Steam Boiler Leaking Main Vent

Sdílet
Vložit
  • čas přidán 26. 01. 2020
  • On a Heat service call, I am told the steam boiler seems to go through the water faster, than usual. Therefore I test the boiler out. I check all piping for signs of leaks. I find the main air vent leaking.
  • Zábava

Komentáře • 90

  • @320ceman
    @320ceman Před 3 lety +4

    Copper piping , no swing joints or proper header , major problems

  • @airmech5083
    @airmech5083 Před 3 lety +2

    I love that big boiler drain♥️

  • @davidlampe4153
    @davidlampe4153 Před rokem +1

    Uninsulated steam mains and no maintenance recipe for high fuel bills copper above the water line done by others and no drop header. Have a nice trip? See you next fall!

  • @austinjay5915
    @austinjay5915 Před 4 lety +1

    Working on a steam boiler really could use advice from the hacker

  • @IslandbreezeMechanical
    @IslandbreezeMechanical Před 4 lety +7

    Another one piped in copper. Wrong.

    • @thehvachacker
      @thehvachacker  Před 4 lety +3

      Yes its not the best yet I run into copper piped steam boilers often. I did it once yet all my boilers I pipe in black pipe. Always end up with small leaks on most copper solder joints over time.

  • @tucobenedicto109
    @tucobenedicto109 Před 4 lety +1

    You removed the tripping hazzard and took it with you cool. Nice job.

    • @thehvachacker
      @thehvachacker  Před 4 lety +1

      Yes now anyone looking for leaks should’ve trip over that hidden treasure.

    • @hvac01453
      @hvac01453 Před 4 lety

      The HVAC Hacker OMG, that’s one hell of a tip she gave you!

  • @royamberg9177
    @royamberg9177 Před 4 lety +2

    Nothing like showing off a new pipe wrench

    • @thehvachacker
      @thehvachacker  Před 4 lety +2

      I bought that for moms water heater yet this wrench has gotten quite a bit of work already. My older 2 foot pipe wrenches teeth were stripped down a lot. Strange usually I don't buy new ridged wrenches since most second hand Ridged tools/ wrenches are just as good as a new one.

    • @hvac01453
      @hvac01453 Před 4 lety

      The HVAC Hacker I noticed he rewarded himself with that new wrench too!😃

  • @joseflores289
    @joseflores289 Před 3 lety +1

    Be careful my man alright

    • @thehvachacker
      @thehvachacker  Před 3 lety

      That fall hurt, yet the pipe vise tripod I fell was tipped to me on this job. Been using it a lot

  • @frmerrin2
    @frmerrin2 Před 4 lety +3

    Someone seriously hacked that boiler install.

  • @davida1hiwaaynet
    @davida1hiwaaynet Před 4 lety +1

    That's interesting! We generally don't have steam heat in the area where I live so no experience with it. The water in there looked pretty dark. I assume that constant leaking and replenishment with tap water just builds up more and more solids? Congrats on the gift as well!

    • @thehvachacker
      @thehvachacker  Před 4 lety +2

      The darkness of the water is iron from the inside of pipes and radiators slowly rusting. Which is why flushing and maintenance is critical on these boilers. I like working on steam boilers it’s what I grew up with heating my home.

    • @mark33545
      @mark33545 Před 4 lety

      The HVAC Hacker flushing how? I was told dumping the guck out of the bottom did nothing (which I thought was odd) and just increased the chances of needing the replace the valve. I wanted to try to do a skim myself in the spring (in case something goes wrong lol) but I was interested in a blow down, there is no king valve on the manifold header does that mean its never been done? There is a union there though. That is something I dont think I can handle myself but it is it needed? 1991 Weil McClain eg-40

    • @davida1hiwaaynet
      @davida1hiwaaynet Před 4 lety

      @@thehvachacker Thanks for the reply. Yep it's interesting how we're all fond of what we grew up around!

  • @More350Power
    @More350Power Před 4 lety +2

    I didnt think copper could be used for a steam system?

    • @thehvachacker
      @thehvachacker  Před 4 lety

      It's not the best and solder joints seem to leak though often. Also seal themselves up at times. why all the green deposit on the hartford loop before boiler.Steel is the better choice

  • @medicalnegligence
    @medicalnegligence Před 3 lety

    Nice vid. Can’t undo my two main vents that are both hissing. They appear to be the original vents from the early 1940’s and seem fused to the iron reducing bushing. Trying to avoid cracking old steam pipes.

    • @mugen-mundo
      @mugen-mundo Před 2 lety

      I removed mine with 3 foot pipe wrench with a cheater attached to the end. It's all about rotational Force.

  • @acechoice45
    @acechoice45 Před 4 lety +1

    Wow they piped that header in copper oh boy. Equalizer line, some return piping and Hartford loop is ok in copper i wouldn't use it for the header!

    • @thehvachacker
      @thehvachacker  Před 4 lety +1

      Yea not the best way to pipe a header. I think steel should be used for most steam piping.

    • @jeffreyjohn2037
      @jeffreyjohn2037 Před 4 lety

      I would never use copper on a supply header. Regardless, when I solder fittings, they are flawless. That boiler was hacked in by a hacker.

  • @ryanmulvany2803
    @ryanmulvany2803 Před 6 měsíci

    We replaced our main air vent 3-5 years ago and it appears to have gone bad again. It is a Hoffman 75 vent. What could be causing it to go back so quickly?

  • @Ted_E_Bear
    @Ted_E_Bear Před 4 lety +2

    The great Hacker is the man, he is so smart. The President needs the Brilliant Hacker on his defense team !!!

    • @thehvachacker
      @thehvachacker  Před 4 lety +2

      I would never know the laws that even a non-trump supporter yet bi partisan Dershowitz pointed out to show how corrupt this impeachment is. By only pointing out the laws and what's actually in the constitution. Or use the bombshell Pam Bombi used to put all of Biden's crimes in front of congress and anyone watching this impeachment. Yet the GOP still is trying to protect their front runner yet need a better candidate or should just recuse the election. If this was sports the Dems would lose their draft pick yet we need a fair election allowing the people to choose our president, not congress.

    • @Ted_E_Bear
      @Ted_E_Bear Před 4 lety +1

      Thanks you for your great wisdom showing through once again, what a genius you are !!

    • @hvac01453
      @hvac01453 Před 4 lety

      @@thehvachacker years ago only congress voted for the president. They felt the people were too ignorant /uneducated, to elect the president.

    • @jeffreyjohn2037
      @jeffreyjohn2037 Před 4 lety

      @@Ted_E_Bear he's a stable hacker

  • @kamechanicalhvac2891
    @kamechanicalhvac2891 Před 4 lety +2

    Great video pal .. What's type of bleeder valve was that

    • @thehvachacker
      @thehvachacker  Před 4 lety

      That's a main steam vent to release air from the return lines. The supply vents are located at the radiators. They are temperature activated. They close when hot enough not to allow steam out. And open when cools down to allow air out until the heat of steam hits the valve.

  • @robertmacdonald8447
    @robertmacdonald8447 Před 3 lety +2

    A bit of pipe insulation would certainly save them a bit of money, but dude, don't be poking old insulation like that without a mask.

  • @throttlebottle5906
    @throttlebottle5906 Před 4 lety +1

    steam stain on the ceiling told a story :)

    • @thehvachacker
      @thehvachacker  Před 4 lety

      Yes but this house has had a steam boiler here since late 1800’s. I’m sure many vents have leaked. If you have time check out my other channel Bills Tools that’s where my garage Reno is being done and other not hvac related projects

    • @throttlebottle5906
      @throttlebottle5906 Před 4 lety

      the light orange stain was perfectly in line with the old vent hole and very doubtful they'd replace it and get it lined back up exactly.
      I tend to notice things like that from tracking piping and roof leaks over the years :)

  • @damionfragoso2655
    @damionfragoso2655 Před rokem

    Have they never purged that boiler before 🤨

  • @mark33545
    @mark33545 Před 4 lety +1

    I’m always worried to use stuff like penetrating oil and wd-40 when working on my steam system because I am paranoid about what it have read about how bad oils getting in the system is. Is it typically safe to use it to free stuck fittings in the steam system? When I saw you use it here I realized maybe I was being overly paranoid

    • @thehvachacker
      @thehvachacker  Před 4 lety

      When a boiler is new there is oil inside from all the threaded pipes. When threading pipe oil is constantly applied not to burn the teeth on threader. That oil gets into the boiler. Which is why a new boiler always needs to get skimmed after running for a few days. A little penetrant or wd-40 won’t do anything. You can tell by the water surging if oil is present in the boiler, then just open up the fitting on the upper side of boiler. When my company installs a boiler we use t’s with a plug on side, on the supply where it leaves the boiler. This allows for skimming to remove the oils, it’s very uncommon to have to skim a boiler that’s been operating for some time. Unless the water is jumping around inside the sight glass

  • @robpowell7599
    @robpowell7599 Před 4 lety +1

    Thats awsomen good stuff still happens to good peoplen

    • @thehvachacker
      @thehvachacker  Před 4 lety

      I could of edited the tumble, yet the tumble was how I found the old pipe vise just collecting dust in this basement. Which was a tip for fixing the boiler. Yet the fall dazed me for a few seconds.

    • @robpowell7599
      @robpowell7599 Před 4 lety

      @@thehvachacker only makes you human

  • @jeffreyjohn2037
    @jeffreyjohn2037 Před 4 lety +1

    You never took the wire nut off of the thermostat wires. What was the temperature in the house when they called you back?

    • @thehvachacker
      @thehvachacker  Před 4 lety +1

      I removed wire nut when I finished this job. Every steam boiler I work on I jump this way. Prevents homeowner from shutting down system of thermostat reaching temp while I test the pressuretroll

  • @aglasserm1679
    @aglasserm1679 Před 4 lety +1

    good deal on the vise! Maybe the amateur who installed the boiler left it behind.........this is the worst piping I have ever seen. this is not to code.

  • @nsaglian
    @nsaglian Před 4 lety +2

    Are automated bottom boiler blow down systems available for residential boilers?

    • @thehvachacker
      @thehvachacker  Před 4 lety +1

      Never seen a residential application with an auto blow down. Yet wouldn’t be a bad idea for some of my older customers who can’t lift buckets of water

    • @throttlebottle5906
      @throttlebottle5906 Před 4 lety

      question is, where you you have it dump too?
      floor drain? sump pit? the yard outside assuming 1st floor boiler or walkout basement.
      all I see is clogged drain/sump, frozen outdoor end or a basement without sump/drain and it wont run uphill :)

  • @muxxor9492
    @muxxor9492 Před 4 lety +1

    Old vent looks like a cheap China air vent. I like Gorton #1 Main Vent or Hoffman #75 Main Vent, But I prefer the Gorton seem more reliable.

    • @thehvachacker
      @thehvachacker  Před 4 lety +2

      It's an old Doyle #1a vent. I believe it was before they started making Doyle vents in China. I use to like those vents before they became Chinese made.

    • @jeffreyjohn2037
      @jeffreyjohn2037 Před 4 lety

      Are the Gorton brand made in Glauster?

  • @cyabits1
    @cyabits1 Před 2 lety +2

    What would cause a steam boiler to shot out water on the radiators air vent?

    • @mugen-mundo
      @mugen-mundo Před 2 lety +1

      Condensate not leaving the radiator. For example the pitch is wrong on the radiator or the vent itself is faulty not closing when steam reaches it.

    • @thehvachacker
      @thehvachacker  Před 2 lety +1

      Water is trapped in the radiator. Or the vent is not working correctly. The radiator should have a slight pitch down to where pipe attaches for drainage. Does the vent close? Or hisses none stop?

    • @cyabits1
      @cyabits1 Před 2 lety

      @@thehvachacker hisses none stop

    • @thehvachacker
      @thehvachacker  Před 2 lety

      @@cyabits1 bad vent

    • @user-rf4ps5co8r
      @user-rf4ps5co8r Před 6 měsíci

      Did you get it up to steam pressure and check that black pigtail Probably plugged

  • @mark33545
    @mark33545 Před 4 lety +1

    My main vent on my single pipe steam is at the top of the Hartford loop drop pipe, only about 1in nipple. I read this is bad. Should I get a longer nipple like 6 inches? Anything I can do to deal with it not being 15 inches back as well?

    • @thehvachacker
      @thehvachacker  Před 4 lety

      Does it operate correctly. I seen many vents on a 1” nipple or just threaded into the t. What have you heard that would make the location of the vent wrong? I see many boilers with the vent directly over where the return pipe drops back into the Hartford loop. Do you get a lot of banging and clanking?

    • @mark33545
      @mark33545 Před 4 lety

      The HVAC Hacker it was in a Weil McLain training video (part 2 I think) that someone uploaded to CZcams. The Weil McLain guy says its important to have the main vent 6 inches up and 15 inches back for proper operation. That being said, I don’t think its an issue from what I can tell, i don’t see condensate coming from the vent. However after my system would run for a while, a radiator (top floor, furthest from the boiler/main vent btw) would make a loud noise kind of like it was leaking steam but instead it was sucking air in very loudly (its a Groton). I was told on heating help this could indicate a bad main vent or insufficient main vent or improperly installed. So i checked and sure enough on the loop that the radiator is on that vent was not getting hot like the other one. It would only get hot if the system ran for a long time so i think it was stuck closed. I replaced the vent and now they both get hot around the same time, its been too warm to run the system long to see if the loud air noise is gone now from the far radiator. If the sound continues i was going to put a t and 2 90s and make a little manifold to put 2 of the Groton #1 vents on to see if increasing the main venting solves it. The main issue with my system was inconsistent heating but i found tons of leaks in the system and it was never building up any pressure. I have been fixing the leaks, i repacked a couple valves and replaced almost all of the air vents with vari-vents (keep hearing mixed feelings on these vents). Its getting definitely improving with all my work but i think it can still get better.

  • @edjovi3677
    @edjovi3677 Před 4 lety +1

    hello bill its eddie from leak master plumbing great too see u again that was like mud !!!!! great job as allways hope all is great with wife and kid !!!! talk soon ed bonjovi

    • @thehvachacker
      @thehvachacker  Před 4 lety +2

      I ended up in hospital from getting really sick Saturday morning. Most likely lack of sleep and non stop work between job and trying to get house ready to move in. Now wife has me trapped at home not allowing me to go paint even though hospital released me yet said to stay home and rest. I'm not use to laying around doing nothing. Hopefully I get energy to get another video ready to upload.

  • @familyrcvideosds3680
    @familyrcvideosds3680 Před 4 lety +1

    Wow all you steam heads and no one commented on how undersized that steam vent was lol

    • @jeffreyjohn2037
      @jeffreyjohn2037 Před 4 lety

      What brand and model number vent do you recommend?

  • @chuckquinn8026
    @chuckquinn8026 Před 4 lety +2

    Asbestos?

    • @thehvachacker
      @thehvachacker  Před 4 lety +2

      All over this house. The house was built late 1800’s many old houses in jersey. Why lots of steam systems exist. Asbestos is safe as long as you don’t break it apart. Usually it’s the fittings on the pipe. The straight pipes had some kind of cardboard with an outer paper wrap.

    • @chuckquinn8026
      @chuckquinn8026 Před 4 lety +2

      The HVAC Hacker correct. I worked around it for 40 years. It’s in bad shape in this house, breaking apart. Just saying be careful. My wife died from it. Taught in an old school that had a lot of it in it. They shut the school down for 2 years to clean it out after she passed. Stay safe buddy!

    • @mark33545
      @mark33545 Před 4 lety

      The HVAC Hacker when i repacked my circa 1920s steam shut off valve on my radiators some kind of fibrous material came out, looked more like some kind of hemp though, could that have been asbestos? I tried to avoid vacuuming it up just in case.

    • @thehvachacker
      @thehvachacker  Před 4 lety +1

      Chuck I am very sorry to hear. I will be wearing masks for awhile. I just got out of hospital been cleaning lots of who knows what from my new house. Ended up with colitis most likely infection yet I’m wondering if all the dust and paint fumes could of caused this, I purchased a respirator for all future work their. I’m hoping for infection not chromes or colon cancer

    • @chuckquinn8026
      @chuckquinn8026 Před 4 lety

      The HVAC Hacker hope you are feeling better fast. I’m not preaching, just reminding people about taking caution around asbestos and wear proper PPE, especially when it’s in a deteriorated condition. Masks are good when cleaning out any basement, garage or attic. God knows what’s being stirred up, and being breathed in...and don’t forget ceramic fibers too in insulation blankets and around burners...just as bad

  • @throttlebottle5906
    @throttlebottle5906 Před 4 lety +1

    mmm, bucket of hot chocolate :))

  • @edjovi3677
    @edjovi3677 Před 4 lety +1

    bill holy shit i did the same thing but on ice over the week end omg hope your ok the next day i was fucked up with my back for 2 day later edbonjovi

    • @thehvachacker
      @thehvachacker  Před 4 lety

      Hopefully your ok. Somehow I was just dazed by the fall temporarily. I felt it was best to keep that in video since the vise I tumbled over became mine as long as I removed it from the basement.

    • @jeffreyjohn2037
      @jeffreyjohn2037 Před 4 lety

      Ed: You should get hooked on phonics.