Replacing or Installing a VAV Box

Sdílet
Vložit
  • čas přidán 7. 09. 2024
  • Description

Komentáře • 33

  • @mrlara57
    @mrlara57 Před 7 lety +1

    Ken. I seen your video with Blair from west ( water treatment ) I know Blair, since I checked all your videos .. Great info , love me...

  • @hueman7
    @hueman7 Před 9 lety

    thanks much for the video , i am currently moving in to the mechanical field from the commercial refrigeration field , this is great precursor well done .

    • @StupidPeasant
      @StupidPeasant Před 9 lety +1

      I also moved from refrigeration, 2 years ago. Building air is a lot cleaner than nasty old supermarkets. Still a lot to learn for me.

    • @hueman7
      @hueman7 Před 9 lety

      Man..... without question

  • @tinysand3517
    @tinysand3517 Před 6 lety +1

    great job Ken, thank you. I learned a lot from yur videos

  • @Losangeles1980
    @Losangeles1980 Před 8 lety +1

    thank you Ken for the videos.

  • @user-rn5ip9ec6j
    @user-rn5ip9ec6j Před 4 lety +1

    Super! Good video!

  • @justinfarquhar8299
    @justinfarquhar8299 Před 7 lety +1

    thanks ken! you are the man

  • @jersung4174
    @jersung4174 Před 6 lety

    Thank you so much for your videos.

  • @itsm3_chrissi3
    @itsm3_chrissi3 Před 4 lety +1

    excellent!

  • @Nichlo88
    @Nichlo88 Před 6 lety

    such a great video ken your the man thanks

  • @jamillesunga441
    @jamillesunga441 Před 6 lety

    You are the best Mr. Ken

  • @uclabh5530
    @uclabh5530 Před 10 lety +3

    Hi Ken, I really enjoy watching your training video. My question to you is how do you trouble shoot the VAV controller? Thanks

  • @jersung4174
    @jersung4174 Před 6 lety +1

    Oh Sorry, I think my question was addressed on the last part of your video regarding changing the sensitivity to compensate for a higher Hot Water Actuator spring range of 10-15psi. I also noticed that you said you calibrated the thermostat at set point of 5.5 psi, why not at 7.5 psi which is the mid point of the Damper Actuator 5-10 psi spring range.Thanks and Regards.

  • @scottc6012
    @scottc6012 Před 4 lety

    If you could do a video with that gauge you mentioned and a bid on reverse tstat, that would be awesome

  • @gracexie4002
    @gracexie4002 Před 4 lety

    Enjoy watching this video. I have a 10 ton AC with 7 VAV box, one room is very hot. The AC company said it was at maxium CFM for the current VAV box. Do I need to change a large VAV box or I can add a fan to cool down the room?

    • @KenTraining
      @KenTraining  Před 4 lety

      I would price out all my options. if you added the fan to increase air flow, we would need to know a few items of data. 1. how much is the current set up doing in CFM and Velocity FPM, then see if there is a fan solution to increase that.
      2. price out a 10" box and a 12" box. Do CFM calculations for all situations. the rule of thumb is 400 SQFT / ton.
      Let us now what direction you go in.
      Thanks

  • @leonelramirez3231
    @leonelramirez3231 Před 5 lety

    Your the man

  • @jersung4174
    @jersung4174 Před 6 lety

    The calibration of the TITUS Controller is based on the summer time where the medium is cold air. Are there any changes in calibration during winter season where you need hot air ?

  • @thomastrang4815
    @thomastrang4815 Před 3 lety

    Are the AHU and VAVs working together in conjunction based on the BAS sequencing?

    • @KenTraining
      @KenTraining  Před 3 lety

      in this case no. My situation was pneumatic. the system you are discribing is DDC.

  • @hvac01453
    @hvac01453 Před 7 lety

    did you notice the screw that was protruding and interfering with the blade swing?

  • @lancerudy9934
    @lancerudy9934 Před 5 lety +1

    Csc3011 have video . Thanks

    • @KenTraining
      @KenTraining  Před 5 lety

      try this one czcams.com/video/9EeDqT1ti18/video.html

  • @cruzrobledo6631
    @cruzrobledo6631 Před 2 lety

    What about the diagram that comes stamp on vav box

    • @KenTraining
      @KenTraining  Před 2 lety +1

      nothing I could do but to block it. I could have taken a picture with my phone and printed it and put it on the box. Yes that diagram is helpful to figure out CFM and air flow.

  • @lancerudy9934
    @lancerudy9934 Před 5 lety

    Please have more videos on pu

  • @keepthinking2666
    @keepthinking2666 Před 9 lety +1

    why didnt you just repair the shaft we do it all the time, all you do is take a drill bit drill out the pop rivet pull broken out push the rest in mark it drill it put new pop rivet and commercial vav should be set for 10% bypass so you dont pull your ducts if you have a main unit not on a vfd supply some states 5%

  • @lancerudy9934
    @lancerudy9934 Před 5 lety

    Have a video on air controller.thanks

    • @KenTraining
      @KenTraining  Před 5 lety

      try this one czcams.com/video/9EeDqT1ti18/video.html