How to control Multiple Motors with One VFD ?

Sdílet
Vložit
  • čas přidán 20. 07. 2024
  • #vfd #plc #motor #automation
    How to control Multiple Motors with One VFD ?
    -------------------------------------------------------------------------------------------------
    Links for the Multimeter from BSIDE are following
    BSIDE Z1 products belong to the latest generation of BSIDE brand smart voltage detector tester!
    aliexpress.com/item/100500429...
    BSIDE Z5 products belong to the latest generation of BSIDE brand smart Pen-shaped multimeter!
    aliexpress.com/item/100500402...
    ---------------------------------------------------------------------------------------------------
    00:00 Introduction to VFD
    00:38 Sponsors AD
    01:48 How to control Multiple Motors with One VFD ?
    02:40 things to consider while connecting Multiple Motors with One VFD.
    ---------------------------------------------------------------------------------------------------
    Please Subscribe to PLC Tutorials for more Videos and Tutorials.
    how to run multiple motors with a single vfd as you might know that a vfd is used to control a motor by controlling means that vfd can run a motor control its speed it can even control the motor torque and can run the motor in reverse and forward direction now the question is that if we can run the two or more motors with a single vfd the answer is yes yes you can connect multiple motors with a vfd this video tutorial is all about this interesting topic before going further into today's topic let's see the message from the sponsor of the today's video tutorial most of the commonly used multimeters are designed in such a way that there are two props connected to a multimeter with this type of design it's sometime really hard to handle and use these multimeters in the field this problem is solved by converting one of the probe into the meter really easy to operate and monitor from the lcd on the positive prop one of the really cool features of this multimeter is the flashlight which is right in front of the red probe now it is really easy to use these multimeters in the dark areas of the electrical panel its red probe can also work as a line tester its other features include contactless voltage sensing ac and dc voltage measurement frequency or hertz measurement continuity and diode test furthermore it has a temperature sensor to check the ambient temperature i have used and tested this new innovative design to buy this multimeter the link is in the description box coming back to the today's topic in this video we will discuss pros and cons of connecting multiple motors with a vfd let's see an example where we'll be connecting three motors with a single vfd we will simply connect the three wires at u v and w terminals of the vfd next we will connect these wires at the input terminals of the first mcb from there the output wire is distributed to the other two breakers each of these mcb will be supplying the power to the individual motor now the three motors are connected to the vfd via mcb breakers these mcbs are really important any of these motor is overloaded its mcb will chip and it will save the vfd and keep the other motors running and in operation it is great to run the multiple motors with the vfd but there are some points which we have to consider seriously and think about before designing such a system the first thing is the output frequency as we are running a system on a single vfd we cannot control the rpm of the individual motor all motors will be running at same frequency and at same rpm if your system doesn't require to change the speed of individual motor you can use this technique second point is the cable length between the vfd and the motor usually the recommended cable length between the vfd and the motor is 500 meters so this means that if we are wiring the three motors the sum of these three cables should be less than the 500 meters the next point is the total power of the motors connected to the vfd the sum of all motors must be less than the vfd output power usually the total load power will be kept 20 percent less than the vfd output power the next point is the vf mode of the vfd we should select vf run mode from the vfd parameters pf mode is designed to run the multiple motors on the single vfd the next point is safety related don't turn on or off the mcbs for the motors when the vfd is running this action can create imbalance in the output current of the vfd and can damage the igbt modules of the vfd the next really critical point is that if any of these motor is short circuit it can damage the vfd because of the sudden and sharp rise in the output current so for this type of application always use the good vfd which have a short circuit protection in it so this is how you can connect multiple motors with a single vfd and in this session we have discussed all the pros and cons i hope you liked today's session please share like and subscribe this channel till next time take care good bye

Komentáře • 35

  • @cheyguvera9680
    @cheyguvera9680 Před rokem

    My favourite channel for automation, thank you so much

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  Před rokem +1

      thank you for the appreciation of my hard work

    • @cheyguvera9680
      @cheyguvera9680 Před rokem

      @@EASYPLCTRAINING i have one doubt brother, all motors rpm should be same ? I mean synchronous speed which is on motor name plate

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  Před rokem +1

      Same kw and same rpm, its better for safe operation. All three motors should be identical to keep the current balanced.

  • @AhmedAli-rz8sf
    @AhmedAli-rz8sf Před rokem

    Thank you so much it's so clear

  • @linossinkala7840
    @linossinkala7840 Před rokem

    Thankyou sir ,i appreciate your vidoes

  • @krzysztofkapcia4521
    @krzysztofkapcia4521 Před rokem +1

    Your animations are incredibly useful in my job. Thank you very much for your effort in creating them.
    Can I ask what software do you use to create these presentations?

  • @datsim_labelle1762
    @datsim_labelle1762 Před rokem

    Hello, nice video and explanation!
    I have a 2post car lift with 2 motors on it (one each side). Both use the same RPM and specs and are already connected together. My question is, using one VFD with the correct spec for example, both motor together are 5.5KW if I use one VFD with an output of 7,5KW that will be enough and safe for operating it ? Those motor are 220V 3PH and my shop only have single phase 220V. With the VFD I’ll be able to convert single to 3phases and make both motor turning without any problem ??
    Thank you for your help
    Simon

  • @AnasAl-Dhafiri
    @AnasAl-Dhafiri Před rokem

    Thank you very much sir

  • @theniii
    @theniii Před 4 měsíci

    that "goodbye" at the end tho.

  • @lawalrafiu151
    @lawalrafiu151 Před rokem

    Thank you for this session.
    I would like to ask if there is a way we can connect a VFD to a single phase motor.
    If anything of such is possible?

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  Před rokem +2

      No dear , for single phase motor you can use speed control cards , these are basically voltage regulators

    • @lawalrafiu151
      @lawalrafiu151 Před rokem

      @@EASYPLCTRAINING thank you so much. I appreciate it.

  • @burhanahmad9095
    @burhanahmad9095 Před 3 měsíci

    Hello sir..im going to connect VSD to 30 induction motors 3kw..can you give an advice ??thank you very much

  • @oll4820
    @oll4820 Před 11 měsíci

    Is there a way to control multiple motors with just 1 VFD without running them simultaneously? I want one motor to run at a time then set the others as backup.

  • @kouassirobertkodo6754

    Thanks a lot.
    What the setting of the current?

  • @roshan2940
    @roshan2940 Před rokem

    Sir, Which software you used to create such type of videos and animation

  • @prakashelectricals5581

    I have used two motors in single vfd, without using any MPCB
    MEAS direct wiring
    What can be problem comes in future?

  • @agent70vids3
    @agent70vids3 Před rokem

    I have a problem in my altivar38 VFD, before its running two motors at the same time, when we replace the card of vfd, it cannot run the two motors at the same time, you need to run one motor, once it reaches the setpoint speed,that is the time you will run the another motor. What is missing?

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  Před rokem

      You replace the control card of the vfd or power card ?

    • @agent70vids3
      @agent70vids3 Před rokem

      @@EASYPLCTRAINING i replace the whole vfd now, It's the same model. I need to run the first motor, once it reaches the set point speed, i can run the another motor. Before they are starting and running at the same time. What is missing?

    • @oll4820
      @oll4820 Před 11 měsíci

      @@agent70vids3 How did you do that? I needed that setup where one motor only runs at a time, then set the others as back up.

  • @goowatch
    @goowatch Před rokem

    What happens if one or more of the MBPCs are automatically activated for protection?

  • @alibakhshayeshi1839
    @alibakhshayeshi1839 Před rokem

    ❤❤❤

  • @rezabahmaninia2571
    @rezabahmaninia2571 Před rokem

    Hello.what software desian vdiuo????

  • @PankajSingh-xs1mw
    @PankajSingh-xs1mw Před 7 měsíci

    एक भी डी एफ से तीन मोटर चलाना सीखे साथ हीं जाने कितने एम्पियर का लेना होगा

  • @kiranchoudhari4717
    @kiranchoudhari4717 Před rokem

    Please mention your insta Id