HVAC: Laars Commercial Boiler Nightmare (Laars Pennant Hydronic Boiler Not Working/Heating Up Water)

Sdílet
Vložit
  • čas přidán 2. 03. 2024
  • HVAC: Laars Pennant Commercial Boiler Nightmare (Laars Pennant Hydronic Boiler Not Heating Up Water) HVAC Emergency Follow Up: Commercial Hydronic Circulating Pump Installation/Repair For LAARS Boiler / HVAC Emergency: Commercial LAARS Boiler Hydronic Circulating Pump NIGHTMARE (Boiler Pump Leak Water) HVAC (Heating, Ventilation, Air Conditioning) Emergency Service Call: Commercial Hydronic LAARS Boiler Water Pump Leaking Water (Water Pump Leak Repair) Boiler Repair / Boiler Not Working / Boiler Leaking Water / Boiler Pump Not Working / Boiler Circulator Pump Leaking Water / Boiler Circulator Pump / Boiler Circulator Pump Wiring / Boiler Circulator Pump Troubleshooting / Boiler Water Leakage / Boiler Leaking Water / Boiler Troubleshooting / Boiler Sequence Of Operation / Laars Pennant Hydronic Boiler / Pennant Commercial Boiler Or Volume Water Heater / Laars PNCH500 / Laars PNCV500
    GoPro HERO8 Black (Camera Used In This Video)
    amzn.to/3q4FmEz
    Veto Pro Pac TECH MC
    amzn.to/3gURJyZ
    Fluke 902 FC HVAC True-RMS Clamp Meter
    amzn.to/39wvwiK​​
    Fieldpiece ADK7 Deluxe Silicone Test Lead Kit
    amzn.to/3VNYXDv
    Klein Tools ET600 Megohmmeter Insulation Tester
    amzn.to/409iNvu
    Supco M500 Insulation Tester/Electronic Megohmmeter
    amzn.to/42oy0ua
    Fluke 1AC-A1-II VoltAlert Non-Contact Voltage Tester
    amzn.to/3FcWElQ
    Fieldpiece JL3KR4 HVACR Charge Kit (Digital Gauges/Probes)
    amzn.to/3E4W0Fr
    Fieldpiece SPK2 Folding Pocket In-Duct Thermometer
    amzn.to/3mi8Fih
    Fieldpiece SPK3 Folding ROD Dual Temperature Thermometer
    amzn.to/3FbDufQ
    Milwaukee M12 2-Tool Combo Kit 2598-22
    amzn.to/3CtCRNC
    Milwaukee Cut 1 Dipped GLOVES L
    amzn.to/3s8H18O​
    Milwaukee 2351-20 M12 LED Stick Light
    amzn.to/3rVJKEK
    Milwaukee 48-22-1985 Fastback Hawk Bill Folding Knife
    amzn.to/3e53ygW
    Milwaukee 48-22-1500 Fastback Compact Folding Utility Knife
    amzn.to/3qazJkC
    Milwaukee 48-22-4041 Iron Carbide Core Large-Looped Jobsite Scissors
    amzn.to/32fxC6I
    Milwaukee 4932459097 Billet Torpedo Level
    amzn.to/30Dh6Nw
    Milwaukee Wide Blade Magnetic Tape Measure 16 FT
    amzn.to/3yEN7kL
    Milwaukee Fine Pt. Markers Black
    amzn.to/3e4fH5W
    Streamlight 66604 MicroStream USB 250-Lumen Rechargable Pocket Flashlight
    amzn.to/320XiEF
    Klein Tools 11-in-1 Screwdriver / Nut Driver
    amzn.to/3s3o8ql
    Klein Tools 32561 Multi-Bit Screwdriver / Nut Driver 6-in-1
    amzn.to/3e4ur4x
    Klein Tools 32807MAG 7-in-1 Nut Driver, Magnetic Driver
    amzn.to/321n4bW
    Klein Tools 600-4 1/4-Inch Keystone Cushion-Grip Screwdriver
    amzn.to/3J11hS1
    Klein Tools 32581 4-in-1 Electronics Screwdriver Set
    amzn.to/3yEj3WC
    Klein Tools LLK12 L-Style Hex Key Caddy Set 12-Piece (Metric/Sae)
    amzn.to/3yRUiGJ
    Yellow Jacket 18975 Charge Tool
    amzn.to/3J4pfvJ
    Yellow Jacket 60613 Service ratchet Wrench
    amzn.to/3E8iYeZ
    Yellow Jacket 19173 5/16" Female Quick Couplers x 1/4" Male Flare
    amzn.to/3q0TQ4M
    Cooper Bussmann BP-FP-2 Cartridge Carded Fuse Puller
    amzn.to/3e0USrY
    Crescent 2 Pc. X6 4-in-1 Black Oxide Spline Ratcheting SAE Wrench Set
    amzn.to/3qqKlw7
    Crescent 4" Adjustable Cushion Grip Wrench
    amzn.to/3J4qsmL
    Knipex 09 08 240 SBA 9.5-Inch Insulated Ultra-High Leverage Lineman's Pliers (1000v)
    amzn.to/30EQmw5
    Knipex 09 11 240 9.5-Inch Ultra-High Leverage Lineman's Pliers with Fish Tape Puller and Crimper
    amzn.to/3H9iYAu
    KNIPEX Tools - Long Nose Pliers With Cutter, 1000V Insulated
    amzn.to/3e3IEi7
    KNIPEX Tools - Long Nose Pliers With Cutter
    amzn.to/3gUSE2i
    KNIPEX Tools 98 62 02, Flat Nose Plastic Pliers 1000V Insulated
    amzn.to/3p6lFsZ
    KNIPEX - 74 08 200 - High Leverage Diagonal Cutters, 1000V Insulated
    amzn.to/3mh8K5U
    KNIPEX - 74 01 200 Tools - High Leverage Diagonal Cutters
    amzn.to/3F1VScb
    KNIPEX Tools - Cobra QuickSet Pump Pliers, 1000V Insulated
    amzn.to/3sftr5Q
    KNIPEX Tools 3 Piece Cobra Pliers Set
    amzn.to/3FbRwy7
    KNIPEX Tools Pliers Wrench 3-Piece Set
    amzn.to/3nnRLfW
  • Věda a technologie

Komentáře • 109

  • @_NCR
    @_NCR Před 4 měsíci +8

    They pressure test those pumps at the factory. That's why the new pump's impeller had rust on it.

  • @garysmith9772
    @garysmith9772 Před 4 měsíci +6

    I never seen anybody that had more guts than you do you are fearless man.

  • @guy872
    @guy872 Před 4 měsíci +8

    Great video man. I work in a similar industry and knew the exact pressure you were feeling lol. Sometimes you have to take a step back and realize it's not your fault if the customer doesn't take care of their equipment. All those unlabeled valves, that boiler room was a mess. Looking forward to the next update on this.

  • @josephkober3324
    @josephkober3324 Před 4 měsíci +4

    Retired stationary engineer here . Can you just replace the broken pump coupler on the B & G pump ? You wouldn't have to open the pump volute up if thats all it needs , just unbolt the motor from the pump and change the spring coupler. Those couplers are always going bad poor design unless the pump is always on . If it cycles they don't last long.

  • @DrCranberry
    @DrCranberry Před 4 měsíci +12

    Hearing "we're gonna have to shut down water for a 24 hour hotel" brought back memories, of us trying to redo an entire riser, on 70 floors, and every floor had 45 rooms AND every room had their own riser. Plus every riser had to get T sections for the fan coil units that were in the rooms as well.
    Half the hotel was still active while we worked.
    Biggest crew i've ever been on, it was 30 guys, with 10 foot stacks of various sized copper. Putting in the risers weren't too bad, we fed every one from the top and pre-connected every one as we went so we didnt run into problems.
    Job went pretty smooth, but god damn you realize how greedy some of these hotels are. Job would go WAY easier if the hotel wasnt active and we'd get it done faster, but bottom line means more than getting done earlier I guess.

  • @miner49er98
    @miner49er98 Před 4 měsíci +13

    Spiralink - replace the coupler

  • @poohbear4130
    @poohbear4130 Před 4 měsíci +13

    That 3” is the boiler water make up, Why is the bypass open, nothing labeled that’s an extremely poor boiler room! There are companies that can freeze the pipe so the valve could be replaced without taking the system down? Something to look into for future repairs as it looks like your the new maintenance man!

    • @manickbarry
      @manickbarry Před 3 měsíci

      10:51 I was just about to mention that bypass.

    • @JonathanLarson-CoolJon
      @JonathanLarson-CoolJon Před měsícem

      I was wondering, too, why the bypass was open. Maybe the regulator is bad.

  • @samuelaranda4568
    @samuelaranda4568 Před 3 měsíci +2

    I retired 4 years ago from 35 years of HVAC . I remember service call in the middle of the night. Those are the ones that became all nights . . Good job and gets some sleep

  • @HEFTYLEFTY303
    @HEFTYLEFTY303 Před 3 měsíci +2

    Just replace the spring couple and motor mounts and you are good unless the bearing assembly is seized

  • @scottlaferriere4499
    @scottlaferriere4499 Před 4 měsíci +24

    No need to replace the complete pump. All that is needed is the spring coupler between bearing assembly and motor and then you would not have to drain. And the pump you picked up may not even be the proper GPM as those are normally designed for the application.

    • @andresland9906
      @andresland9906 Před 4 měsíci +6

      Lol this guy is a parts changer , you are right he should've replaced the coupling.

    • @topher8634
      @topher8634 Před 4 měsíci +2

      That's usually what's needed but I have seen the pump be locked down and that's what will break the coupler. It probably wasn't a bad idea to put a new one in, especially if it had a lot of run time on it or proper maintenance or water treatment hasn't been done.

    • @christopherleubner6633
      @christopherleubner6633 Před 4 měsíci +3

      That is the typical case, but this one the pump was subjected to both misalignment and overload from the valve being almost shut off. Likely the pump head shaft bearing failed and caused the coupler to fail. They are designed to do that to prevent the motor from going up in flames.❤

    • @richritchie5434
      @richritchie5434 Před 3 měsíci +2

      What I’ve learned is the most convenient and cost effective way is do replace the complete bearings assembly. Come with seal kit, bearings housing and coupler…and gasket….

    • @non-human3072
      @non-human3072 Před 3 měsíci

      🤠

  • @williamgildea8348
    @williamgildea8348 Před 4 měsíci +3

    Love the channel, but I think you could have just replaced the coupler. There’s an allen key that just gets loosened.

  • @MetalDetectingwithCZkidd
    @MetalDetectingwithCZkidd Před 4 měsíci +2

    Loosen valve packing nut and you may find valve may move. Challenging jobs, loved those. Nice vid.

  • @Eddy63
    @Eddy63 Před 4 měsíci +2

    The harder the job , the better you and your helper do ... Nice work ... Thx

  • @izzybell11
    @izzybell11 Před 4 měsíci +3

    Interesting subject and well explained. Great job JMT. You nailed it. It was a helpful and interesting video.

  • @matthewgrallert1603
    @matthewgrallert1603 Před 4 měsíci +4

    couldn't fine a pump coupling?

  • @chrisgotgame16
    @chrisgotgame16 Před 4 měsíci

    Great job to you and your helper JMT with that pump definitely a nightmare!

  • @chrisvig123
    @chrisvig123 Před 4 měsíci +7

    You don’t need to replace the pump…just replace the spring clutch assembly on that pump assembly and make sure that valve is fully opened. Your good to go until a proper replacement of the boiler can be arranged

  • @johnwalker890
    @johnwalker890 Před 4 měsíci +1

    Good job Jumper, I knew you'd get it done, let us know what happens.

  • @jeremiahsfoods
    @jeremiahsfoods Před 4 měsíci +2

    I always enjoy these videos 🔥

  • @springws14lbss
    @springws14lbss Před 4 měsíci +3

    You always get the nightmare calls! 😅

  • @zekenzy6486
    @zekenzy6486 Před 4 měsíci +1

    Great Video. Thank you for sharing. Good Job and Nice Work. This is a big job. and It is nightmare.

  • @HVACK
    @HVACK Před 4 měsíci +3

    Dude, you really do find some sh*t, don't you!? Great job! Are those stress factures in the pipes? Let us know what you find out. Thanks for the video, bro!

  • @michaelsmith9034
    @michaelsmith9034 Před 4 měsíci +2

    Good job,don’t envy you working in NYC.

  • @genewheeler6320
    @genewheeler6320 Před 4 měsíci +1

    Great job again sir

  • @johnj4860
    @johnj4860 Před 3 měsíci +1

    A little knowledge is a dangerous thing!

  • @lowrybrock8272
    @lowrybrock8272 Před 4 měsíci +3

    Always enjoy the videos! That place is a shit show. They do little or no maintenance and then the dominoes fall when repairs are needed. Are all the buildings in NYC this poorly maintained? If so, you’re gonna be a millionaire by the time you’re 30. Keep making them and I’ll keep watching! Be safe out there.

  • @joeyyc8515
    @joeyyc8515 Před 4 měsíci +1

    When you said it was done, i knew you were a pro

  • @royjurd3843
    @royjurd3843 Před 4 měsíci +3

    Why was the bypass open on the 3" ? , was the pressure regulator U/S "

  • @patrickvafbhvac5248
    @patrickvafbhvac5248 Před 3 měsíci

    You are a HERO.

  • @davidillich7014
    @davidillich7014 Před 4 měsíci

    Enjoyed watching from calif

  • @lachcik5084
    @lachcik5084 Před 2 měsíci

    this is my day every single day in this trade and i love it lol. keeps me going ;)

  • @thesilentonevictor
    @thesilentonevictor Před 4 měsíci +3

    Man those job love you all these work come at like butter 😂

  • @therealromster
    @therealromster Před 3 měsíci

    I am not in this field but it was me I would of replaced them two valves not just the one, before doing anything else. Then work on that unit as the other boilers can stay on. Good work keep it up!

  • @jrh86
    @jrh86 Před 4 měsíci

    Excellent video very interesting and as if i was their 💯💯💯💯👍👍👍👍👍

  • @matthewkren8814
    @matthewkren8814 Před 3 měsíci

    i know what you are going through. similar thoughts, pump wouldnt come free, had to pry it off and break it free. eventually it popped off and we got the new pump in and replaced the whole bearing assembly.

  • @bluebeastgamer3005
    @bluebeastgamer3005 Před 4 měsíci +1

    In Vancouver, bc Canada, we have soooo many more plumbers, HVAC and heating guys are like that, they keep changing replacement parts until they can find the problem because they don't have any experience, expertise or skills. They are exactly parts changers!!!!!!!!!!😢😢😮😅😢

  • @jimbeam275
    @jimbeam275 Před 4 měsíci +1

    This video gave me so much damn anxiety, whoa man

  • @richritchie5434
    @richritchie5434 Před 3 měsíci

    What I’ve learned is the most convenient and cost effective way is do replace the complete bearings assembly. Come with seal kit, bearings housing and coupler…and gasket….

  • @user-rz8ps4js5m
    @user-rz8ps4js5m Před 4 měsíci +2

    It looks like the impeller broke off the shaft. That broken coupler spins to freely for that size pump. And why use 2 coupling when you could have just put the valve on the pipe then tie it back into the other pipe with one coupling. Less change for leaks. But then it nice to sit on my couch and be the Quarterback. Great job

  • @arias3angel
    @arias3angel Před 3 měsíci

    It also seemed like the tube bundle was leaking. Might want to replace that as well..

  • @jeffreykubiak5126
    @jeffreykubiak5126 Před 4 měsíci

    😢Feel for you brothers good job nightmare !

  • @bigc8300
    @bigc8300 Před 4 měsíci

    Wow that there is a Chit Show my friend.

  • @christopherleubner6633
    @christopherleubner6633 Před 4 měsíci

    You could get a flex coupler and fix the old pump if the bearings are ok. They do wear out eventually. In this case you made the right call for replacement over repair as the original was subjected to fairly severe abuse that made the flex coupler fail.❤

  • @mannytaurus
    @mannytaurus Před 4 měsíci

    Looking forward to the follow up video but man all the equipment has been neglected for a long time, job security for you guys I guess lol

  • @matthewgregory8218
    @matthewgregory8218 Před 3 měsíci

    9:45 there will be announcements by the super for the water shutoff?

  • @TinaLucindaNekoMolly
    @TinaLucindaNekoMolly Před 3 měsíci

    I understand using pro press in a pinch or emergency repair but this was a solder joint seriously just sweat old valve out and either replaced with proper valve or pro press blank till like Monday when you can get proper valve

  • @michaelpaulsen64
    @michaelpaulsen64 Před 4 měsíci

    Yeah, I’ve had one rip before those gaskets are pretty flimsy a lot of times I’ll ask for an extra one if they have them sometimes they do sometimes I don’t you think they’d be a little more durable

  • @zourig
    @zourig Před 4 měsíci

    Hello from France, can't you freeze the pipe ? We're used to do this here in these kind of situations.

  • @andresland9906
    @andresland9906 Před 4 měsíci +1

    The flow switch should've prevented the boiler from coming on because there's no flow. That is called the primary pump not just the pump.

  • @elcrazy8017
    @elcrazy8017 Před 2 měsíci

    I would of replaced the whole header and gasket in the first place. Especially how you found it leaking the day before.

  • @thetheorizxr
    @thetheorizxr Před 4 měsíci +1

    Can’t believe this call 😂 one thing after another

  • @quantaearth1
    @quantaearth1 Před 4 měsíci +1

    JMT - I've been watching lots of your videos and the question I have is - why do you say 'we do everything diy?' You are obviously a professional and seem to be damn good at what you do...are you not certified with the brands you service? Not knocking you - just genuinely curious

    • @JumpermanTech
      @JumpermanTech  Před 4 měsíci

      Hey, great question. Thank you for the compliment 🙏 I am a HVAC/R professional and fully certified to perform the work that I do. The reason I mention "DIY" is because I have many videos on my channel where I've done DIY projects such as installing LED lights in various applications, small construction jobs and even build computers from scratch. Thank you for watching! 🔧⚡️

  • @GackFinder
    @GackFinder Před 4 měsíci +1

    Hey man, when replacing valves, if you had to chose between only installing new gate valves or only installing new ball valves, what would you chose?

    • @JD-hr6dr
      @JD-hr6dr Před 4 měsíci +4

      Ball valves less likely to leak, but sometimes get seized in a single position.
      Ball valves are superior overall, but they are bigger and often more expensive. When space is a consideration, Gate valves are better

    • @christopherleubner6633
      @christopherleubner6633 Před 4 měsíci

      As a rule balll valves are my favorite because they shut off at two points, gate valves only one point internally. Gate valves are cheaper, though. Really depends on the use case.

  • @ryans413
    @ryans413 Před 2 měsíci +2

    What you should have done first is change that broken valve that way you could isolate the boiler and not have to shut down the entire building of water. Then work on the boiler. That’s just me though.

    • @JumpermanTech
      @JumpermanTech  Před 2 měsíci +1

      We had to shut down the main water supply to everything in order to change the valve in order to isolate that one boiler. Thanks for watching! 🔧⚡️

    • @ryans413
      @ryans413 Před 2 měsíci

      @@JumpermanTech I know you should have done that first the valve then with the boiler isolated you could have come back later to do the pump. You found the broken valve and just ignored it and went on to do the pump and made it a little harder on yourself.

  • @stevencossaboon3237
    @stevencossaboon3237 Před 4 měsíci +1

    Great job Jumper Man.

  • @dougstuart9222
    @dougstuart9222 Před 4 měsíci +3

    Need some vice grips

    • @JD-hr6dr
      @JD-hr6dr Před 4 měsíci +3

      Exactly. Vice grips would have turned that valve without chewing it up more

  • @davidperry4013
    @davidperry4013 Před 4 měsíci

    You should’ve stocked a few spare valves in a good assortment of sizes. Sometimes Home Depot is a good option.

  • @waterhill623
    @waterhill623 Před 4 měsíci +1

    NYC 😂everything looks like a nightmare

  • @scottmaz4063
    @scottmaz4063 Před 4 měsíci +1

    Great job JMT

  • @michaelbuxton9368
    @michaelbuxton9368 Před 4 měsíci +3

    That place is a hot mess!!

  • @qewobob
    @qewobob Před 4 měsíci

    what do you mean by you do everything DIY?

  • @greekmaster1001
    @greekmaster1001 Před 3 měsíci

    Couldn't you freeze the pipe?

  • @VinylToVideo
    @VinylToVideo Před 4 měsíci +1

    Does nobody solder anymore?

    • @warmowed
      @warmowed Před 3 měsíci +1

      A lot of guys do, and a lot of guys don't. Although I do understand when pressing is needed. Jumperman did a video where there was so little access to the pipes due to the order they were installed that the only way to make a repair without repiping everything was with press fittings. I think in situations like this it is also fine to press (under time pressure and in a non-ventilated space; possibly the only 2" valve they had on hand). But I agree soldering is the gold standard. The press fittings aren't any less reliable, but they make repairs more difficult and cost more.
      I don't like seeing press fittings on easily accessible pipes in residential, that's just being lazy and racking up a big bill for the customer. I see guys do a garden hose replacement and do like 20 presses and it just seems ridiculous and non-servicable.

  • @kenrolle2338
    @kenrolle2338 Před 4 měsíci +1

    If there so much riding on these boilers why is there no redundancy.

  • @you166mhz
    @you166mhz Před 4 měsíci

    a professional under stress -- got it done ...

  • @top0nic
    @top0nic Před 4 měsíci

    why bypass is open ?

  • @ILoveKittys78
    @ILoveKittys78 Před 4 měsíci +2

    😻💚💜💚

  • @user-mn9gj9op1n
    @user-mn9gj9op1n Před 4 měsíci

    Those ripples marks are extrusion defects when the fitting was made

  • @JesseDoesHVAC
    @JesseDoesHVAC Před 3 měsíci

    Bruv thats why you gotta out in a “nightmare job tax” on the quotes especially for these poorly maintained plant room equipment! Its a can of worms half the time. I always have a clause in our quotes basically telling the customer your paying extra if we uncover more issues

  • @christopherleubner6633
    @christopherleubner6633 Před 4 měsíci

    25:13 judicious use of a 🔨 gently. Been there before. Use RTV to seal the new one on.

  • @c21meister
    @c21meister Před 3 měsíci

    Omg 😮

  • @MrAsxetos1
    @MrAsxetos1 Před 4 měsíci +1

    even if you change the pump you will still have a leak from the front :(

  • @matthewgrallert1603
    @matthewgrallert1603 Před 4 měsíci

    That pump will come off of that volute. It's just stuck. You will have to force. But you know that by now i suspect.

  • @kc0eks
    @kc0eks Před 4 měsíci

    What the heck does dude say in the intro? Whatever he says about DIY I just can't figure it out.

  • @cliveramsbotty6077
    @cliveramsbotty6077 Před 3 měsíci

    i love how american plant rooms look like they're in the 1940s

  • @OverKillPlusOne
    @OverKillPlusOne Před 4 měsíci

    That bypassed pressure regulator is sus. Could’ve caused that whole leak situation too.

  • @EyebrowsMahoney
    @EyebrowsMahoney Před 4 měsíci

    Man what a rats nest of pipe. I feel like that building had gone through several different boilers to have that screwed up of a pipe layout. The fact that they had the bypass open with the pressure regulator open probably says that the regulator is trashed too.
    All these building owners just don't wanna do maintenance and then complain when everything is broken and complain and beat up on technicians doing whatever bubblegum fix they can to make it keep working because they don't want to pay to fix it properly. That bypass shouldn't even be open - so either their new boilers outflow the reg, or the reg is trash. Honestly not surprised that the pumps are the way they are. I mean looks like there's even a storage tank that's AIP'd in there for probably rotting out.
    It's just so typical man. Can't stand it. You got these big name places reporting record profits, raising prices to consumers, but their buildings and equipment are held together with chewing gum and a prayer and a massive safety/health hazard...

  • @kaloiankrastev6851
    @kaloiankrastev6851 Před 4 měsíci

    Man, hold on..... i see you in trouble... but Dont panic and think out of the box. If you cant flip that valve in off position you have only one thing to do: Those pipes are copper just cut the pipe, pinch it with pliers and braze it, Thats gonna hold till you sort out another pump problem! You can thanks me later... and please get your self socket set if you wanna play with this big boys!!!

    • @chuckd5819
      @chuckd5819 Před 4 měsíci +1

      The dude is not posting this in real time, he's long gone from that problem.

    • @kaloiankrastev6851
      @kaloiankrastev6851 Před 4 měsíci

      yeah i know that.... just giving him some last hope options....@@chuckd5819

    • @thetheorizxr
      @thetheorizxr Před 4 měsíci

      Nah why spend time brazing and cutting if you just need to go back, circuit is offline anyways, best to do it all at one go when your not exhausted but yeah definitely would work in a pinch

    • @kaloiankrastev6851
      @kaloiankrastev6851 Před 4 měsíci

      well my answer were just in case in the midle of the night and no spare valve and couplings in the van. But anyway he did the right thing@@thetheorizxr

  • @scottmaz4063
    @scottmaz4063 Před 4 měsíci

    Just change the impeller

  • @scottmaz4063
    @scottmaz4063 Před 4 měsíci

    Motor mounts shot

  • @jeremiahsfoods
    @jeremiahsfoods Před 4 měsíci

    Fucking nightmare 😂😂 quote them for a new unit 💀💀

  • @gzahirny
    @gzahirny Před 4 měsíci

    Why didn't you just rebuild the clutch? Would have been simpler and cheaper for the customer...

  • @EWB66
    @EWB66 Před 3 měsíci

    You did a lot of work for nothing. All you had to do was replace the coupler. At most replace just the bearing assembly. You are costing your customer a lot of money that they don't need to spend.

  • @whyyoupissmeoff
    @whyyoupissmeoff Před 3 měsíci

    Remove set screw on motor to impellor shaft

  • @stormeagle28
    @stormeagle28 Před 2 měsíci

    What I don't get about such places - if a night in those rooms is that expensive, which beat-down equipment they rely on. That's a disaster just waiting to happen and sooner or later it *will* happen.