Split Range Control

Sdílet
Vložit
  • čas přidán 5. 09. 2024

Komentáře • 7

  • @elmurodermatov8518
    @elmurodermatov8518 Před 2 lety +1

    Thank you so much mr, it helps me great 🖐🖐✊

  • @MM-vi9kh
    @MM-vi9kh Před 4 lety

    "In split range control and valve A open till 50%, valve B open from 50% - 100% How much valve B is open if the controller output is 57%? Is there any method or equation to calculate it?"

    • @schoolofengineering1017
      @schoolofengineering1017  Před 4 lety +2

      %opening valve B = (controller output - 50%) x 2

    • @schoolofengineering1017
      @schoolofengineering1017  Před 4 lety +3

      Thus if controller output is 57%, %opening valve B = (57% - 50%) x 2 = 14%

    • @MM-vi9kh
      @MM-vi9kh Před 4 lety +1

      @@schoolofengineering1017 thanks ❤️

    • @allinonechannel8717
      @allinonechannel8717 Před 3 lety

      @@schoolofengineering1017 so valve A will be always fully open when Controller output more than 50% and valve B will be open 14% as per your calculations
      So if controller output will be 20% then Valve A is 40% open and Valve B will be in 0% Am I right?