Over current relay solved numerical problem

Sdílet
Vložit
  • čas přidán 5. 09. 2024
  • Easiest way to solve numerical problem on the topic relay

Komentáře • 39

  • @adityajain2502
    @adityajain2502 Před 4 lety +1

    Good video for Semister exam, Thanks sir

  • @sauravmazumdar5369
    @sauravmazumdar5369 Před 3 lety

    Nice video...

  • @tanktejas6016
    @tanktejas6016 Před 3 lety +1

    1. Calculate the relay setting of single line diagram of radial feeder shown in the fig 1. The relay
    used are standard IDMT phase over current relay, having rated current of 1 A. The normal
    range of PS (Plug Setting) is fro 50%-200% of 1 A in equal step of 25%, where as TDS range is
    0.1 to 1 sec in steps of 0.05. The PS of relay R2 is givens 50% of CT Secondary rating and TDS
    is given as 0.2 Sec.
    How to solve example Sir

  • @great_India3344
    @great_India3344 Před 3 lety

    Very good video sir. Thank you sir

  • @debaranjan1
    @debaranjan1 Před 4 lety +4

    can we see an education system....where we can experience the same thing from today generation numerical relay, means how an over current setting is done, what are different over current setting are available and when to apply a particular setting , what are the different standards used for protection system setting, tools where we can check the relay operation with its behavior and can get a conclusion that the relay has operated as per the setting.
    We need our education system to change and teach the thing which are used at practical field...not just a book worm who has explored protection system just on a pen, paper and calculator.

  • @nimishbishnoi7365
    @nimishbishnoi7365 Před 4 lety +3

    use top=0.14*(TMS)/((fault current/settings current)^0.02-1)
    we can get the operating time of the relay for IDMT relay under normal standard condition
    top=operating time of relay
    tms=time multiplier setting

  • @sudhirsharma3435
    @sudhirsharma3435 Před 3 lety +2

    What ever you calculated the end result was from the given value in the question it self. 3 x 0.6 = 1.8 sec. Then why all these calculation required.

  • @ashishsoni3287
    @ashishsoni3287 Před 3 lety

    Thanks you..

  • @nadim606
    @nadim606 Před 2 lety

    Seen

  • @srinivasmamidala7828
    @srinivasmamidala7828 Před 4 lety

    How the rated secondary current 5 A is taken. Is that fixed for every problem or it will be changed according to the problem. And tell me how secondary current is taken?

  • @97542729
    @97542729 Před rokem

    Sir mujhe 33/11kv substation me relay cordnetion karna hai as per power transformer, 11kv main and feeder protection my substation in rural areas and feeder connected in agriculture fault generated havey my problem is cum to feeder fault feeder trip ho jata hi leki 11kv main and Transformer vcb bhi trip ho jata hai power transformer installed in my substation caipcity 8 mva 5 mva and 3.15 mva ct connected ratio 400-200/5 200-100/5 and 300-150/5 for transformer protection 300-150/5 and 200-100/5 11kv main and feeder protection relay connected make earth fault over current Numerical relay sir mujhe relay cordnetion bata do jisse ki feeder fault aane par feeder hi trip ho transformer Tak fault na jaye

  • @subratabepari4746
    @subratabepari4746 Před 3 lety

    how can we pass 50 amp secondary fault current through a relay of 5 amp relay? donot we need to change the CT ratio(1000/1)

  • @Subhajit_Ray
    @Subhajit_Ray Před 11 měsíci

    Sir ji 3.5 kaha se aya samjha nahi

  • @ssarkar7485
    @ssarkar7485 Před 4 lety

    Definition of trip current of relay

  • @yashchavan7384
    @yashchavan7384 Před 3 lety

    Sir what if the question starts in this way
    A 5a ,2.2 sec .....
    Sir will there be any changes in the ans ??

  • @luckymaurya1912
    @luckymaurya1912 Před 2 lety +1

    Psm =0.8
    Time is 3sec×0.8= 2.4 sec That is ans sir.

  • @josefinaiipolicarpio6647

    where you get TSM=0.6?

  • @serialupdates2330
    @serialupdates2330 Před 4 lety

    125% how it's get

  • @abhinavdancy5482
    @abhinavdancy5482 Před 4 lety +1

    3.5 kaise aya..???

    • @rahulkhatri6350
      @rahulkhatri6350 Před 4 lety

      It's a mistake waha par 3 second aayega

    • @rajeshtk1246
      @rajeshtk1246 Před 4 lety +1

      The value of time is to be taken from the time vs psm graph for the 3 sec relay for TMS = 1. Then, multiply that time with the TMS of 0.6. That will give you the answer.

    • @yashchavan7384
      @yashchavan7384 Před 3 lety

      @@rahulkhatri6350exam mai diya jayega ki if psm is 8 then the time of operation will be ______
      Jo exam mai diya jayega vo hi likhna hai

  • @SkillMaxTrainingSolutions-STS

    I have one smart excel sheet which you may see on my youtube channel. Final resultant value will be 1.97 sec using IEC SI curve.