Komentáře •

  • @emmanuellimjoco4709
    @emmanuellimjoco4709 Před 21 dnem

    The best detailed computation ever watch. Galing mo Sir God bless and thanks for sharing.

  • @justinlanielbaniqued2500
    @justinlanielbaniqued2500 Před 6 měsíci

    Thank you Sir! Dami ko na pong napanuod abt short ciruit analysis diko ma gets yung iba pero yung inyo na gets ko agad hehe. Na lilito po kasi ako nung una paano kunin KAIC rating ng mga CB, salamat Sir sa learnings po! God Bless po.

    • @RandyAmorTutorials
      @RandyAmorTutorials Před 6 měsíci

      Salamat sir for watching my video

    • @justinlanielbaniqued2500
      @justinlanielbaniqued2500 Před 5 měsíci

      Sir may question po ako, yung 500kva 3phase transformer po ba single phase pole mounted transformer na naka banking lang po ba na consist of 167kva each rating ganon po? Parang sinum up lang Sir? Thank you po. ​@@RandyAmorTutorials

  • @banjomirandilla3917
    @banjomirandilla3917 Před 4 měsíci

    Thank you sir clear and concise

  • @raphaelcacanog73
    @raphaelcacanog73 Před 7 měsíci

    nakakatulong po ito maraming salamat po

  • @ravenvillanueva7816
    @ravenvillanueva7816 Před rokem +1

    sir pano po pag from center meter ang pag babasehan? pwede ba mag based sa 80percent ng kaic kung saan naka tap yung fault?

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem +1

      Pag point-to-point method ang gamit mo kailangan mong mag simula sa source papunta sa point of fault kasi may factors na magdedepende sa fault current upstream ng fault point na gusto mong kunin.

  • @kamotipstv6980
    @kamotipstv6980 Před 3 dny

    sir anung program yang gamit mo?

  • @DemetrioBautista-r9k
    @DemetrioBautista-r9k Před 10 dny

    Saan po Eng’r. Nanggaling yung Table 4 “C”?

  • @gbgb8878
    @gbgb8878 Před rokem

    It was nice video. Kindly give english subtitles.

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem

      Thanks for the comment. I will try to put english subtitles to it.

  • @jonasfuertes5895
    @jonasfuertes5895 Před rokem

    2nd is, di ba natin gagamitin yung actual voltage doon sa computation assuming na may voltage drop na pagdating doon sa Location ng Fault? Thanks

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem +1

      Sir with regards to voltage used, ang voltage drop sa buong system ay limited to 3% from source to last point as per standards, so negligible na yung voltage drop. Kung gusto talaga nating gamitin yung actual voltage sa point of fault, pwede din naman pero mag calculate ka pa ng voltage at every point. Salamat sir and God bless.

  • @jonasfuertes5895
    @jonasfuertes5895 Před rokem

    Assuming na running yung ckt at nagkaroon ng Fault sa Point 3, hind po ba magkakaroon ng contribution sa Fault yung motor loads? Thanks

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem

      Yung point-to-point method, sabi ay kapag hindi significant yung motor contribution at pwede nang hindi isama. Sa dulo ng video pinakita ko yung fault currents at different points of the system with and without motor contribution. Salamat sir. God bless

  • @erickmanangan4803
    @erickmanangan4803 Před rokem

    Hello Engr. Nice video. Saan yan nilalagay A3 or A4 pag iaatached na at ipapasa for electrical permit? Thank you

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem

      Kasama po yan sa analysis na ginagawa at pinipirmahan ng PEE. Normally separate sheet sa A4

  • @alvinnobitski2159
    @alvinnobitski2159 Před rokem

    Sir tanong ko lang po, kapag po ang fault point po ay nasa Main distribution Panel, ang Length (L) po ba na gagamitin sa formula ay from MDP to service point lang o from MDP to transformer?

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem

      Consider mo yung length hanggang transformer kasi may contribution yung transformer sa fault current

  • @anniehofer4151
    @anniehofer4151 Před měsícem

    Sir, yung 500KVA sa simula san po sya kinukuha? Gumagawa kasi kami project sa residential house and di ko sure if sa schedule of loads ko ba kukunin yang KVA

  • @cas49713
    @cas49713 Před rokem

    Good day sir, accepted na ba ang poin-to-point method ng Bussman sa PEE exam or sa detail engineering? Thank you in advance.

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem +1

      Ang alam ko PU method ang accepted ng OBO for permit. Dapat na siguro mag update ng OBO sa acceptable method of calculation ng SC to include other methods. Pero magagamit mo tong methid na to for quick calculation para sa KAIC rating ng equipment

  • @Botchukoy
    @Botchukoy Před rokem

    sir, anung gamit mong app sa presentation?

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem

      Smath Solver (formerly known as Smath Studio) sir gamit ko jan. Free alrernative to Mathcad

  • @eduardodangoy9730
    @eduardodangoy9730 Před 10 měsíci +1

    sir pwuede maka hingi ng smath solver "worksheet short-circuit calculation" for reference, thanks

    • @RandyAmorTutorials
      @RandyAmorTutorials Před 10 měsíci +1

      You may download the file from my Facebook Group
      facebook.com/groups/usapangelektrikalph/files/files

  • @christophermillan6310

    good day po, constant po ba ang percentage ng impedance, or naka depende pomsa size ng transformer?at kung oo po,san po pwede macheck ang mga impedances na to?

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem

      Yung impedance ng transformer varies depende sa capacity at sa manufacturer din. Makikita naten ang % impedance ng transformer sa nameplate. Salamat sir question mo sir. God bless

    • @marvin082500
      @marvin082500 Před 5 měsíci

      @@RandyAmorTutorials Sir kung walang nakaindicate na impedance sa nameplate, ano ang gagamitin na impedance?

    • @RandyAmorTutorials
      @RandyAmorTutorials Před 5 měsíci

      @@marvin082500 standard nameplate ng transformer shall always include impedance. Pero kung di available for example eh nabura na or nawala yung nameplate, etc at wala kang sources ng information tungkol sa impedance, pwede kang mag refer sa IEEE std 142 or yung Gray Book. May table dun na Approximate Impedance Values.

    • @marvin082500
      @marvin082500 Před 5 měsíci

      Thank you Sir @@RandyAmorTutorials

  • @Jepz_
    @Jepz_ Před 10 měsíci +1

    Engr
    Ano gamit mo na software sa presentation 😁.. galing..

    • @RandyAmorTutorials
      @RandyAmorTutorials Před 10 měsíci

      Smath Solver sir, may video ako kung paano mag download at gamitin
      czcams.com/play/PLfGtZkfoxIwyw55mf2kqRSNfz86rOLRuK.html

    • @Jepz_
      @Jepz_ Před 10 měsíci

      Nakita ko Engr sa suggestion.. salamaat ng marami.

  • @marclestercarlos6619
    @marclestercarlos6619 Před 7 měsíci

    Kelangan ba iconvert to "feet" yung length ng cable?

    • @RandyAmorTutorials
      @RandyAmorTutorials Před 7 měsíci

      Yes po sir kailangan i-convert sa feet kasi yun po ang nasa formula

  • @bloomberg4865
    @bloomberg4865 Před měsícem

    Bkt s pag compute mo ng isc3 hindi mo naconsider ung current contribution ng motor during fault condition. Meron dn yan contribution.

  • @rommelbondoc1121
    @rommelbondoc1121 Před 2 měsíci

    Engr anong program/app yun gamit mo na auto nagcompute after mo magtype?

    • @RandyAmorTutorials
      @RandyAmorTutorials Před 2 měsíci

      Smath Studio sir. May tutorials din ako tungkol jan
      czcams.com/play/PLfGtZkfoxIwyw55mf2kqRSNfz86rOLRuK.html

    • @rommelbondoc1121
      @rommelbondoc1121 Před 2 měsíci

      @@RandyAmorTutorials salamat

  • @Dragon26-Tiger31
    @Dragon26-Tiger31 Před 9 měsíci

    sa calculation ng M1, 100 divide by Z times 0.9, san nangaling yung 100?

  • @eap0226
    @eap0226 Před 11 měsíci +1

    Paano po kunin yong n, number of parallel rods?

    • @RandyAmorTutorials
      @RandyAmorTutorials Před 11 měsíci

      Sir sa design po yun makikita normally naka indicate sa single-line diagram

  • @pochitaiitft
    @pochitaiitft Před 6 měsíci

    Sir anong software ginagamit nyo

  • @jeffreymanalomanalo2682
    @jeffreymanalomanalo2682 Před 9 měsíci

    Sir sana po naituro mo din yun breaker na gagamitin para sa na compute na fault

    • @RandyAmorTutorials
      @RandyAmorTutorials Před 9 měsíci +1

      sir pagdating sa breaker na gagamitin base sa na calculate ng fault current, ang rule lang naman dun ay kunin mo yung breaker na may kAIC rating na equal or mas mataas sa calculated fault current.

    • @jeffreymanalomanalo2682
      @jeffreymanalomanalo2682 Před 9 měsíci

      @@RandyAmorTutorials thanks

  • @leovincalubag479
    @leovincalubag479 Před rokem

    anong C value and dapat gamitin pag Single Phase.

    • @ImmortalShiro
      @ImmortalShiro Před rokem +1

      Same lang din. Naka dipende naman po kasi yung C values mainly sa wire size, then kung magnetic or nonmagnetic yung conduit, tsaka yung voltage.

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem +1

      Walang separate value for single phase. Magkaiba lang ng value for single conductors and multi-conductor cables or kung busway

  • @ouevv
    @ouevv Před 10 měsíci +1

    Sa value ng n, paano naging 2 sa pt 1? 3phase po diba so bale 3 wires? Medyo nakakalito lang.

    • @RandyAmorTutorials
      @RandyAmorTutorials Před 10 měsíci

      Yung n dun sir is number of parallel runs, in that case, n=2

    • @jeffreymanalomanalo2682
      @jeffreymanalomanalo2682 Před 9 měsíci

      ​@@RandyAmorTutorialsKunwari po 3 na acb galing sa hvsg to lvsg. So times 3? Tama po ba

    • @RandyAmorTutorials
      @RandyAmorTutorials Před 9 měsíci

      @@jeffreymanalomanalo2682 hindi po ganun sir. Yung number of parallel runs of cable po is kung ilang set ng three-phase cables and ginamit, for example kapag nakalagy sa single-line diagram na 2 - 3Cx100mm2 ibig sabihin 2 sets ng three-phase feeder so ang n=2

    • @emmanuellimjoco4709
      @emmanuellimjoco4709 Před 21 dnem

      Kung 1 set lang n value is 1.
      Kung 3 sets ang n value is 3 di po ba?

  • @arielgallego8803
    @arielgallego8803 Před měsícem

    Sir, may video ka ba kung genset naman ang power source?

  • @dhardstv9818
    @dhardstv9818 Před rokem

    boss panu mo ginawa sa diagram?panu ininsert

  • @jeffreymanalomanalo2682
    @jeffreymanalomanalo2682 Před 9 měsíci

    Hello sir. Saan po nakuha Yun 100

  • @incoyjoshuagabriell.4184
    @incoyjoshuagabriell.4184 Před 5 měsíci

    san po nangaling yung %z=5 thanks po

    • @RandyAmorTutorials
      @RandyAmorTutorials Před 5 měsíci

      Sir yung 5% impedance po ay given sa problem, pero sa actual na calculation kukunin nyo po ang impedance sa nameplate ng transformer. Salamat po sa panonood sa video. God Bless.

  • @OP-OP999
    @OP-OP999 Před rokem +1

    Hello Sir. Blurry po ang given. Kindly provide clearer video. 🙏🙏🙏

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem +1

      Malinaw naman po yung video.

    • @OP-OP999
      @OP-OP999 Před rokem

      @@RandyAmorTutorials Hello po Sir Randy. Blurry sa cellphone ko sir. But clear sa laptop. Maraming salamat po sir.

    • @OP-OP999
      @OP-OP999 Před rokem

      @@RandyAmorTutorials Hello Sir Randy, tanong ko lng po kasi nalilitu po ako. yung impedance po ng transformer is 5%. Yung tanong ko is M1=100/(5)(0.9), since 5% po yan sir hindi po ba dapat 0.05 ang gagamitin natin Sir? magiging M1=100/(0.05)(0.9)?

    • @RandyAmorTutorials
      @RandyAmorTutorials Před rokem +1

      @@OP-OP999 kung ano po yung naka indicate na %Z ayun po yung gagamitin hindi na po gagawing decimal

    • @OP-OP999
      @OP-OP999 Před rokem

      @@RandyAmorTutorials got it po sir. Maraming salamat po at binigyan niyo po ako nang kalinawagan.