Basic Charger Troubleshooting
After this month's webinar you'll:
• Understand what a charger/rectifier is (Quick Overview) - for more in depth details visit our CZcams channel and watch czcams.com/video/RBj7QhiG0oM/video.html
• Understand DC Chargers/Rectifiers
• Know how to check input problems
• Know how to check transformer issues
• Know how to check SCR issues
• Know how to check control board issues
• Know how to check filter circuit issues
AMETEK Solidstate Controls: www.solidstatecontrolsinc.com
Facebook: ameteksolidstatecontrols
Instagram: ameteksci
LinkedIn: www.linkedin.com/company/solidstate-controls-inc
Twitter: AmetekSCI
zhlédnutí: 78

Video

Battery Basics and More Battery Myths
zhlédnutí 179Před měsícem
This month's learning objectives are: • Understand the basics of lead acid batteries • Understand the purpose of a battery in a back-up power system • Battery sizing • Discuss common maintenance mistakes • Discuss some common myths about batteries AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Facebook: ameteksolidstatecontrols Instagram: ameteksci LinkedI...
What's Inside an Industrial UPS System?
zhlédnutí 308Před 2 měsíci
In this month's webinar we will discuss the following components that make up a UPS system: -Input transformer -Charger -Inverter -Static Switch AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Facebook: ameteksolidstatecontrols Instagram: ameteksci LinkedIn: www.linkedin.com/company/solidstate-controls-inc Twitter: AmetekSCI
Ascend High Frequency Charger Introduction
zhlédnutí 102Před 3 měsíci
Introducing the Ascend High Frequency Battery Charger, a set it and forget it modular battery charger. Watch this short video to learn how you can elevate your charging with the efficient and easy-to-use single and three phase Ascend charger. Want to learn more about the Ascend High Frequency Charger? Visit our website, www.solidstatecontrolsinc.com/products/battery-chargers/ascend-high-frequen...
Why We Need Uninterruptible Power Supply (UPS) Systems and How to Use Them
zhlédnutí 381Před 4 měsíci
This month's webinar objectives: ✔️Understanding the importance of UPS systems ✔️Learn the difference between a UPS and a generator ✔️Understanding how a UPS works AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Facebook: ameteksolidstatecontrols Instagram: ameteksci LinkedIn: www.linkedin.com/company/solidstate-controls-inc Twitter: AmetekSCI
IGBT Inverter Designs Used by AMETEK Solidstate Controls
zhlédnutí 219Před 5 měsíci
What's in store for this month's webinar: ✔️Understanding basic inverter design ✔️Understanding the two Solidstate Controls designs of inverter bridge ✔️Discuss the components used ✔️Discuss De-Saturation ✔️Explanation of the benefits of each design AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Facebook: ameteksolidstatecontrols Instagram: ameteksci Linke...
An Introduction to the NEW 3 Phase Modular Ascend Charger
zhlédnutí 131Před 6 měsíci
After this month's webinar you will have a(n): ✔️Full overview of both the single and three phase Ascend ✔️Understanding of what makes Ascend efficient and reliable ✔️Understanding of how modular charging works ✔️Understanding of the benefits of our Animated LCD Touch Screen Display AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Facebook: ameteksolidstatecontrols Instagr...
Answering Your Previously Asked UPS Questions
zhlédnutí 148Před 7 měsíci
Our Senior Technical Manager will be walking you through how to properly set up a UPS system while answering your questions. AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Facebook: ameteksolidstatecontrols Instagram: ameteksci LinkedIn: www.linkedin.com/company/solidstate-controls-inc Twitter: AmetekSCI
Understanding UPS Semi-conductors
zhlédnutí 278Před 9 měsíci
From this month's webinar, you will be able to: • Understand the most common semi-conductors used in industrial UPS systems • Understand how each semi-conductor works • Discuss power flow and general operation of each semi-conductor • Discuss the advantages and disadvantages of different semi-conductors AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Facebook: ameteksolid...
How AMETEK Solidstate Controls' RMBS Helps You Isolate Your UPS Systems
zhlédnutí 159Před 10 měsíci
AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Facebook: ameteksolidstatecontrols Instagram: ameteksci LinkedIn: www.linkedin.com/company/solidstate-controls-inc Twitter: AmetekSCI
DC Rectifier/Charger Design Explained
zhlédnutí 354Před 10 měsíci
After this month's webinar, you will: -Understand the most common DC systems -Understand what a DC system is designed for -Know the advantages and disadvantages of different designs -Know the power flow and general operation of each design -Be aware of common misconceptions AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Facebook: ameteksolidstatecontrols Instagram: insta...
Understanding DC Ground Faults
zhlédnutí 1,7KPřed 11 měsíci
After viewing this month's webinar you will: -Know what a DC ground fault is -Know how to detect a DC ground fault -Be able to find the faulty circuit -Understand the common misconceptions around DC ground faults AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Facebook: ameteksolidstatecontrols Instagram: ameteksci LinkedIn: www.linkedin.com/company/solidst...
Ascend High Frequency Charger Instructional Video
zhlédnutí 339Před rokem
AMETEK Solidstate Controls is proud to announce the launch of the Ascend High Frequency Charger - the modular solution for your DC power needs. This video will give you an overview of the intuitive operation of the system. AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Ascend High Frequency Charger Product Webpage: www.solidstatecontrolsinc.com/products/battery-chargers/ascend-high-f...
Basic Charger/Rectifier Troubleshooting
zhlédnutí 693Před rokem
After viewing this month's webinar you will be able to: - Understand what a rectifier/charger is - Understand input problems - Check transformer and filter circuit issues - Check SCR and Control board issues AMETEK Solidstate Controls: www.solidstatecontrolsinc.com Facebook: ameteksolidstatecontrols Instagram: ameteksci LinkedIn: www.linkedin.com/company/solidstate-c...
Introduction to the New Modular Ascend High Frequency Charger!
zhlédnutí 231Před rokem
Introduction to the New Modular Ascend High Frequency Charger!
Common UPS Questions from Our Technical Webinar Surveys
zhlédnutí 413Před rokem
Common UPS Questions from Our Technical Webinar Surveys
Understanding Recommended Maintenance of Your AMETEK Solidstate Controls UPS Systems
zhlédnutí 594Před rokem
Understanding Recommended Maintenance of Your AMETEK Solidstate Controls UPS Systems
Testing VRLA Batteries and More
zhlédnutí 1,7KPřed rokem
Testing VRLA Batteries and More
Understanding UPS Systems and Common Misconceptions
zhlédnutí 940Před rokem
Understanding UPS Systems and Common Misconceptions
Analyzing and Understanding Schematic Drawings
zhlédnutí 640Před rokem
Analyzing and Understanding Schematic Drawings
Understanding Battery Basics and Battery Myths
zhlédnutí 1,2KPřed rokem
Understanding Battery Basics and Battery Myths
Introduction to the New DCR Animated Display Screen
zhlédnutí 293Před rokem
Introduction to the New DCR Animated Display Screen
Animated LCD Touch Screen Display Demonstration
zhlédnutí 410Před 2 lety
Animated LCD Touch Screen Display Demonstration
Understanding Semi-Conductors in UPS Systems
zhlédnutí 328Před 2 lety
Understanding Semi-Conductors in UPS Systems
Understanding DC Ground Faults
zhlédnutí 10KPřed 2 lety
Understanding DC Ground Faults
Understanding DC Chargers/Rectifiers
zhlédnutí 1,3KPřed 2 lety
Understanding DC Chargers/Rectifiers
Understanding How Inverters Work
zhlédnutí 970Před 2 lety
Understanding How Inverters Work
Understanding Maintenance for UPS Systems Webinar
zhlédnutí 2,2KPřed 2 lety
Understanding Maintenance for UPS Systems Webinar
UPS FAQ with Our Experts
zhlédnutí 560Před 2 lety
UPS FAQ with Our Experts
Understanding Uninterruptible Power Supply Systems
zhlédnutí 2,1KPřed 2 lety
Understanding Uninterruptible Power Supply Systems

Komentáře

  • @anisslekkal2981
    @anisslekkal2981 Před měsícem

    Gutor FSE, i am sending you my greatest respect Thx a lot for the efforts

  • @anonymousanonymous5327
    @anonymousanonymous5327 Před 2 měsíci

    seinor?

  • @michellecleveland7936
    @michellecleveland7936 Před 3 měsíci

    Great video, really explains the product well!

  • @AH-ib2co
    @AH-ib2co Před 6 měsíci

    great job

  • @zzz-nu2re
    @zzz-nu2re Před 9 měsíci

    18:12 the mechanical equivalent would be a stop check valve (normally closed solenoid/pneumatic control would be most similar to scr). Love ur videos btw, helps me learn and actually helped me during my interview for ups'. Used to work in a nuclear power plant

  • @swapnasumanpati6520
    @swapnasumanpati6520 Před 9 měsíci

    Very informative

  • @weir-doe3205
    @weir-doe3205 Před 10 měsíci

    Hi, for CB1 & 52C of a commercial UPS(9:37) , does it detect DC current or voltage propagating into the AC mains?

  • @cs72727
    @cs72727 Před 10 měsíci

    how do I make a printout of your slides? it is very informative. I am a UPS engineer. thanks,

  • @cs72727
    @cs72727 Před 10 měsíci

    great information. what is your e-mail for Mr. Craig Williams?

  • @abuelobarimene9712
    @abuelobarimene9712 Před 11 měsíci

    how can I test a ups system after design before construction

    • @ameteksolidstatecontrols4657
      @ameteksolidstatecontrols4657 Před 11 měsíci

      Hi, please email us at sci.marketing@ametek.com and we will get your question passed along to our technical manager.

  • @eepower
    @eepower Před rokem

    Thank you for sharing your experience. Great work.

  • @markswamy5364
    @markswamy5364 Před rokem

    Where are your products manufactured?

  • @JBafable
    @JBafable Před rokem

    If thier is a problem to an any outlet from UPS ,how can I reset the UPS ?

  • @rondickinson1907
    @rondickinson1907 Před rokem

    So are the ground fault detectors typically wired to the load side of the DC breakers? If not then opening the breaker would disconnect the fault detection and there would beno balance anymore.

  • @azeddineabdoune6394

    good work,thanks!

  • @azeddineabdoune6394

    good work,thanks!

  • @azeddineabdoune6394

    good work,thanks!

  • @janakapriyadarshana5835

    Nice video, can I get your email pls?

  • @AMMOHL
    @AMMOHL Před rokem

    awesome training

  • @azeddineabdoune6394

    thank you,sir,good work.

  • @azeddineabdoune6394

    good work!

  • @sadaqatali9166
    @sadaqatali9166 Před rokem

    And we have no any relay or alaram fir DC grounding in substation

  • @sadaqatali9166
    @sadaqatali9166 Před rokem

    How we find out exect location in substation DC ground fault with using mullti meter....sir

  • @EletricistaEmBrasilia

    very good!!!

  • @robertspiewak1759
    @robertspiewak1759 Před rokem

    Questions: 1. How the contractual requirements between Ametek and Saft work on the project/PO level? Is Ametek Vendor providing single solution? Or Is this a JV? 2. The new lithium batteries chemistry introduce a lot of technical requirements for the batteries and interactions during operation. It seems the model of how electronics - battery is should be working and interfacing is not established yet. How Ametek assures they have all the info from Saft to implement system properly?

  • @fernandomorales2512

    Great explanation.😊 -

  • @CraigWilliamsVoiceover

    I want to correct a comment mentioned in this video. I state that nowhere in IEE450 does it mention using internal resistance as a maintenance tool. This is not true. Although it is not mentioned anywhere in the recommendations for maintenance of a vented lead acid battery it is mentioned in an annex at the end of the report. I apologize if I misled anyone.

  • @michaelf3805
    @michaelf3805 Před 2 lety

    Is the 135V that you always reference the float for a 120V single phase system?

  • @michellecleveland7936

    Great explanation of the new display!

  • @Moviesfans2157
    @Moviesfans2157 Před 2 lety

    Send me ups pdf notes

  • @levipsb..1403
    @levipsb..1403 Před 2 lety

    Esta perfecto este curso estaría vien si nos pusieran subtitulos al español además otro más de rectificadores HF Felicidades casi eh visto todos los videos de ametek gracias por compartir sus conocimientos

  • @andresariza3451
    @andresariza3451 Před 2 lety

    Dear AMETEK, Do you have any kind of UPS suitable for connect variable frecuency inverters?

  • @astroboy2123
    @astroboy2123 Před 2 lety

    This channel is gold for a electrical/electronics student like me.

  • @hardiknandaniya6880
    @hardiknandaniya6880 Před 2 lety

    👌🏻👌🏻thank you

  • @immrnoidall
    @immrnoidall Před 2 lety

    Are you still around? I started a project of an off grid power supply for my new C-PAP [sleep apnia] machine that requires pure sine wave, and a few lights , using a new pure sine wave, " APC Back-UPS Pro 1000 S BR1000MS", with larger battery for longer run time because I lose power here a lot. My older non- sine wave UPS worked for years with my old CPAP . But after hauling everything out to the shed. and try it out, I found out that this [used but new] " APC Back-UPS Pro 1000 S BR1000MS" , which is supposed to be so smart and has a nice battery monitoring and load display and calculates time load voltage and also protects from high low and surge voltagages, was a lie. its all fake. this has no clue what the battery is doing. it seems to just have some kind of timer. make you wait 16 hours to get 15 minutes of runtime no mater if your battery if full charged when you put it in or if ,like me, use a 100 amp hour battery . 16 hours, for 15 minutes. can you point me to a schematic or idea of how to disable this . none of it is really needed anyway because it is all done via Bluetooth .to my phone ,from the battery. just looking for the easy ,cheap way out.

    • @ameteksolidstatecontrols4657
      @ameteksolidstatecontrols4657 Před 2 lety

      Thank you for reaching out! Please email us at sci.marketing@ametek.com and we can connect you with someone to assist you.

  • @muchamedabdelaziz7953

    amazing

  • @trvn0891
    @trvn0891 Před 2 lety

    When normal power is lost, but normal power is fed thru ATS and you get normal power back within a couple of cycles; what are the sequence of the UPS? my understanding is to batterie power and back to normal after normal is restore to UPS

    • @ameteksolidstatecontrols4657
      @ameteksolidstatecontrols4657 Před 2 lety

      Please email your questions to sci.marketing@ametek.com and we will connect you with someone to answer your questions.

    • @karbonphiber
      @karbonphiber Před 2 lety

      Yea that’s correct.

    • @craigwilliams6158
      @craigwilliams6158 Před 2 lety

      Ricardo. When you have an ATS feeding the normal power (rectifier/charger) to the UPS, when normal power is lost a standby generator will start. This generator usually takes around 30 seconds to 1 minute to start and get up to speed. After it is up to speed, the ATS will transfer power supplied to the rectifier/charger to the generator. During the 30 seconds to 1minute, there will be no power into the rectifier/charger. Therefore the battery will supply the inverter while the generator is starting. Once the generator is on and the ATS transfers, power will be returned to the charger/rectifier section of the UPS and the batteries will start to charge again. It should be noted that the ATS does not have anything to do with the load circuits. Only the input power to the rectifier charger section of the UPS.

  • @alishafi9272
    @alishafi9272 Před 2 lety

    in ferroresonant transformer type Inverter, IGBTs are switched are at constant frequency (50/60Hz). while in PWM type inverters, IGBTs are switched at varying frequency. kindly correct if i am wrong

    • @ameteksolidstatecontrols4657
      @ameteksolidstatecontrols4657 Před 2 lety

      For clarification or any questions please email sci.marketing@ametek.com and we will connect you with someone to answer your questions.

  • @alishafi9272
    @alishafi9272 Před 2 lety

    amazing that how from very simple ideas, you easily explain complex topics. Thanks. Looking forward to more webinars

  • @alishafi1
    @alishafi1 Před 3 lety

    thanks sir, learnt alot

  • @alishafi9272
    @alishafi9272 Před 3 lety

    thanks sir, learnt alot (power electronics, control system all in one hour), certainly made my life easire :)

  • @inamaman9891
    @inamaman9891 Před 3 lety

    I have the the arrangement where two sources are connected on the same battery bank 12* 4 =48 volts. One is solar through a charge controller , the other source is a rectifier connected to the load as well which source would charge the batteries and drive the load ?

    • @ameteksolidstatecontrols4657
      @ameteksolidstatecontrols4657 Před 3 lety

      Please email your questions to sci.marketing@ametek.com and we will connect you with someone to answer your questions.

  • @hoxuanloca7707
    @hoxuanloca7707 Před 3 lety

    Great video, thank you so much, sir!

  • @UudFlix
    @UudFlix Před 3 lety

    50:59 Would you please give me scheme diagram about ups

    • @UudFlix
      @UudFlix Před 3 lety

      My UPS have alarm signal with "charging out of order" What your solution about this problem, Thanks a lot...

    • @ameteksolidstatecontrols4657
      @ameteksolidstatecontrols4657 Před 3 lety

      Thank you for commenting, please email your questions to sci.marketing@ametek.com and I will connect you with someone to answer your questions.

  • @rfans4
    @rfans4 Před 3 lety

    07:26 what function of external transformer in UPS? for motor load did we also need transformer?

    • @ameteksolidstatecontrols4657
      @ameteksolidstatecontrols4657 Před 3 lety

      Thank you for watching the video and commenting! Please email your questions to sci.marketing@ametek.com and we will connect you with someone to answer your questions.

    • @karbonphiber
      @karbonphiber Před 2 lety

      Function of the external transformer is to step up/down voltage, or derive a neutral source, or create a solid ground source for the ups. Not ideal to place motor load on ups as it will overload it during startup due to high in rush

    • @AMMOHL
      @AMMOHL Před rokem

      Isolation of the inverter or electronic system in the inverter against inrush currents arising from industrial loads. Basically, it is for safety purposes of the UPS systems.

  • @georgestracey4139
    @georgestracey4139 Před 3 lety

    cool

  • @ametekprestolitepowerprodu744

    Good video