Design Guidelines for HVAC system of OT (Operation Theater) (ENGLISH)

Sdílet
Vložit
  • čas přidán 18. 08. 2024
  • #OTDESIGN
    #HAVCDesign
    OT HVAC guideliness
    passionatengin...
    Filter selection HVAC
    passionatengin...

Komentáře • 113

  • @yusopmanga9188
    @yusopmanga9188 Před měsícem

    Hi, thank you for your nice video sir.

  • @prashanthgaitonde3451
    @prashanthgaitonde3451 Před 2 měsíci +1

    Sir do you have the electrical technical specifications in a word file similar to the one you have shown here?

  • @MrSudeepantony
    @MrSudeepantony Před 9 měsíci +1

    Boss, Can you Please work out an example for calculation of Airflow with room volume 5200 ft3 , 5-8 occupancy, Equipment Load of 7-9 Kw.??

  • @passionateengineer04
    @passionateengineer04  Před 3 lety

    Kindly check video description for OT documents

  • @mdmasihmechanical
    @mdmasihmechanical Před 2 lety

    Dear ,Very good and brief explanation.THanks for sharing.Please provide details of Lab,ICU and other areas design.

  • @GSPK9
    @GSPK9 Před 2 lety

    Great Information. Thanks

  • @tsmech9
    @tsmech9 Před 3 lety

    Very Good Information 👍👍

  • @santoshhatankar
    @santoshhatankar Před rokem

    Hi Sir very good explanation sir. Thanks for clearing this concept. Also provide video on RH control strategies or Heating kw calculation.

  • @warissirkhot5955
    @warissirkhot5955 Před 3 lety

    Thank you very much sir...it has really cleared my concept.
    Can u pls make a video on indoor swimming pool designing 🙏.

  • @justpocong7414
    @justpocong7414 Před 2 měsíci +1

    kindly send to me the specifications in a word file, thank you

  • @ashpaksheikh1616
    @ashpaksheikh1616 Před 4 lety +1

    Cau Send this document to download

  • @nse08
    @nse08 Před 2 lety

    Hi ! Could you please share the summary sheet that you explain in the video, thank you !

  • @adityavibhute6225
    @adityavibhute6225 Před 3 lety

    How to calculate heat load for 20'x20' sized OT using E-20 form?

  • @abhyunnati8589
    @abhyunnati8589 Před 7 měsíci

    Super video

  • @hpzen8371
    @hpzen8371 Před 2 lety

    Good video sir

  • @khalilmondal3876
    @khalilmondal3876 Před 7 měsíci

    As per the video what would have been the CFM of AHU at 20 ACPH 100% Fresh Air..?

    • @passionateengineer04
      @passionateengineer04  Před 5 měsíci

      100% Fresh air means that fresh air flow will be based on 20 ACH according to your question.

  • @abdulrahmanshah6040
    @abdulrahmanshah6040 Před 3 lety

    How you will maintain positive in any room, what is the formula and how should we know the required CFM to maintain that pressure difference with surrounding.

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      To maintain positive pressure the return air must b less than supply air, like one room have supply air is 400 cfm return is 300 cfm and another room has 400 cfm and return is 250 cfm that one will have positive with respect to another.
      The minimum pressure differential is 2.5 pascal.

  • @sagarpatankar6347
    @sagarpatankar6347 Před 3 lety

    Nice video..

  • @abhijeetsinghsisodiy
    @abhijeetsinghsisodiy Před 3 lety

    Sir ur teaching skills are great 🙏thax for sharing your learnings.....sir I request u to plz start a detailed course of HVAC design and heatload calculation a paid course🙏

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      I am already offering HVAC courses online, contact me for further details.
      Naqqash.sajid@gmail.com

  • @petrickarizala5932
    @petrickarizala5932 Před rokem

    how to compute the return air

  • @PremKumar-ws1br
    @PremKumar-ws1br Před 4 lety +1

    If u have notes sir plz provide..... Especially pharma note... Design..... Please upload one video of dehumidifier air plz

    • @PremKumar-ws1br
      @PremKumar-ws1br Před 4 lety

      Dehumidified air calculation ans ahu coil calculation

  • @hpzen8371
    @hpzen8371 Před 2 lety +1

    Minimum ACH for OT is 20 and out of which 4 ACH needs to be fresh air.
    Consider a OT having 1000sqft, as per ACH equation EA will be 334cfm(20ach) and 4 ACH means 67cfm. Then if we want to size AHU what percent of RA needs to be mixed with OA and what should be the supply air to the OT
    Pls help me in this case.

    • @passionateengineer04
      @passionateengineer04  Před 2 lety +1

      In this case 334 cfm is SA and 67 cfm is FA so RA will be SA-FA=267 cfm

    • @hpzen8371
      @hpzen8371 Před 2 lety

      @@passionateengineer04 thanku sir

    • @hpzen8371
      @hpzen8371 Před 2 lety

      So now total SA will be 334cfm and as per this we have to select AHU tonnage...

    • @passionateengineer04
      @passionateengineer04  Před 2 lety +1

      400 cfm per ton

    • @hpzen8371
      @hpzen8371 Před 2 lety

      @@passionateengineer04 ok sir

  • @PRIYAYADAV-nd5zm
    @PRIYAYADAV-nd5zm Před rokem

    Atmoshpheric pressure is 101,325 pasacl than how 2.5 pascal pressure is called positive pressure in operation theatre

    • @passionateengineer04
      @passionateengineer04  Před rokem

      Its differential pressure is not with respect to the atmosphere.
      It is a mini pressure difference between rooms.
      Thank you

  • @danisekotanowo8485
    @danisekotanowo8485 Před rokem

    hello sir ,, let me ask . what is the function of the exhaust fan in the hvac system in the operating room? and how do we calculate the exhaust fan capacity? Thank You

    • @passionateengineer04
      @passionateengineer04  Před rokem

      OT must be at positive pressure, when OT is pressurized some of air flows through door gaps, if the room is sealed tight then the fresh air needs to be exhausted.
      Because when fresh air is added and there are no escape gaps then it will increase pressure beyond limits and no room for further fresh air, because OT required constant 4 ACh of outdoor air as per ASHRAE 170.

  • @PRIYAYADAV-nd5zm
    @PRIYAYADAV-nd5zm Před rokem

    What does 2.5 pascal differential pressure

  • @engalihvac4712
    @engalihvac4712 Před 4 lety

    nice video

  • @aakangkhitachoudhury2530

    Sir ,can you please explain why temperature is lower in ortho OT as compared to other OTs?

    • @passionateengineer04
      @passionateengineer04  Před 2 lety

      Orthopaedic implant surgery have high risk of surgical site infection and the surgeons have their own temperature requirements as they have to work in their heavy surgical clothing in order to avoid infection whereas anaesthesist requires a slightly lower temperature. It was noticed in study that the rise in postoperative infections for the period when ventilation system of the theatre was substandard and the temperatures were high.

  • @ajaysaitawadekar9690
    @ajaysaitawadekar9690 Před 2 lety

    how to make air balancing in hospital room like positive and negative pressure room

    • @passionateengineer04
      @passionateengineer04  Před 2 lety

      In positive pressure room ,the return air must be less than supply to maintain pressure, opposite for negative room. Watch this video for Pressure requirements and air adjustment.
      czcams.com/video/FuoMTa-9Y6Y/video.html

  • @ashpaksheikh1616
    @ashpaksheikh1616 Před 4 lety

    How to design AHu of OT for 16 deg.
    Also how much return air we need to take for AHU
    Do we need uv light in ahu

    • @passionateengineer04
      @passionateengineer04  Před 4 lety

      I explain this in previous comment.
      AHU RA depends on Supply, that how much pressure you want to maintain if you want to maintain more pressure in OT, RA will be less than SA and for Air balancing you have to add OA and exhaust some percent of Air for Air relief.
      Its better to use UV lights or UVGI.

  • @deepakkaranam2677
    @deepakkaranam2677 Před rokem

    Sir are HEPA filter is necessary for procedures such as hernia repair and hydrocele

  • @krantikumar7929
    @krantikumar7929 Před 3 lety

    Plz, can you make a video of the OT Heat load calculation

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      you can watch my video on clean-room heat load calcualtion.It will give you an idea, i will try to upload it soon.

  • @deepaklavaniya2198
    @deepaklavaniya2198 Před 3 lety

    Sir return air pick outside the ot ya inside Ot?

  • @yunuspervez4702
    @yunuspervez4702 Před 3 lety

    First of all thanks for making a nice video over it. Can you please define more about the controls of AHU for OT? Supply air should be based on cooling load calculation results or according to 20 ach? Please answer

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      You're welcome!
      Do you need electrical controls?
      Ventilation should be according to 20 ACH.

  • @ZEESHANUSTAD
    @ZEESHANUSTAD Před 3 lety

    What is mean by 4 air changes out of total minimum 20 air change?
    NABH Guidelines for OT 2018 says "FA required to be min 4 Air changes out of total minimum 20."
    I'm a bit confused. In my case for 3535 CFM and 4590 vol I'm getting 44.6 ACH.
    How much fresh air to be considered in this case?
    Thanking you

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      You have to calculate the supply air by 20 ACH and fresh air or OA by 4 ACH.
      So the cfm calculated by 20 ACH will be supply air and cfm calculated by 4 ACH will be fresh air, so total supply air will be the cfm calculated by 20 ACH plus cfm calculated by 4 ACH and returns air will be only cfm calculated at 20 ACH.
      So the OT is at positive pressure hence cfm calculated at 4 ACH will maintain positive pressure.

    • @ZEESHANUSTAD
      @ZEESHANUSTAD Před 3 lety

      @@passionateengineer04 NABH asks min 4 ACH (fresh air) out of min 20. Here I'm getting 39 supply air change.
      I got your point that 4 FACH would help in creating +ve pressure which is must in OTs, NOW my question is fresh ACH is 4 (that too minimum), but how much Max FACH could be considered? Is there any limit?

    • @passionateengineer04
      @passionateengineer04  Před 3 lety +1

      FA will be 10 to 15% max of the total SA.

    • @ZEESHANUSTAD
      @ZEESHANUSTAD Před 3 lety

      @@passionateengineer04 Thank you

  • @vishwajeetjadhav4157
    @vishwajeetjadhav4157 Před měsícem

    Sir can we get the soft copy of word file

  • @harkaranandsavreen327
    @harkaranandsavreen327 Před 2 lety

    Sir, What is size of ducts required for supply and return ducts for 3000cfm AHU for standard 20× 20 ×10 (ht) in fts of OT size.

  • @santoshlamichhane9944
    @santoshlamichhane9944 Před 3 lety

    plz mention about reheater size selection for RH control in OT

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      It depends on thr air flow rate and capacity

    • @santoshlamichhane9944
      @santoshlamichhane9944 Před 3 lety

      please send your whatsapp number. I will tell the problem thatI have faced while Designing HVAC system for OT

    • @karankotian6071
      @karankotian6071 Před 3 lety

      @@passionateengineer04 can you share knowledge if it’s possible to use same OT For positive and negative pressure application
      Like isolation and surgery or vice versa ?

    • @passionateengineer04
      @passionateengineer04  Před 3 lety +1

      OT can only be used for positive pressure. If you want to use it for negative pressure it will contaminate the OT with bacteria or virus, than you will do fumigation etc to use it again as OT

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      Naqqash.sajid@gmail.com

  • @bedahkasusremajaofficial

    Hallo. I read from ashrae also that ACH for isolation negative press.room for covid is 12. But there is no explanation wheter ACH 12 is for fresh air only or fresh air Plus supplyr air. What is your opinion.

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      In negative pressure room air is only fresh air, and exhaust air, so 12 ach is for OA.

    • @bedahkasusremajaofficial
      @bedahkasusremajaofficial Před 3 lety

      @@passionateengineer04 how about for operation room but special for covid patient. Is the room positif press or neg press.

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      OT are always at positive pressure.

    • @bedahkasusremajaofficial
      @bedahkasusremajaofficial Před 3 lety

      @@passionateengineer04 can you show me the reference or standard that OT fot covid patient is positive pressure.

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      OT cannot be at negative pressure because of the outoor contiminants, it doesn't matter whether its covide patients or not.

  • @ashpaksheikh1616
    @ashpaksheikh1616 Před 4 lety

    How much off coil temperature required to get 16 deg in OT

    • @passionateengineer04
      @passionateengineer04  Před 4 lety

      It will be covered in coil sizing and calculation topic. Coil temperature depends upon refrigerant flow rate and Air flow rate, if you need to maintain 16 deg in OT you have to design coil according to it at temp difference of 5c. Or during equipment selection manufacture can provide this data.

    • @ashpaksheikh1616
      @ashpaksheikh1616 Před 4 lety

      @@passionateengineer04 u mean to say if need 16 deg, off coil temp shall be 11 deg with 5C diff

    • @passionateengineer04
      @passionateengineer04  Před 4 lety

      For Chilled water system we supply water 7c and return it on 12c to maintain 16c. But it all depend on manufacturer, if you want to achieve 16c room quickly its off coil temperature will be different and air flow will be different if you want to achieve gradually than its different.

    • @passionateengineer04
      @passionateengineer04  Před 4 lety

      5c difference in case of CHW 7c water supply temperature and 12c on return, but off coil temperature is different it depends on how quickly you want to achieve temp, normally for 16c its 6c coil temperature that is 10c difference.

    • @yokeleetan8525
      @yokeleetan8525 Před 3 lety

      @@passionateengineer04 you cannot get 6 deg off coil when your entering chill water temperature is 7 deg C.

  • @pankajmanral6290
    @pankajmanral6290 Před 3 lety

    👏👍

  • @mohamedraafatragab5537

    Could i get this word please?!

  • @JayaKumar-jl6qo
    @JayaKumar-jl6qo Před 3 lety

    Hi Sir, I am doing HVAC design for Fish market. Could you please provide me the reference documents related to the HVAC system design for fish markets. (mainly about ventilation rate required and RH control). I was searching in ASHRAE, where i couldn't able to identify the data related to Fish market design. Client is very concerned about the smell and condensation/ moisture since the market is very close to sea. Kindly help to provide reference documents if you have any. Regards Jayakumar

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      Do you want to store fish for long time? Or just need to store for selling purpose?

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      And what kind of fish are they selling? Lean fish, flat fish, glazed type etc because their storage temperature and ACH and other parameters are different.

    • @JayaKumar-jl6qo
      @JayaKumar-jl6qo Před 3 lety

      PASSIONATE ENGINEER Just need to store for selling purpose

    • @passionateengineer04
      @passionateengineer04  Před 3 lety

      @@JayaKumar-jl6qo Kindly check ASHRAE Handbook of refrigeration 2018, chapter 32 "Fishery products".

  • @ashpaksheikh1616
    @ashpaksheikh1616 Před 4 lety

    What is Hvac criteria for dialysis room or

    • @passionateengineer04
      @passionateengineer04  Před 4 lety

      Same criteria but ACH, temp and humidity is different, check ASHRAE code 170.

  • @bimmakersonline459
    @bimmakersonline459 Před 3 lety

    hi sir provide email i have few questions on hospital design

  • @zoaibjamali6638
    @zoaibjamali6638 Před 3 lety

    Can I have your contact

  • @khalilmondal3876
    @khalilmondal3876 Před 7 měsíci

    how to calculate or design 100% fresh air burn ward hvac system with AHU?

    • @passionateengineer04
      @passionateengineer04  Před 7 měsíci

      Check ASHRAE 170.

    • @khalilmondal3876
      @khalilmondal3876 Před 7 měsíci

      @@passionateengineer04 only given 2 outdoor ACPH & 6 Total ACPH. 100% FA not given. Could you please share sir...

    • @passionateengineer04
      @passionateengineer04  Před 7 měsíci

      If its per ASHRAE than you don't need 100% fresh air, you will require 2 ACH of fresh air.