HVAC Videos For Beginners

Sdílet
Vložit
  • čas přidán 19. 04. 2022
  • HVAC videos for beginners. HVAC troubleshooting tips. AC is not cooling but the fan is running. Two apartment air conditioners are not cooling properly.
    If you'd like to support the channel, you can do so by shopping for tools or whatever you need on AMAZON at no extra cost to you through this link,
    amzn.to/3sLjyNv
    Tools That Can Make You Easy Money: www.dirtymaintenancenation.co...
    If I've provided any value for you and you'd like to donate $1.00 or more into my online tip jar, you can do so through this link, (all cards accepted)
    squareup.com/store/dirty-main...
    Friend me on Facebook! dirtymainten...
    This page contains affiliate links, which means that if you click on the link and make a purchase, I’ll receive a small commission at no extra cost to you. Lex Vance is a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to amazon .com
    #propertymanagement #maintenancetechnician #multifamilyhousing #apartmentmaintenance #handyman #Tallahassee
  • Zábava

Komentáře • 140

  • @LexVance
    @LexVance  Před 2 lety +1

    The Best HVAC Tools for New Technicians: www.dirtymaintenancenation.com/the-best-hvac-tools-for-new-technicians/
    Tools That Can Make You Easy Money: www.dirtymaintenancenation.com/diy-tools-for-men/
    If you'd like to support the channel, you can do so by shopping for tools or whatever you need on AMAZON at no extra cost to you through this link,
    amzn.to/3sLjyNv
    If I've provided any value for you and you'd like to donate $1.00 or more into my online tip jar, you can do so through this link, (all cards accepted)
    squareup.com/store/dirty-maintenance-nation
    This page contains affiliate links, which means that if you click on the link and make a purchase, I’ll receive a small commission at no extra cost to you. Lex Vance is a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to amazon .com

  • @danelamb79
    @danelamb79 Před 2 lety +36

    I'm HVAC tech with 25 years experience, the double up dryers one should be removed. It really taxes the compressor just like a kinked line with the extra restrictions of the second dryer. It can cause the liquid to start to flash to gas just like a metering device and not feed the txv with a solid collum if liquid causing all kinds of problems. IMHO I would remove the one inside the unit, that way if you have to change the dryer you can just pump down the unit instead of having to recover it. I know you like to install them in factory location but that why I always relocate them, it's a time and labor saver in the future. Hope this helps you out. You do a great job I don't want you to think I'm criticizing you about dryer location just trying to help you out. Love your content

    • @LexVance
      @LexVance  Před 2 lety +9

      Right on Dane! I agree. You're right about the restrictions and the easy pump down in the future. Thank you so much for watching!

  • @Cuete590
    @Cuete590 Před 6 měsíci +11

    I’ve been warehousing for 10 years and lately hvac has been catching my attention this is interesting stuff right here !

    • @LexVance
      @LexVance  Před 6 měsíci

      Thank you so much for watching!

    • @vanessamontes1463
      @vanessamontes1463 Před měsícem

      Get into it brother

    • @topdawgtate7426
      @topdawgtate7426 Před 27 dny

      I’ve been in a warehouse the last 6 years and I start HVAC on Monday. Super excited

    • @WTFDEMXNTIME
      @WTFDEMXNTIME Před 21 dnem

      i’m 21 just started in a hvac school actually this shit will change your life brother

    • @vladthedude7231
      @vladthedude7231 Před 18 dny

      I’m thinking getting into this but I’m nervous

  • @Eddy63
    @Eddy63 Před 2 lety +11

    After a stressful day that blunt roaster might be a good ole buddy to have 😂🤣😂 ... Thx for sharing ... You make me laugh ...

    • @LexVance
      @LexVance  Před 2 lety +3

      👍😆👍 Felt like I was in one of those old Cheech and Chong movies I use to watch. 🤣 Good to hear from you Eddy!

  • @abrahammiron8319
    @abrahammiron8319 Před 2 lety +2

    Thanks for the tip on those hard starts. I have the same Goodman condensers at my current property so it’s good to know that those hard starts tend to trip the breaker when they go bad.

    • @LexVance
      @LexVance  Před 2 lety +1

      Thank you so much for watching Abraham!

  • @NETWizzJbirk
    @NETWizzJbirk Před 2 lety +3

    If only I wasn't stuck in a meeting.. I cannot wait to watch. Usually HVAC as you know is easy... It's does it cycle on running both indoor and outdoor fans and the compressor then whether or not all the refrigerant leaked out. It's a mess fixing a leak though ripping out an EVAP coil on their third floor...it seems they never pump down especially the rotary compressor units which run on a prayer and a hard start just to get them in the mood to run.

    • @LexVance
      @LexVance  Před 2 lety +1

      Right on Justin! Thank you so much for watching!

  • @MoeManfrm8824
    @MoeManfrm8824 Před 4 měsíci +6

    I’m going into hvac soon and I’m loving this.

    • @LexVance
      @LexVance  Před 4 měsíci +2

      Thank you so much for watching!

    • @lazarogonzalez4537
      @lazarogonzalez4537 Před 3 měsíci +3

      Well worth it I just recently jumped into the refrigeration field

    • @Gervy12
      @Gervy12 Před dnem

      Is hvac hard

    • @LexVance
      @LexVance  Před dnem

      Not when you get used to it and learn it. It is at first but you have to stay with it and be disciplined.

  • @generationtestimony6423

    That was majorly helpful!!! Thank you

    • @LexVance
      @LexVance  Před 2 lety

      You're welcome! Thank you so much for watching Generation Testimony!

  • @cleftheart1969
    @cleftheart1969 Před rokem +2

    I'm taking a h vacation class just starting...this gives me a good idea 💡 what to expect thanks 😊 🙃 🙂 😅 👍🏾

    • @LexVance
      @LexVance  Před rokem

      Thank you so much for watching Cleft!

  • @soloch69
    @soloch69 Před 2 lety

    Great video bro keep them coming, I work on the property and I sometimes have to close out work orders and the ones that I look at is the commons that the other maintenance guys report AC unit is ice up and all they do is add refrigerant don’t even look for leaks this is sad and don’t even know the superheat or sub cooling and we are talking about the senior tech🧰 at that 🤦‍♂️

    • @LexVance
      @LexVance  Před 2 lety +1

      Right on! Thank you so much for watching Solo Tech!

  • @parkerbufkin6187
    @parkerbufkin6187 Před 2 lety +4

    Lol you kept talking about that blunt makes us wonder why you didn't film inside 🤣🤣

    • @LexVance
      @LexVance  Před 2 lety +2

      The guy was posted up on the couch chiefing away. 😆

  • @jaysonescoe5799
    @jaysonescoe5799 Před 2 lety

    I won’t beat a dead horse on this one. Yep good stuff as usual my friend!!

    • @LexVance
      @LexVance  Před 2 lety

      Thank you so much for watching Jayson!

  • @robertpenczar8930
    @robertpenczar8930 Před 2 lety

    Lex another informative video

    • @LexVance
      @LexVance  Před 2 lety

      Thank you so much for watching Robert!

  • @ftwbreeze
    @ftwbreeze Před 2 lety +1

    Hello Lex, I agree two filter dryers are one too many. Would like to hear from the tech that installed new compressor. Your content is refreshing, many thanks Lex!

    • @LexVance
      @LexVance  Před 2 lety +1

      Thank you so much for watching Breeze!

    • @rrodgers3285
      @rrodgers3285 Před 2 lety

      screw that call n get ur money back tell them take mickymouse back to Florida with their transgender education they try to indoctrate

    • @ryanroberts8135
      @ryanroberts8135 Před rokem +1

      2 filter driers is also twice the restriction in the head pressure. It’s going to cause more w/t on compressor.

    • @JustinRivera-sq6cf
      @JustinRivera-sq6cf Před 4 dny +2

      I heard it's bad b/c it Acts as a metering device (txv)

  • @techfive7202
    @techfive7202 Před 2 lety +7

    Look on the back of that electrical panel on the condenser. It'll tell you the design subcool/temperature charge correlation with ambient and indoor temperatures. Normally Apt ac's are oversized anyways so doesn't have to be perfect unless you're working on 3rd floor end unit. Unit with a high load that is.

    • @LexVance
      @LexVance  Před 2 lety

      Right on TechFive! Good to hear from you, man!

  • @justwork_hvac
    @justwork_hvac Před 2 lety

    the hvac guy said that the maintenance guy won't know they use ryobi drills 😂.. two filter are better then one 😂... but all joke aside thank you for all your great video big fan of yours.. I watched your cpo video. and sure enough I passed it the guys I knew I didn't sit with them 😂..

    • @LexVance
      @LexVance  Před 2 lety

      👍😆👍 Nice! Way to go Rudy!

  • @Optimal_Living01
    @Optimal_Living01 Před 9 měsíci +1

    Bro keep posting Im learning from ya

    • @LexVance
      @LexVance  Před 9 měsíci +1

      Thank you so much for watching!

  • @realSamAndrew
    @realSamAndrew Před 2 lety +4

    My guess on the high SH would be an extra long lineset since it's apts. and you have multiple floors and long runs.

    • @LexVance
      @LexVance  Před 2 lety

      So true! Thank you so much for watching Sam!

  • @alexcannova2271
    @alexcannova2271 Před 2 lety +5

    You should be good on the superheat thing since it's a txv I was always taught its the subcool that matters you would pay more attention to superheat if it was a piston . Superheat for piston subcool for txv is my rule at least .

    • @LexVance
      @LexVance  Před 2 lety +1

      Right on Alex! Good to hear from you, man!

    • @williamschieber4236
      @williamschieber4236 Před 2 lety +3

      Yes subcool for txv but super heat is still very important even on txv system . Still must know super heat to ensure the txv is metering correctly

    • @alexcannova2271
      @alexcannova2271 Před 2 lety

      @@LexVance thanks lex you too buddy

  • @SteveTJ001
    @SteveTJ001 Před 2 lety +6

    Another great video Lex, thanks you! My 2 main thoughts after watching this video are this:
    A: The fact that those units come from the factory with a hard start kit to me is a big red flag of poor engineering. I took hvac courses back in the early 2000’s and I don’t ever remember a situation with a hard start kit being installed at the factory, seemed like it was always an option to be installed in the field after if a compressor for being troublesome and popping breakers
    B: Correct me if I’m wrong but with all the problems you are seeing on those units, how much research did the apartment complex honestly do before deciding to install those over the entire property when it was built? So sad that we are in the day and age where the lowest bidder is always what wins.
    Anyways, just a few thoughts I had, keep up the great vids!

    • @LexVance
      @LexVance  Před 2 lety

      Thank you so much for watching Steve!

  • @vladthedude7231
    @vladthedude7231 Před 18 dny

    I’m thinking on getting into this I hope I do good

    • @LexVance
      @LexVance  Před 18 dny +1

      Thank you so much for watching!

  • @phillipgroom9187
    @phillipgroom9187 Před 2 lety

    Thanks for sharing the video. I hope you don’t have to change out those txv and all those dryers. Good job. Safe safe out there.

    • @LexVance
      @LexVance  Před 2 lety

      Good to hear from you Phillip!

  • @TexMex508
    @TexMex508 Před 2 lety +1

    Can you make a video about the phase out of 410 and new freon that will replace it

    • @LexVance
      @LexVance  Před 2 lety +1

      Will do TexMex! I've been watching and keeping my feelers out on this. Hopefully someone who works in actual HVAC can help you out more on this here in the comment section. Thank you so much for watching!

  • @Kilcrops0914
    @Kilcrops0914 Před 2 lety +2

    If your line set goes underground your superheat may be high if you check it outside. Have you checked your true superheat upstairs at the air handler?

    • @LexVance
      @LexVance  Před 2 lety

      No, I'll start doing that as the line set does go underground. Great idea Carlos! Thank you!

    • @ryanroberts8135
      @ryanroberts8135 Před rokem

      True your SH should depend on length of line set as well as if coils are clean, I would never dump extra refrigerant in without making sure you got proper air flow. Think about it, what is more likely event to cause coils to ice up ? A leak in a sealed unit which is not subject to wear on lines since they stationary ? Or coils getting dirty over time which increases the pressures since they raising temperature from restricted air flow ? In my 10-12 years experience I have solved the problem by cleaning coils 60% of time, the othe 40% is refrigerant leaks either shoddy installs or units 15-20 years old.

  • @DanO181919
    @DanO181919 Před 2 lety +1

    Working hospitality maintenance…. Smell the reefer all day everyday in the hotel. Especially in a larger complex.

    • @LexVance
      @LexVance  Před 2 lety +1

      👍😆👍 It was like Cheech and Chongs place up in there. Good to hear from you Danny!

  • @manino04baby
    @manino04baby Před 2 lety

    I straight pipe the filter dryer inside with copper and put a new one on the outside of condenser

    • @LexVance
      @LexVance  Před 2 lety

      I like that! Thank you so much for watching manino!

  • @edwardgarza5104
    @edwardgarza5104 Před 2 lety +2

    Your saying you can never get the superheat below 20? Even by adding charge? Either semi stop up txv, undersize TXVs or sometimes there's strainers b4 the TxV those could be plugged due to being a appartment complex installs go really fast and not much care goes into it, thoes be my guesses

    • @LexVance
      @LexVance  Před 2 lety +2

      I can try to add a little more refrigerant and see. I've never tried that. The subcool would be closer to 20 though. That don't seem right either. Thank you so much for watching Edward!

    • @edwardgarza5104
      @edwardgarza5104 Před 2 lety +2

      @@LexVance yes your right the subcool would increase. As long as superheat is around 5-20 with a txv and your close to your subcooling I say your good. But yeah a 28 superheat with the subcool spoton , indicates a restriction. Filter dryer ,txv , strainer ECT could be the issue. Check to see if you have more than 3 degrees across filter dryer that would indicate restrictive dryer

    • @LexVance
      @LexVance  Před 2 lety

      @@edwardgarza5104 Right on, thank you Edward!

    • @dalitohana6979
      @dalitohana6979 Před 2 lety +2

      @@edwardgarza5104 I just wonder if all the factory installed filter dryers are restricted or semirestricted seems like problems started like 2-3 years into them being in operation. I think I would remove the factory installed filter dryer the contractor left in the unit and replace the one the contractor put outside and see what your superheat is then. Maybe bad dryers are causing the evap coils to go bad prematurely. Just thinking out loud. You could also check the temp difference on both the factory installed filter dryer and the filter dryer the contractor installed that would be interesting.

    • @ryanroberts8135
      @ryanroberts8135 Před rokem

      True not just bad apartment installations but how many apts do techs clean BOTH coils ? Most techs rather clean outdoor coils and give extra shot of refrigerant. Granted in some apt setups it’s harder to get to indoor coils unless there is mechanical closet but restriction that close to TXV could be your issue.

  • @MoeManfrm8824
    @MoeManfrm8824 Před 4 měsíci

    So would you recommend an HVAC school that offers classrooms to simulate the work or online? My only toss up is the time difference between in person and online in person is 11 months and online at six or less

    • @LexVance
      @LexVance  Před 4 měsíci

      Although I've never been to an HVAC class, I'd like in person for hands-on experience. I learn better by doing. Thank you so much for watching!

  • @juliopinero3878
    @juliopinero3878 Před 4 měsíci

    I've been repairing electrical/electronics for over 40 years. I Now teach AIRC technology. Looks like you have some skills! The only thing I would recommend is for you to reference the installation and parts manual as opposed to using the procedures used in the past. The industry is changing fast!
    The capacitor that was changed out (30/5mfd), may have been the correct cap for the rotary compressor. The only way to know for sure is to reference the parts manual instead of : "all rotary compressors comes with a 45 mfd"! That's just not true! It's possible this one did; however, you don't want to be the goofball replacing a cap with the wrong value. The only way to know for sure is by referring the parts manual with the model number of the unit.
    Also, you don't mention what subcooling the unit calls for. If it called for 8 +/-1, the unit was overcharged because it was running at 12 degrees subcooling. It was 3 degrees off. This information you will find in the installation manual, service manual, or data plate.
    This is why its very important to reference the manuals. You may have been stressing the super heat when all along there was nothing wrong with it. Old Industry standards are changing! Read the manuals! Don't assume all units and/or brands work the same. Once you have read the manuals x many times, you won't need them anymore.
    Good luck!

    • @LexVance
      @LexVance  Před 4 měsíci

      Thank you so much for watching!

  • @cutum
    @cutum Před 2 lety +2

    Smoke em if ya got em. 😆

    • @LexVance
      @LexVance  Před 2 lety +1

      👍😆👍 Good to hear from you cutum!

  • @user-yv4np4ur3q
    @user-yv4np4ur3q Před 3 měsíci

    He's chiefing a blunt 😂😂

    • @LexVance
      @LexVance  Před 3 měsíci

      👍😆👍 Thank you so much for watching!

  • @MichaelMckenzie-hd8sz
    @MichaelMckenzie-hd8sz Před 5 dny +1

    I want too learn hvac but no jobs hire without experience

    • @LexVance
      @LexVance  Před 5 dny

      I got in by starting out on student housing properties. They'll hire anyone. If you have a college around you, Google student housing and go apply at those properties.

  • @jamesrooney7689
    @jamesrooney7689 Před rokem +1

    lex i have a goodman heat pump i have therostat set a 67 and temp coming out of the vents is 84 is that normal thank you

    • @LexVance
      @LexVance  Před rokem

      Either heat strips are stuck on and you'll need to replace the sequencer or your reversing valve is stuck and will need to be replaced. Or, the 24v orange wire is not getting power. The orange wire has to have power for cooling.

  • @adamdavis8515
    @adamdavis8515 Před rokem

    Do you have a link for purchasing that multimeter? Tia

    • @LexVance
      @LexVance  Před rokem +1

      Click on the Amazon link below and type in Craftsman multimeter. They may not make it anymore. Fieldpiece is a great meter too. Just look at the picture and make sure it has the MFD setting. That's the microfarads setting you'll use to test capacitors. Thank you so much for watching Adam!

  • @gaoutdoor4372
    @gaoutdoor4372 Před 2 lety

    The last ac unite got big leaks, can you use LEAK SAVER to save it?

    • @LexVance
      @LexVance  Před 2 lety

      A guy on CZcams put some Leak Stopper in a pickle jar and let it sit. It turned into sludge. Almost a hard wax. I don't trust that stuff and don't want it to ruin the system. So, I just fix it the right way. Thank you so much for watching GA!

  • @MrPrinceA1of916
    @MrPrinceA1of916 Před měsícem

    I was taught that the subcool should be between 8-12, and the super heat should match. Is that true?

    • @LexVance
      @LexVance  Před měsícem

      Yes, however getting them to match isn't always easy. Just try and get them close. Some equipment in the real world just can't do it. The instructors equipment in a class room can do it easily. But, come out in the real world where things are mix matched and not installed correctly and see if an instructor can do that. I highly doubt it. Thank you so much for watching!

  • @louiegarcia6189
    @louiegarcia6189 Před 2 lety

    The old filter could be a restriction later on or very soon. That is not good for the new compressor...

    • @LexVance
      @LexVance  Před 2 lety

      So true! Thank you so much for watching Louie!

  • @bernardolunafigueroa6438
    @bernardolunafigueroa6438 Před 10 měsíci

    Hey where did you do your training

    • @LexVance
      @LexVance  Před 10 měsíci

      I've never had training or went to school. I watched HVAC videos on CZcams and then just got out there on property and figured it out. I made a lot of mistakes but mistakes are our greatest teachers. Mistakes breed experience and experience breeds wisdom. Thank you so much for watching!

  • @parkerbufkin6187
    @parkerbufkin6187 Před 2 lety

    Do you ever try adding leak seal before you replace coil?

    • @LexVance
      @LexVance  Před 2 lety

      No, there was a guy on CZcams who put that stuff in a pickle jar and let it sit for a week. It turned into hard sludge. I'm scared it'll wreck the whole system. Thank you so much for watching Parker!

  • @wes4619
    @wes4619 Před 9 měsíci

    Did you put a bigger hard start on then?

  • @noelv1976
    @noelv1976 Před 2 lety +1

    I need to get the digital gauge. Or have the company buy one lol

    • @LexVance
      @LexVance  Před 2 lety

      Yep! Have your company get them. 👍 Thank you so much for watching Jean!

  • @alexjimenez2568
    @alexjimenez2568 Před 2 lety +1

    i change the fan motor and the capacitor my AC still won't run what could be ? the contactor ?

    • @LexVance
      @LexVance  Před 2 lety +1

      It could be. I would need to be there to see if its getting voltage. It needs high and low voltage. 240 and 24 volts. I would need to be there with my volt meter. Thank you so much for watching Alex!

  • @analogmoz
    @analogmoz Před 2 lety +1

    Factory-installed filter driers inside condensing units should be banned. I'm not as riled up about the filter being installed outdoors but almost everyone says having it as close to the expansion device as possible to prevent any potential moisture from flashing into ice right at the TXV/piston.
    At least that is my opinion.

    • @LexVance
      @LexVance  Před 2 lety +1

      Right on, good to hear from you Big N8!

    • @txta786
      @txta786 Před 2 lety

      Filter dryers or accumulators are found in the engine bay on every vehicle exposed to extreme temperatures. They seem to do alright.

  • @therealanthony4978
    @therealanthony4978 Před 2 lety

    Man I’m in Texas it’s getting hot and my ac not cooling let me see if replacing the capacitor with a 45/5 will work . I’ve already cleaned it out .

    • @LexVance
      @LexVance  Před 2 lety

      I hope it all works out for you Anthony! 🤞

    • @therealanthony4978
      @therealanthony4978 Před 2 lety

      @@LexVance so the one I removed says 35/30 I bought the 35/30 440v replaced it and now the fan isn’t running outside should i try the 45/5 ? Or that a hazard ?

    • @LexVance
      @LexVance  Před 2 lety

      @@therealanthony4978 You may have a bad fan motor or a wire is misplaced.

    • @therealanthony4978
      @therealanthony4978 Před 2 lety

      @@LexVance so I had the ac guy come out and it just needed free on I forgot to turn the breaker back on that’s why the fan wasn’t spinning 😵‍💫 hahahaha thanks for your help man !

  • @johnprince8171
    @johnprince8171 Před 2 lety

    That's what happened overworked start kit

    • @LexVance
      @LexVance  Před 2 lety

      Thank you so much for watching John!

  • @1stFlyingeagle
    @1stFlyingeagle Před rokem

    So I see in this vid Fieldpeice gauges and not testo. Why? Why did you buy fieldpiece?

    • @LexVance
      @LexVance  Před rokem

      I own my own set of Testo gauges. The Fieldpiece are the propertys and I use them to prevent wear and tear on my Testos. Thank you so much for watching Robert!

    • @mostlikelywedoitservices6926
      @mostlikelywedoitservices6926 Před rokem

      @@LexVance Smart man.

  • @ehrenlloyd-ty9pd
    @ehrenlloyd-ty9pd Před rokem

    The old filter drier should have been replaced

    • @LexVance
      @LexVance  Před rokem

      So true! Thank you so much for watching Ehren!

  • @wes4619
    @wes4619 Před 9 měsíci

    What are the numbers your refering to?

  • @ReginaPhalange917
    @ReginaPhalange917 Před 9 měsíci

    Hi, quick question I found you on a CZcams search for HVAC heating and cooling. Trying to help my son I’m a single mother, putting my son through trade school for heating and cooling HVAC. he’s struggling severely. He just started about a week or so ago and had a test two days after school started for the math part and didn’t do well. it is super hard for him and he has to learn everything so damn quickly very fast and the teacher he has is AWFUL and rude. he’s getting very discouraged and wondering if this is really for him. I want to keep motivating him, but don’t know a thing or have any men around that know about this. if you had any tips for new students, that would be greatly appreciated. (cause i’m sure you’ve been there lol) I understand if you’re very busy. thank you 🙏 Have a great day! 👍

    • @LexVance
      @LexVance  Před 9 měsíci +1

      I'm an apartment maintenance tech. We don't have to go to HVAC school so I've never taken a class in anything so I'm not sure my advice would help as I've never been to HVAC school. Apartment maintenance will always welcome your son with open arms, though! Thank you so much for watching!

  • @tylerstewart3035
    @tylerstewart3035 Před 10 měsíci

    What kind of math do I need to know to do hvac? I’ve never been good at math I only know algebra

    • @LexVance
      @LexVance  Před 10 měsíci

      I don't do any math. Unless you're an installer and measuring duct, all you need to know are pressures which gets easier the more you do it.

  • @robertmunguia250
    @robertmunguia250 Před 2 lety

    Why those units so low to the ground?

    • @LexVance
      @LexVance  Před 2 lety +1

      I don't know? Great question, though. Thank you so much for watching Robert!

    • @robertmunguia250
      @robertmunguia250 Před 2 lety

      @@LexVance watch them floods.

  • @jakestone2591
    @jakestone2591 Před 11 měsíci

    I'm 15 years H-VAC...he really should have changed out that filter.

    • @LexVance
      @LexVance  Před 11 měsíci

      Thank you so much for watching!

  • @brieri418
    @brieri418 Před 2 lety

    Instead of replacing the coil. Why not just replace the air handler it’s a hell of lot cheaper then a coil

    • @LexVance
      @LexVance  Před 2 lety

      So true! 😆 Thank you so much for watching B Gunter!

  • @benjamintimmins1656
    @benjamintimmins1656 Před 2 lety

    2 filter driers is def WRONG!! You did em the right way skid...and a freakin contractor did that lol...

    • @LexVance
      @LexVance  Před 2 lety

      👍😆👍 Good to hear from you Ben!

  • @RickSegui
    @RickSegui Před 2 lety

    I just replaced a titan pro that went from 45uf to 20uf in les than 2years.
    They are made in China. The titan hd is made in America .
    I went to buy an MARS made in American and it’s assembled in Mexico.
    Went to another supply house and the MARS same part number as the other one Is made in American .
    MARS ADVERTISES “Made in American”. So, is assembled a legal play on words!

    • @LexVance
      @LexVance  Před 2 lety

      Thank you so much for watching Richard!

  • @jerryon9367
    @jerryon9367 Před 8 měsíci

    That's a muffler on the inside

    • @LexVance
      @LexVance  Před 8 měsíci

      Thank you so much for watching!

  • @brianhaller406
    @brianhaller406 Před 2 lety

    You shouldn't have 2 filters 🤪

    • @LexVance
      @LexVance  Před 2 lety +1

      👍😆👍 That's what I figured. Thank you so much for watching Brian!

  • @johnprince8171
    @johnprince8171 Před 2 lety

    Lazy did not want to change it.

    • @LexVance
      @LexVance  Před 2 lety

      Agreed. Thank you so much for watching John!

  • @user-dd1xm4hb5g
    @user-dd1xm4hb5g Před 8 měsíci

    need to be off