@BonMj thanks you sir.,

  • @ajaybedia1154
    @ajaybedia1154 Před 2 lety +1

    Hi sir ,
    In vrv 4 unit ,, connected 12 indoor unit and only 1 unit show u4 error and all 11unit cooling ok . What's the problem?

    • @BonMj
      @BonMj  Před 2 lety

      Check comunication wire

  • @Louisyongcool2328
    @Louisyongcool2328 Před 2 lety +2

    Hi bon, do you have video for daikin u8 error code please thanks

    • @BonMj
      @BonMj  Před 2 lety +1

      Dun have.
      Check the remote controller main/sub setting

    • @BonMj
      @BonMj  Před 2 lety +1

      If wallmounted,please check the main/sub switch at receiver pcb

    • @Louisyongcool2328
      @Louisyongcool2328 Před 2 lety +1

      Thanks bon i have a look in the indoor pcb

  • @laworder6092
    @laworder6092 Před 3 lety +1

    Cheers.

  • @hinlawkok5318
    @hinlawkok5318 Před 3 lety +1

    Teacher, I like to see ur video how to do multi condensing pump down system. Let said indoor one unit eev v body choke. How do I do pump down system?

    • @BonMj
      @BonMj  Před 3 lety

      I suggest you manual pump down better.

  • @manganyibright9415
    @manganyibright9415 Před 2 lety +1

    I have the same problem for vrv3. But mine still the condenser is not running

    • @BonMj
      @BonMj  Před 2 lety

      May be insufficient gas

  • @gothandaraj860
    @gothandaraj860 Před 3 lety +1

    Hi vrv 4 model 18 hp master and slave unit I'm changed for control pcb for master unit then I'm switch on the AC AC start but 10 number indoor that all AC is bringing for timer what's the problem

    • @BonMj
      @BonMj  Před 3 lety

      What is the error code, you try off and on back power supply,afterthat need to test run.

    • @gothandaraj860
      @gothandaraj860 Před 3 lety +1

      @@BonMj I'm that AC contr PCB is defective so I'm changing the control PCB and I do test run but indoor unit is timer lite is blinging

    • @BonMj
      @BonMj  Před 3 lety

      @@gothandaraj860 what is the error code.
      Are you set the deep switch

    • @gothandaraj860
      @gothandaraj860 Před 3 lety +1

      @@BonMj m yes I set dip switch settings but is not working

    • @BonMj
      @BonMj  Před 3 lety

      @@gothandaraj860 dun set dip switch.
      Adjust back to off.

  • @julienst6509
    @julienst6509 Před 3 lety +1

    Thanks @bon Mj. Do you know how to bypass U4 when at least x1 indoor unit shut down ? (breaker off ) ? Thanks

    • @BonMj
      @BonMj  Před 3 lety +1

      Off outdoor power supply and on back , press reset button.
      If the indoor pcb faulty, suggest u take out the communication wire and reset.

  • @arosharosh6660
    @arosharosh6660 Před 2 lety +1

    All indoor unit same like this

  • @yaoyiu5997
    @yaoyiu5997 Před 2 lety +1

    有一台vrv 全部室內出u4 outdoor 有電源 電相正常 hp2長閃 hp3 hp8 長亮 master control 閃燈 怎麼辦

    • @BonMj
      @BonMj  Před 2 lety +1

      试关电十五分钟再开会,按reset多过5秒

    • @yaoyiu5997
      @yaoyiu5997 Před 2 lety

      @@BonMj 試一下 謝兄地

  • @janshaw5472
    @janshaw5472 Před 2 lety +1

    今天check 到一台4mks 80 三台内机blinking 出U4 . 发现CU control board 没有灯显示。reset了也不行!不确定是filter board 还是control board 坏!直接让他换了台外机!

    • @BonMj
      @BonMj  Před 2 lety

      这个model问题比较多

  • @karthikdhonithala9708
    @karthikdhonithala9708 Před rokem +1

    👍👍👍

  • @user-ri6lv5lp9u
    @user-ri6lv5lp9u Před 9 měsíci +1

    Vrv 4
    Last time fcu 4 use now 3 only how tow to rest

    • @BonMj
      @BonMj  Před 9 měsíci

      Off outdoor power supply and on back, press return button more than 5 second to reset

  • @JoseANTONIO-hl7yp
    @JoseANTONIO-hl7yp Před 2 lety +1

    Hello sir, I have a similar problem, when I try to perform a test operation by pressing BS2, in T01 I get the error U403. I have 6 cassette and all with thermostat, with 1-10 it recognizes the 6 cassettes, and when I perform the test 2-05 it also works for me, but the starter does not perform it. how can I solve that. Thank you.

    • @BonMj
      @BonMj  Před 2 lety +1

      If auto charging system, you need to auto charging after that test run

    • @JoseANTONIO-hl7yp
      @JoseANTONIO-hl7yp Před 2 lety +1

      @@BonMj but test run does not start, I get U403, it is probably the PCB?

    • @BonMj
      @BonMj  Před 2 lety +1

      @@JoseANTONIO-hl7yp you replace the main pcb?
      If yes,check the DS1 and DS2 setting.
      Afterthat auto charging and then test run.

    • @BonMj
      @BonMj  Před 2 lety +1

      czcams.com/video/RleCvum-bEQ/video.html
      if new installatio, follow this video, 1st auto charge after test run

    • @JoseANTONIO-hl7yp
      @JoseANTONIO-hl7yp Před 2 lety +1

      @@BonMj is auto charging always done first?
      And I have not replaced the main pcb yet, but it does not perform the test run.
      Where is the DS1 and DS2 setting??

  • @Hamba_Allah_11
    @Hamba_Allah_11 Před měsícem +1

    Boss where to download the error code diagnosis in pdf. Thanks you

  • @sanjiong7252
    @sanjiong7252 Před 2 lety

    hello sir,what happen vrv4, all fcu error u4,and cu led 000 light,transmission cable cu to last fcu no issue

    • @BonMj
      @BonMj  Před 2 lety

      May be one of the indoor pcb got problem