How To Install an Exit Sign by a Professional Electrician

Sdílet
Vložit
  • čas přidán 29. 08. 2024
  • An Exit Light Company Electrician demonstrates the process of installing an LED Exit Sign. In this demonstration we use the COMBOG2 (www.exitlightc...) Combination Exit Sign / Emergency Light Unit.
    Full Instructions at : www.exitlightc...
    Shop Exit Signs : www.exitlightc...
    Shop Emergency Lights : www.exitlightc...
    Installation Steps From This Video:
    1) Remove the front faceplate
    2) Pop out the mounting canopy knockouts on either the top or the side of unit
    3) Attach the mounting canopy
    4) Attach the metal grid to the mounting canopy with included screws using the configuration of the junction box
    5) Feed the input wires through the mounting canopy
    6) If the exit sign housing is metal, wire and cap the green ground wire to the corresponding ground wire in junction box (plastic housing exits will have no ground wire)
    7) Place the white common (neutral) wires together and cap them with a wire nut (included)
    8) Wire and cap either the 120V (black) or 277V (red/orange) wire with the line input wire (depending on the decided voltage)
    9) Cap off the remaining wire that was not used
    10) Fasten the mounting canopy to the junction box with the included screws leaving all installation wiring inside the junction box
    12) Connect the battery to the circuit board
    13) Reattach the front faceplate
    Background music from : www.bensound.com/

Komentáře • 94

  • @DocIlpalazzo
    @DocIlpalazzo Před 10 měsíci +4

    😬😬😬 It’s a good thing I unplugged it when I did. I plugged all the wires in to there corresponding colors and notices the transformer started getting really hot. Didn’t know it’s one or the other.
    Thanks man

  • @Thunderbolt1003
    @Thunderbolt1003 Před 5 lety +15

    I like how he made the connections inside the junction box as to not obstruct the lettering in the sign itself

    • @alvarogalindo596
      @alvarogalindo596 Před 4 lety +1

      👍

    • @18436Melissa
      @18436Melissa Před 4 lety

      To install a exit sign I think you need drywall/wood for the installation

    • @Thunderbolt1003
      @Thunderbolt1003 Před 4 lety

      Melissa Dingle it can be installed on the ceiling, it’s also required to use a junction box or conduit

    • @18436Melissa
      @18436Melissa Před 3 lety

      @@Thunderbolt1003 well at 8 pm I'm getting a exit sign with the rectangular heads.

    • @eugeniuszminkowski6486
      @eugeniuszminkowski6486 Před 3 lety

      @@alvarogalindo596
      9

  • @queencitysirens8755
    @queencitysirens8755 Před 3 lety +6

    I just laugh at all the comments from "CZcams Master Electricians" who think they know everything. Yet they wire there exit signs to extension cords lol. Great Video!

  • @b0y.slvt7
    @b0y.slvt7 Před 3 lety +14

    everyone watching this video probably being older adult men needing a sign for their office or something but then you got my teenage self here wanting it for my room😹😹 why can’t you just like stick it on the ceiling or like screw it in then it has a regular plug you could run down the wall lol, there might be but idk

    • @frenchfreys
      @frenchfreys Před 3 lety +1

      Hey same

    • @brothadre76
      @brothadre76 Před 3 lety +1

      I'm sure it can be done

    • @EternalWithin
      @EternalWithin Před 3 lety +1

      Same.

    • @ALT-9167
      @ALT-9167 Před 3 lety +2

      @@EternalWithin same i have one but my mum does not want me to screw it to the ceiling

    • @thoward575
      @thoward575 Před rokem +1

      @@ALT-9167 same i put a lithonia lhqm led combo but my dad didn’t want holes in the wall so we used weight rated 3M tape to mount it

  • @ironjohn5914
    @ironjohn5914 Před 7 měsíci +1

    I paid an electrician to install this 25.00 while I went out for a nice lunch. Your welcome

  • @jesusacosta3047
    @jesusacosta3047 Před rokem +1

    Thanks will be installing 2 this Saturday❤️

  • @Grapho137
    @Grapho137 Před 2 lety +3

    i love how you do ur work

  • @SonicIsCool5422
    @SonicIsCool5422 Před rokem +1

    I saw those green exit sign combos at my school

  • @brothadre76
    @brothadre76 Před 3 lety +1

    Cool beans.....So I don't have to wire the exit sign straight to the junction box huh? I'll get it done this weekend! Thnx!

  • @juicred1
    @juicred1 Před 6 měsíci +1

    Do you have to ground the light?

    • @ExitLightCo
      @ExitLightCo  Před 6 měsíci

      The majority of thermoplastic housing exit signs and emergency lights typically do not include a green ground wire. However, steel and aluminum housing units usually come equipped with one, and it is advisable to ground these units for safety reasons.

    • @juicred1
      @juicred1 Před 6 měsíci

      @@ExitLightCo thank you 👌🏿👌🏿

  • @jakestone6793
    @jakestone6793 Před 3 lety +2

    I installed a few 2 head LED emergency light and tested others (working in my own building) 4 of them failed to light up. So checked the battery - each were good, around 6.x volts. Pressing the test button and it just make sort of a wimpy buz noise for a second. So I just replaced the whole unit, still have the same issue - no lights - this is in about 4 wings of the building. is it possible a wiring issue or user error (LOL).
    steps taken:
    1. out of box
    2. back plate to the wall
    3. connected black/white, and snipped the red wire
    4. tucked them into the wall
    5. connected batter to itself (spade connectors)
    6. connected whole unit to wall plate
    7. red light comes on - so there is power
    8. press test button - nothing.
    Same problem with 3 others

  • @jongdave2691
    @jongdave2691 Před 4 měsíci

    Ok, should u feed the wire into the juction box or you could keep it within the emergency light? what is the logic? Thanks.

  • @erikramos9249
    @erikramos9249 Před 2 lety +2

    If the rest of the lamp is off and I have one on, what do you think is that friend?

    • @ExitLightCo
      @ExitLightCo  Před 2 lety

      That's a great question. It can actually be several things, we suggest asking your certified electrician to check if the lamps are making a proper connection to the unit. Often times, the lamp connections come lose causing a faulty lamp. They can also check the user manual for further troubleshooting steps.

    • @erikramos9249
      @erikramos9249 Před 2 lety

      @@ExitLightCo ok thank you sir

  • @TheExitSignDudeOfficial
    @TheExitSignDudeOfficial Před rokem +1

    Cool Video! I seen these exit sign combos in red!

  • @ugsisr
    @ugsisr Před 4 měsíci

    Can Emergency lighting be wired from existing ceiling lighting circuit ?

  • @18436Melissa
    @18436Melissa Před 4 lety +3

    Make sure there is a 2x4 in the drop ceiling. If there is none then the exit sign will fall.

  • @heckeroffical3862
    @heckeroffical3862 Před 2 lety +1

    Do I need a plate adapter thing for a light switch box?

  • @khato786
    @khato786 Před 10 měsíci +1

    where was the battery and circut board?

    • @ExitLightCo
      @ExitLightCo  Před 10 měsíci

      The battery for this particular combo exit sign is located inside towards the bottom of the sign; the circuit board is right above it.

  • @Sodlam
    @Sodlam Před 4 měsíci

    the side lights are on without reason may i know what could be the possibility to turn off without any emergency

    • @ExitLightCo
      @ExitLightCo  Před 4 měsíci

      The side lights are typically on when the exit sign is in emergency mode; meaning that the unit is being operated by the battery. If the lights do not shut off within 90-180 minutes you might have a faulty unit. We suggest contacting a licensed electrician to further troubleshoot the exit sign.

  • @UnwrappingByMimiKoteng
    @UnwrappingByMimiKoteng Před 2 lety +2

    Amazing

  • @dalestringer7038
    @dalestringer7038 Před 2 lety +1

    i cant find a breaker to turn the power to my emergency lights off. would it be tied in to the fire alarm system

    • @ExitLightCo
      @ExitLightCo  Před rokem

      Typically they are not tied into alarm systems but there are a few that do. Sometimes there isn't a 'dedicated circuit' specifically run for emergency lighting and they're tied into other lighting circuits.

  • @Breakingfree577
    @Breakingfree577 Před rokem +1

    I'm new to this stuff. I see a power wire and neutral is their no need for a ground wire?

    • @ExitLightCo
      @ExitLightCo  Před rokem

      Excellent question! Since the sign is constructed of a non-conductive thermoplastic, there is no need for a ground wire. We do sell steel and aluminum units which do have that extra ground wire.

  • @mtfguy8336
    @mtfguy8336 Před 2 lety +1

    l like exit signs

  • @dieueeheheh2385
    @dieueeheheh2385 Před 2 lety +2

    Tysm

  • @mrexitsign2024
    @mrexitsign2024 Před 2 lety +1

    I have that kind of exit sign

  • @julianklich3371
    @julianklich3371 Před 11 měsíci

    Is that octagonal box properly supported tho?

  • @18436Melissa
    @18436Melissa Před 4 lety +4

    2:23 why not just leave it like that? Lol

  • @trustinmyselfalways6310

    Where do I hook the ground wire to? Mine has a red white and green wire. I only have a black and white wire from the wall. Do I put the green wire to the black wire?

    • @laureno7757
      @laureno7757 Před rokem +1

      u don't have to connect the ground if you want just cap it you can't connect the ground wire to the black

    • @trustinmyselfalways6310
      @trustinmyselfalways6310 Před rokem +1

      @@laureno7757 thanks man.

  • @mjsobcz
    @mjsobcz Před 5 lety +1

    Hmm, this was open earlier as he removed the instruction sheet and plugged in the battery cable.
    He never mentioned checking to see that the battery needs to be hooked up before installing.
    He "assumed" people would have done this already.

    • @ExitLightCo
      @ExitLightCo  Před 5 lety +2

      Our Electrician didn't touch the battery until after the unit was wired to the buildings power. All signs are manufactured with the battery disconnected. If you attach the battery first before connecting to a stable power supply, the sign will automatically go into Battery Backup mode and start running off battery power until it's out of juice. Connect power first, battery last. Thanks for watching.

  • @IIAlphaQII
    @IIAlphaQII Před 6 měsíci +1

    What does the 120 vac mean?

    • @ExitLightCo
      @ExitLightCo  Před 6 měsíci

      "120 VAC" stands for "120 volts alternating current." It refers to the standard voltage provided by electrical outlets in many regions, particularly in North America. This voltage is the potential difference between the hot and neutral wires in the electrical system and is commonly used to power household appliances, lighting fixtures, and other electrical devices. The "AC" indicates that the current alternates direction periodically, as opposed to direct current (DC), which flows consistently in one direction.

  • @Kasey1776
    @Kasey1776 Před 5 lety +1

    Awesome

  • @localrealtor1303
    @localrealtor1303 Před 4 lety

    Hi, we installed several of these but the lights don't come on when pushing the test button. I dont see any cables not connect. Any ideas ?

    • @ed6852
      @ed6852 Před 4 lety

      You probably need a Nicad battery there should be a connection on the LED board

    • @localrealtor1303
      @localrealtor1303 Před 4 lety +1

      erik dopp
      Hi
      Found it. There is a cable to connect. Nothing in instructions and you can see the cable dangling. We had to pull off the plate on the other side and now working.
      :)
      Appreciate it.

    • @ed6852
      @ed6852 Před 4 lety

      No problem i did these for the first time yesterday lol

    • @18436Melissa
      @18436Melissa Před 4 lety +2

      @@ed6852 my combo2 exit sign works properly. Test mode works.

  • @angelsrailfanandmore
    @angelsrailfanandmore Před 5 lety

    Your exit sign combo is self diagnostics

  • @kabirubrown8112
    @kabirubrown8112 Před 5 lety +1

    Does anybody know how much it may cost to replace the red covering

    • @ExitLightCo
      @ExitLightCo  Před 5 lety

      Are you talking about the diffuser, which is the red or green sheet inside the exit sign? Or are you talking about the faceplate, where the "EXIT" lettering is? If you ordered your Exit Sign from us, contact our Customer Service, as we may be able to get you a replacement part.

    • @kabirubrown8112
      @kabirubrown8112 Před 5 lety

      The Exit Light Company the diffuser

  • @Codylun92
    @Codylun92 Před 3 lety

    Do you know why a light would start drawing small amounts power from a battery but still have AC power going to it?

  • @sperez6140
    @sperez6140 Před 5 lety +1

    What is the red wire u cut

    • @ExitLightCo
      @ExitLightCo  Před 5 lety +1

      The red wire is for installations using 277 Volt. Our Electrician determined he was going to be installing on 120 Volt. Whichever wire you don't use, you cap off and tuck away. Thanks for your question.

    • @psyo123
      @psyo123 Před 5 lety

      the first job I did in my present company was installing combo exit sign with living 277v. it was tough but priceless experience.

    • @nl5607
      @nl5607 Před 4 lety

      I have one ive been wanting to mount for years but I’d have to take bedroom light out to do so lol I want it up bad there is yellow and blue wire inside but was different from irs it looks

    • @samdag9755
      @samdag9755 Před 4 lety

      What wire color should I use if I have a 220V suppy?

    • @18436Melissa
      @18436Melissa Před 4 lety

      @@samdag9755 red and white.

  • @alvarogalindo596
    @alvarogalindo596 Před 4 lety +1

    Yes.

  • @yessicastro7236
    @yessicastro7236 Před 4 lety

    Makita 😍

  • @ckeilah
    @ckeilah Před 4 lety

    “Always turn the power off first!” Yeah, right- do as I say, not as I do! ;-)

  • @mtfguy8336
    @mtfguy8336 Před 2 lety +1

    i am a smart electrican

  • @raqman915
    @raqman915 Před 3 lety

    I'm stealing one in 2 hours and 15 minutes wish me luck

  • @18436Melissa
    @18436Melissa Před 4 lety

    im getting another exit sign from a place called home depot

    • @PeliculasOnline2017
      @PeliculasOnline2017 Před 4 lety +1

      Many thanks, I been tryin to find out about "emergency exit light batteries" for a while now, and I think this has helped. You ever tried - Eenseh Unthinkable Expediency - (do a google search )?
      It is a smashing one off product for discovering how to get emergency light without relying on batteries minus the normal expense. Ive heard some super things about it and my work buddy got cool results with it.✅

    • @18436Melissa
      @18436Melissa Před 4 lety

      @@PeliculasOnline2017 well I replaced my sign with a AKT Exit Sign emergency lighting

    • @18436Melissa
      @18436Melissa Před 4 lety

      @@PeliculasOnline2017 you should get the exit signs with the square emergency light

  • @numb7556
    @numb7556 Před 2 lety +1

    >:( Installing exit signs

  • @kanyewest6539
    @kanyewest6539 Před 4 lety

    fucking god damn plastic clips on these things are made out of powder and glue. mine broke and now im here looking for ways to jerry rig them back.

  • @sabahhasan4228
    @sabahhasan4228 Před 4 lety

    Excuse me, are the wires inside the junction box connected directly to the final distribution board? so it has its separate circuit breaker or they are connected to a lighting circuit. explain please by a single line diagram if possible. Thanks in advance.

    • @menopassini9348
      @menopassini9348 Před 4 lety

      Usually city building dept.s Want all. Emergency/Exit light on their own Circuit with a lock on the breaker. Just like the Ffire alarm. At least that is what they do here. For small remodeled the i inspectors aren't this particular.