How to wire a type 2 surge arrester into a distribution board - factors to consider - South Africa

Sdílet
Vložit
  • čas přidán 30. 10. 2021
  • How to install a type 2 surge arrester into a distribution board.
    Further details found in the SANS 10142-1:2020 wiring standard - The Wiring of Premises Part1: low voltage installations.

Komentáře • 38

  • @user-yv6vx2fd5r
    @user-yv6vx2fd5r Před 9 měsíci +4

    very good explanation but we need more

  • @yaseenbenjamin5197
    @yaseenbenjamin5197 Před rokem

    Thank you for your detailed explanation. Very useful

  • @iLink_LTD
    @iLink_LTD Před 4 měsíci

    Very helpful and detailed explanation, thank you!

  • @louismathews6831
    @louismathews6831 Před rokem +2

    Awesome Video, thank you

  • @dulajohnstone5704
    @dulajohnstone5704 Před rokem +4

    Good Day to you Sir. I'm back again after 8 months lol. Thank you for the simple yet very clear explanations. Could you please do a 3 phase surge arrestor installation using the same method as you've shown in the single phase method thank you so much for your valuable time.

  • @SnowyPe
    @SnowyPe Před 2 lety

    Good info..thanks

  • @andrew39454
    @andrew39454 Před rokem +4

    I think u get the wrong point about SPD need over current protection device (MCB or fuse). It is to isolate the SPD from the DB system if SPD fail, fault or damage. So you need an extract MCB or fuse as over current protection to connect between the Main MCB and the SPD, not directly connect the SPD to the main 63A MCB.
    Actually in current situation over current fuse disconnector is prefer than MCB, because you don't want the MCB in between SPD and Main MCB trip during lightning strike , you want the SPD to arrest the lightning to channel it to the ground, so fuse disconnector is prefer, that is why among all the SPD catalogue they normally emphasis fuse disconnector before SPD, not an MCB.

  • @mlondenimakhaye8634
    @mlondenimakhaye8634 Před rokem

    Very useful 👌

  • @ebrahimseedat5554
    @ebrahimseedat5554 Před 2 lety

    Sir thank you so so much for your videos!
    Need to ask: If the light on my surge arrester is not completely off but is slightly faded when comparing to my other (same) surge arrestors.... Is it still okay to use or should I replace it?

  • @education9135
    @education9135 Před 19 dny

    And I've seen that some or most SPD they don't specify the current, say for example I want to use 63 amps how will I know that it is 63 amps. And also how long can a SPD run before damaged.

  • @sanelengcobo404
    @sanelengcobo404 Před 3 měsíci

    Awesome ❤

  • @mahlekojoni
    @mahlekojoni Před 8 měsíci

    THANK YOU SIR
    🤓

  • @education9135
    @education9135 Před 19 dny

    Some double poles SPD they connect live and neutral on incoming power then earth on neutral side of outgoing power. Some they put live on both incoming power then earth on outgoing power, what's the difference. And also comparing it with single pole SPD.

  • @user-se2pb5yx5p
    @user-se2pb5yx5p Před 2 měsíci

    Will single pole spd on load be enough? Or is it better to use 2 pole on both load and neutral?

  • @dulajohnstone5704
    @dulajohnstone5704 Před 2 lety

    Does the Surge arrestor on the Main DB also cover the sub DB feeding from the Main DB?

  • @flinfaraday1821
    @flinfaraday1821 Před rokem

    If this is a sub-db, and the main db already has overcurrent protection, do I still need to to include an overcurrent protective breaker in this db before the surge arrester?

  • @princekhumalo7737
    @princekhumalo7737 Před rokem

    Hi Anthony. I would love to learn the solar installation, especially the connection to the db box. Do you know any course i can attend or on the job learning program?

  • @royalarmy1837
    @royalarmy1837 Před rokem

    Good day Sir. What size of Earth cable is suited for a 600vDC SPD 20kA?

  • @markvanner1110
    @markvanner1110 Před 5 měsíci

    Hi sorry to be negative but is that board wired compleaty backwards. Eg should the main isolator not be on the right and rccd next to it with bus bars feeding the bottom of the mcb s. Like wise the out going cuicuits coming out of the top of the mcb s not the bottom. Look s like a very over complicated solution for a standard instalation to me.

  • @JAG_UAR
    @JAG_UAR Před 2 lety +1

    type1+type2 uc 275v or type1+type2 uc 330v , sir which spd is better, for homes?

  • @tonybrock5288
    @tonybrock5288 Před rokem +1

    I'm a DIY'er and have always had a preference for building a DB Board from left to right as you show. It's like reading 😀. However I see in some standards that Neutral should always (understandably) be on the "outside". So, a Main Switch with "L" and then "N" on the right, should always be mounted on the right of the DB board. What is the ruling in SA?

  • @ngocehgayabebas2118
    @ngocehgayabebas2118 Před 2 lety +1

    Does it protect tv from internal surge, like start-off surge motor dynamo or refrigerator?

  • @ashwinshadygold6277
    @ashwinshadygold6277 Před 2 lety

    Can you do down lights or outside Piller lights

  • @itsalive7309
    @itsalive7309 Před rokem +1

    This is probable a stupid question but anyway....
    I have a CBI Type 2 Surge arrestor QFL-N-2(13). The diagram printed on the device shows N wired on the top left terminal and L wired on the top right terminal , with Earth bridged across the bottom terminals. However, the electrician has wired it so that Live (Red) is connect to the top left terminal (N in the diagram) and Neutral (black) is connected to top right connector (L in the diagram). According to the diagram, this the wrong way around. My suspicion is confirmed by the fact that the surge arrestor light is off. Am I correct and if the diagram says N is left, then N should be connected on the left? Or doesn't it matter and I need to go back to Reading 101?

    • @sajidmohammad3190
      @sajidmohammad3190 Před měsícem

      L or N doesn't matter if it has two separate identical blocks. If it is a 1P spd, then L & N will matter.

  • @srinivasanragavan5737

    Where the surge attestor available

  • @namzy410
    @namzy410 Před rokem

    16mm2 cable?

  • @bosuglosalifulongi6406

    The bent busbar is not insulated. Is it okay to leave it as it is?

  • @kza691
    @kza691 Před 2 lety +2

    Are these one time use or can they be reset?

    • @flinfaraday1821
      @flinfaraday1821 Před rokem +2

      They work until the flag/indicator shows red/replace, then you throw it away and install a new one.

  • @Alec_Aldawg
    @Alec_Aldawg Před rokem +1

    Why does it need an over current protector if it’s not drawing current?

  • @Charles.parker
    @Charles.parker Před 10 měsíci

    Can we connect output of type 2 spd to neutral instead of earth?